ISO 9001:2015 certified industrial automation spare parts supplier

Yokogawa AAI543-H50 16-Channel HART Analog Output Module

Yokogawa AAI543-H50 is a 16-channel isolated 4–20 mA output module for CENTUM FIO. It supports HART communication and standard-response switching in a dual-redundant configuration.

Version check: Match the -H50 standard switchover response, hardware Style and terminal option; a redundant pair must use the same response class.

Download
  • Yokogawa AAI543-H50 16-Channel HART Analog Output Module

    Yokogawa AAI543-H50 delivers sixteen 4–20 mA control outputs from a CENTUM FIO system to compatible field devices, including control devices that use HART communication. It is suited to process-output duties where the analog command and digital instrument information are both needed. The module supports dual-redundant operation, but AAI543-H50 is the standard switchover-response version. Matching this response class matters when replacing one member of an installed redundant pair.

    Hardware specifications. AAI543-H50 provides 16 isolated current outputs with a permitted load resistance of 0–750 Ω, ±48 µA accuracy and a 10 ms data update period. Open-circuit detection is below 0.65 mA. Maximum consumption is 230 mA at 5 V DC and 540 mA at 24 V DC. Dimensions are 32.8 × 130 × 107.5 mm (W × H × D), excluding the chosen terminal adapter.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model AAI543-H50
    Dimensions (W × H × D) 32.8 × 130 × 107.5 mm; module only

    Functional Configuration

    Function Analog output with HART communication
    Output channels 16; isolated output module
    Output signal 4–20 mA DC
    Open-circuit detection Less than 0.65 mA
    Redundancy response Standard; output below 4 mA during switchover for 100 ms maximum

    Performance & Power

    Allowable load resistance 0–750 Ω
    Accuracy ±48 µA
    Data update period 10 ms
    Maximum current consumption 230 mA at 5 V DC; 540 mA at 24 V DC

    Environment

    Protection option Standard response version without explosion protection

    Compatibility & Selection Guide

    System compatibility. AAI543-H50 is a CENTUM FIO module; the Release 6 environment includes AFV30/AFV40 stations with VP6F1700 and VP6E5100 engineering. In a redundant arrangement, use two modules with the same switchover response. The H50 code identifies HART, standard response without explosion protection and the basic type; it must not be substituted by code resemblance alone.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to AAI543-H50.

    Signal and connection checks

    Item Requirement Check
    Output loop 4–20 mA DC Total load 0–750 Ω
    Open circuit Below 0.65 mA Review output-loop continuity
    Redundant pair Same response class Standard response for -H50

    View connection specifications (PDF)

    Module fit and configuration

    1. Confirm the system position.

      Match the field control unit, node type, complete module code and existing configuration before replacement.

    2. Match termination and dimensions.

      Use the specified terminal/cable interface and check the module envelope against the installed assembly.

    3. Verify the configured function.

      Match the -H50 standard switchover response, hardware Style and terminal option; a redundant pair must use the same response class.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Match the response class of both redundant modules before replacement.

    • Verify loop load and the exact terminal/cable option; cable electrical ratings can limit the complete installation isolation rating.

    Frequently Asked Questions

    What is the function of AAI543-H50?

    It provides sixteen isolated 4–20 mA analog outputs from a CENTUM FIO control system to field devices.

    Does AAI543-H50 support HART devices?

    Yes. The H suffix selects HART communication, allowing analog output operation and access to digital information from compatible field instruments.

    What load can AAI543-H50 drive?

    The allowable load resistance is 0–750 Ω for its 4–20 mA outputs. Include the full connected loop burden when checking this limit.

    Is AAI543-H50 the fast-switchover version?

    No. It has the standard switchover response. During redundant-module switchover, output may fall below 4 mA for up to 100 ms.

    Can AAI543-H50 be paired with a different switchover-response version?

    A redundant pair must use two modules with the same switchover response. Do not mix response classes simply because their channel count and current range match.

    How accurate are the outputs of AAI543-H50?

    Output accuracy is ±48 µA. The data update period is 10 ms.

    How does AAI543-H50 detect an open output circuit?

    Its circuit-open detection threshold is below 0.65 mA. Check the connected loop and the configured system diagnostics when investigating an open-circuit indication.

    Which termination options are available for AAI543-H50?

    Options include ATA4S-00 single pressure-clamp, ATA4D-00 dual pressure-clamp and ATK4A-00 cable-interface hardware. Confirm the complete ordered option and what is included with the offered unit.

    What does the complete AAI543-H50 suffix identify?

    H identifies HART communication, 5 selects standard switchover response without explosion protection, and 0 selects the basic type.

    Manufacturer Documentation

    AAI543-H50 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 5 pages · 108.0 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33J60F60-01EN, 6th Edition, 2017-03-20.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa AAI543-H50

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message