ISO 9001:2015 certified industrial automation spare parts supplier

Yokogawa AAI841-H00 8-Input 8-Output HART Analog I/O Module

Yokogawa AAI841-H00 is a non-isolated FIO module with eight 4–20 mA inputs and eight 4–20 mA outputs. It supports up to eight loops, HART communication and dual-redundant configurations.

Version check: Confirm the legacy -H00 code, hardware Style, node and terminal option; HART in an ER-bus remote node requires EB401 Rev. 2 or later.

Download
  • Yokogawa AAI841-H00 8-Input 8-Output HART Analog I/O Module

    Yokogawa AAI841-H00 combines eight analog inputs and eight analog outputs in one CENTUM FIO module, supporting up to eight process loops. Both sides use 4–20 mA signals, so it can receive transmitter measurements and deliver current commands within the same module footprint. The H version supports HART communication and the module can operate in a dual-redundant arrangement. AAI841-H00 is non-isolated, making signal isolation and the exact legacy H00 suffix essential checks for a replacement purchase.

    Hardware specifications. AAI841-H00 has eight 4–20 mA inputs and eight 4–20 mA outputs with a 10 ms update period. Input accuracy is ±16 µA and output accuracy is ±48 µA. Normal output load resistance is 0–750 Ω; a specified 60–70 °C node environment requires 200–750 Ω. Maximum consumption is 310 mA at 5 V DC and 500 mA at 24 V DC.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model AAI841-H00
    Dimensions (W × H × D) 32.8 × 130 × 107.5 mm; module only

    Functional Configuration

    Function Combined analog input/output with HART
    Channels 8 inputs and 8 outputs; up to 8 loops
    Isolation Non-isolated
    Signals Input: 4–20 mA DC; output: 4–20 mA DC

    Performance & Power

    Allowable input current 25 mA
    Accuracy Input ±16 µA; output ±48 µA
    Data update period 10 ms
    Output load resistance 0–750 Ω; 200–750 Ω for the specified 60–70 °C node environment
    Maximum current consumption 310 mA at 5 V DC; 500 mA at 24 V DC

    Environment

    Conditional ambient/output load 200–750 Ω at 60–70 °C when installed in the specified high-temperature node

    Compatibility & Selection Guide

    System compatibility. AAI841-H00 is covered by the legacy CENTUM VP FIO specification for ANB10, ANR10, AFF50 and AFV10 arrangements. HART operation in an ER-bus remote node requires EB401 firmware Rev. 2 or later. Match the installed release, node, hardware Style and terminal option; later H50 ordering tables must not be used to redefine this H00 product.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to AAI841-H00.

    Signal and connection checks

    Item Requirement Check
    Input 4–20 mA DC Select two-wire/four-wire per channel
    Output 4–20 mA DC 0–750 Ω; temperature condition applies
    Remote HART EB401 Rev. 2 or later Verify the installed remote-node firmware

    View connection specifications (PDF)

    Module fit and configuration

    1. Confirm the system position.

      Match the field control unit, node type, complete module code and existing configuration before replacement.

    2. Match termination and dimensions.

      Use the specified terminal/cable interface and check the module envelope against the installed assembly.

    3. Verify the configured function.

      Confirm the legacy -H00 code, hardware Style, node and terminal option; HART in an ER-bus remote node requires EB401 Rev. 2 or later.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Do not connect a Zener barrier; use a suitable isolation barrier for intrinsically safe applications.

    • Use the 200–750 Ω output-load range when the specified node temperature condition is 60–70 °C.

    Frequently Asked Questions

    Is AAI841-H00 an input module or an output module?

    It combines both functions: eight 4–20 mA inputs and eight 4–20 mA outputs, supporting up to eight loops.

    Are the channels of AAI841-H00 isolated?

    No. AAI841-H00 is a non-isolated analog I/O module. Do not select it for a duty that requires channel isolation without reviewing the system design.

    Does AAI841-H00 support HART?

    Yes. H identifies the HART communication version. For HART operation in an ER-bus remote node, EB401 firmware must be Rev. 2 or later.

    What output load is permitted for AAI841-H00?

    The normal range is 0–750 Ω. When used in the specified 60–70 °C node environment, the permitted range is 200–750 Ω.

    Can AAI841-H00 connect to two-wire and four-wire transmitters?

    Yes. Each input channel has a setting pin for selecting the two-wire or four-wire transmitter arrangement.

    What accuracy does AAI841-H00 provide?

    Input accuracy is ±16 µA and output accuracy is ±48 µA. The data update period is 10 ms.

    Can AAI841-H00 be connected to a Zener barrier?

    No. Use an isolation barrier if an intrinsically safe application is required; this module does not allow a Zener barrier connection.

    Can AAI841-H00 be used in a redundant configuration?

    Yes. It supports dual-redundant operation. Match the existing module, node, release and the single or dual termination arrangement.

    Can AAI841-H00 be replaced solely by matching the AAI841 base model?

    No. Preserve the complete H00 suffix and check the hardware Style, system release, terminal option and HART requirements before accepting a different ordering code.

    Manufacturer Documentation

    AAI841-H00 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 5 pages · 112.9 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33M50F30-40E, 5th Edition, 2010-08-01.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa AAI841-H00

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message