Yokogawa AAP135-S50 8-Channel Isolated Pulse Input Module

Yokogawa AAP135-S50 is an eight-channel isolated pulse input module for CENTUM FIO. It accepts contact, voltage-pulse and current-pulse signals, with frequency limits determined by the selected signal and redundancy configuration.

Version check: Match pulse source, frequency, transmitter supply and redundancy mode; dry-contact limits are lower than the 10 kHz electronic-pulse limit.

Download
  • Yokogawa AAP135-S50 8-Channel Isolated Pulse Input Module

    Yokogawa AAP135-S50 collects pulse signals from field devices and makes them available to a CENTUM FIO control system. Its eight channels are isolated from the system and from one another, supporting pulse-count duties with contact, voltage-pulse or current-pulse sources. The module can provide transmitter power and can be used in a dual-redundant configuration. AAP135-S50 selection depends on the actual pulse waveform and frequency: the maximum electronic-pulse rate must not be applied indiscriminately to dry-contact inputs.

    Hardware specifications. AAP135-S50 offers eight isolated channels, a 2 ms data update period and an electronic-pulse range up to 10 kHz subject to signal conditions. The minimum specified pulse width is 40 µs. Selectable transmitter power is 12 V or 24 V DC. Dry-contact inputs between B and C have lower limits: 800 Hz for single and 600 Hz for dual-redundant operation.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model AAP135-S50
    Dimensions (W × H × D) 32.8 × 130 × 107.5 mm; module only

    Functional Configuration

    Function Pulse input
    Channels 8; isolated between channels and from the system
    Supported signals Contact ON/OFF, voltage pulse and current pulse
    Dry contact at B/C Single: 0–800 Hz; dual redundant: 0–600 Hz

    Performance & Power

    Electronic-pulse range 0–10 kHz; subject to specified signal conditions
    Minimum pulse width 40 µs; dry-contact conditions differ
    Data update period 2 ms
    Transmitter supply Selectable 12 V or 24 V DC
    Maximum current consumption 300 mA at 5 V DC; 400 mA at 24 V DC

    Environment

    Protection option Standard version without explosion protection

    Compatibility & Selection Guide

    System compatibility. AAP135-S50 belongs to CENTUM FIO. The Release 6 environment includes AFV30/AFV40 stations with VP6F1700 and VP6E5100 engineering. Match the source type, frequency, pulse width, filter and transmitter supply to the configured channel. The S50 suffix selects the standard, non-explosion-protected basic version; choose the correct single or dual terminal option separately.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to AAP135-S50.

    Signal and connection checks

    Item Requirement Check
    Electronic pulses Up to 10 kHz Minimum pulse width 40 µs; signal conditions apply
    Dry contact B/C 800 Hz single / 600 Hz dual Minimum pulse width 625 / 833 µs
    Transmitter supply 12 V / 24 V DC Current limits 40 / 30 mA

    View connection specifications (PDF)

    Module fit and configuration

    1. Confirm the system position.

      Match the field control unit, node type, complete module code and existing configuration before replacement.

    2. Match termination and dimensions.

      Use the specified terminal/cable interface and check the module envelope against the installed assembly.

    3. Verify the configured function.

      Match pulse source, frequency, transmitter supply and redundancy mode; dry-contact limits are lower than the 10 kHz electronic-pulse limit.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Do not apply the 10 kHz rating to dry-contact wiring without checking its separate limits.

    • Match the transmitter supply and input conditioning to the actual source; cable capacitance can further reduce usable contact-input frequency.

    Frequently Asked Questions

    What signal types does AAP135-S50 accept?

    It accepts two-wire contact ON/OFF, voltage-pulse and current-pulse signals, and three-wire power-supply-type voltage-pulse signals.

    Are the eight channels of AAP135-S50 isolated?

    Yes. Isolation is provided between field signals and the system and between individual channels.

    Can every AAP135-S50 input run at 10 kHz?

    No. The 0–10 kHz range is subject to signal conditions. Dry-contact input between B and C is limited to 800 Hz in a single configuration and 600 Hz in a dual-redundant configuration.

    What minimum pulse width applies to AAP135-S50?

    The electronic-pulse minimum is 40 µs. For the specified dry-contact B/C connection, the minimum is 625 µs in single operation and 833 µs in dual-redundant operation.

    Can AAP135-S50 power a transmitter?

    Yes. Its selectable transmitter supply is 12 V or 24 V DC. The respective current limits are 40 mA and 30 mA.

    How quickly does AAP135-S50 update data?

    The data update period is 2 ms. The usable input rate still depends on the pulse waveform, source and configured input arrangement.

    Does AAP135-S50 provide contact-chatter filtering?

    A chatter filter is available for mechanical contact inputs with input frequency up to 10 Hz. Apply it only where that operating condition is appropriate.

    Can AAP135-S50 be installed in a redundant configuration?

    Yes. Dual-redundant operation is supported. Check the lower dry-contact frequency limit and the matching dual termination hardware.

    What should be confirmed when ordering AAP135-S50?

    Confirm the complete S50 suffix, hardware Style, pulse source and frequency, transmitter supply selection and terminal-adapter option. These conditions determine whether the module fits the existing pulse-count application.

    Manufacturer Documentation

    AAP135-S50 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 5 pages · 100.6 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33J60F60-01EN, 6th Edition, 2017-03-20.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa AAP135-S50

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.