ISO 9001:2015 certified industrial automation spare parts supplier

Yokogawa AAI135-H50 8-Channel HART Analog Input Module

Yokogawa AAI135-H50 is an eight-channel, channel-isolated 4–20 mA input module for CENTUM FIO systems. It combines process-current acquisition with HART communication and supports dual-redundant module configurations.

Version check: Confirm -H50, channel isolation, hardware Style and the installed terminal adapter; -S versions do not provide HART.

Download
  • Yokogawa AAI135-H50 8-Channel HART Analog Input Module

    Yokogawa AAI135-H50 brings eight 4–20 mA field measurements into a CENTUM FIO control system. It is intended for process transmitters where each input requires isolation from the system and from the other channels. The HART version carries the analog process value while providing access to digital information from compatible field instruments. AAI135-H50 also supports dual-redundant configurations, making its channel isolation, transmitter requirements and installed redundancy arrangement important checks when selecting a maintenance spare.

    Hardware specifications. AAI135-H50 provides eight inputs with a 10 ms data update period and ±16 µA accuracy. The allowable input current is 25 mA. Transmitter supply is at least 15.0 V at 20 mA; available voltage must account for cable drop. Maximum module consumption is 360 mA at 5 V DC and 450 mA at 24 V DC. The basic module measures 32.8 × 130 × 107.5 mm (W × H × D).

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model AAI135-H50
    Dimensions (W × H × D) 32.8 × 130 × 107.5 mm; module only

    Functional Configuration

    Function Analog input with HART communication
    Input channels 8; isolated between channels and from the system
    Input signal 4–20 mA DC
    Redundancy Dual-redundant configuration supported

    Performance & Power

    Allowable input current 25 mA
    Accuracy ±16 µA
    Data update period 10 ms
    Transmitter supply At least 15.0 V at 20 mA; allow for wiring voltage drop
    Maximum current consumption 360 mA at 5 V DC; 450 mA at 24 V DC

    Environment

    Protection option Standard version without explosion protection

    Compatibility & Selection Guide

    System compatibility. AAI135-H50 is part of the CENTUM FIO family. The Release 6 application environment includes AFV30/AFV40 field control stations with VP6F1700 control functions and VP6E5100 engineering. Preserve the complete -H50 code when replacing a module: H identifies HART, 5 identifies the non-explosion-protected version and 0 the basic type. Confirm the installed system release and terminal-adapter option.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to AAI135-H50.

    Signal and connection checks

    Item Requirement Check
    Signal 4–20 mA DC Maximum allowable current 25 mA
    Transmitter supply ≥15.0 V at 20 mA Allow for cable voltage drop
    Barrier selection Isolation barrier Do not connect a Zener barrier

    View connection specifications (PDF)

    Module fit and configuration

    1. Confirm the system position.

      Match the field control unit, node type, complete module code and existing configuration before replacement.

    2. Match termination and dimensions.

      Use the specified terminal/cable interface and check the module envelope against the installed assembly.

    3. Verify the configured function.

      Confirm -H50, channel isolation, hardware Style and the installed terminal adapter; -S versions do not provide HART.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Do not connect a Zener barrier. Use the appropriate isolation barrier for an intrinsically safe application.

    • Choose the specified terminal or cable interface; cable electrical ratings can limit the complete installation isolation rating.

    Frequently Asked Questions

    What does AAI135-H50 do in a CENTUM system?

    It receives eight 4–20 mA process signals and transfers them to the FIO control system. The -H version also supports HART communication with compatible field instruments.

    Are the channels of AAI135-H50 individually isolated?

    Yes. Its eight inputs are isolated both from the system and from one another. This differs from modules described only as isolated between field signals and the system.

    Does AAI135-H50 support HART?

    Yes. The H suffix identifies the HART communication version. A standard -S version is not an equivalent choice when HART functions are required.

    What signal range can AAI135-H50 receive?

    Its nominal input range is 4–20 mA DC, with an allowable input current of 25 mA.

    How quickly does AAI135-H50 update its measurements?

    The data update period is 10 ms. This is the module update interval, not a guarantee of the complete control-loop response time.

    Can AAI135-H50 supply a two-wire transmitter?

    The transmitter supply is at least 15.0 V at 20 mA and no more than 29.3 V at zero current. Check the transmitter minimum operating voltage after allowing for external wiring drop.

    Can AAI135-H50 connect directly to a Zener barrier?

    No. Use an isolation barrier for intrinsically safe applications; a Zener barrier must not be connected to this module.

    Can AAI135-H50 operate in a redundant pair?

    Yes. It supports dual-redundant configurations. Match the module specification and the single or dual terminal arrangement to the installed design.

    Which terminal option should be checked for AAI135-H50?

    Check the actual ordered option and existing termination. Available choices include ATI3S-00 single pressure-clamp, ATI3D-00 dual pressure-clamp, ATI3A-00 and ATK4A-00 cable-interface adapters; the base code alone does not include a particular adapter.

    Manufacturer Documentation

    AAI135-H50 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 5 pages · 99.4 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33J60F60-01EN, 6th Edition, 2017-03-20.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa AAI135-H50

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.