Yokogawa ALR121-S50 2-Port RS-422 RS-485 Communication Module

Yokogawa ALR121-S50 is a two-port RS-422/RS-485 serial communication module for CENTUM N-IO/FIO systems. It exchanges subsystem data with the FCS using supported functions such as Modbus RTU and FA-M3 communication.

Version check: Confirm RS-422/RS-485, the common protocol selected for both ports, baud rate, data mapping and the installed redundancy arrangement.

Download
  • Yokogawa ALR121-S50 2-Port RS-422 RS-485 Communication Module

    Yokogawa ALR121-S50 connects serial subsystems to a CENTUM field control station, allowing external device data to be used within the process-control system. It provides two RS-422/RS-485 ports for supported communication functions including Modbus RTU and FA-M3. Both ports use the same selected communication function, rather than acting as two independently programmable protocol gateways. ALR121-S50 can also participate in supported redundant-module arrangements, making protocol, baud rate and redundancy design central to replacement selection.

    Hardware specifications. ALR121-S50 provides two half-duplex serial ports with point-to-point RS-422 or multipoint RS-485 connection. Maximum total transmission distance is 1200 m. Supported speed depends on protocol: Modbus uses 1200–19200 bps, while specified FA-M3 configurations can use 38400 bps. Wiring uses two five-pole M4 screw-terminal groups. Current consumption is 0.5 A; module dimensions are 32.8 × 130 × 142.9 mm.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model ALR121-S50
    Dimensions (W × H × D) 32.8 × 130 × 142.9 mm

    Functional Configuration

    Function Serial subsystem communication
    Interfaces 2 × RS-422/RS-485
    Transmission Half duplex; start-stop synchronization
    Connections RS-422 point-to-point; RS-485 multipoint
    Modbus protocol / stations RTU; maximum 30 subsystem stations per port
    Port-function rule Both ports use the same communication function
    Wiring terminals M4 screws; 5 poles × 2

    Performance & Power

    Maximum transmission distance 1200 m total
    Modbus speed 1200 / 2400 / 4800 / 9600 / 19200 bps
    Current consumption 0.5 A

    Environment

    Protection option Standard version without explosion protection

    Compatibility & Selection Guide

    System compatibility. ALR121-S50 operates with the applicable AFV30/AFV40, A2FV50 and A2FV70 field control stations and corresponding VP6F1700/1800/1900 control functions. Engineering uses VP6E5100. Modbus RTU supports up to 30 subsystem stations per port. Verify the subsystem driver, data mapping and redundancy support; two ports on one module do not themselves create a redundant pair.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to ALR121-S50.

    Signal and connection checks

    Item Requirement Check
    Interface RS-422 / RS-485 Use the configured connection method
    Terminals 5 poles × 2; M4 screws Use specified shielded cable or AKB161/162
    Bus distance 1200 m maximum total Match subsystem and cable requirements

    View connection specifications (PDF)

    Module fit and configuration

    1. Confirm the system position.

      Match the field control unit, node type, complete module code and existing configuration before replacement.

    2. Match termination and dimensions.

      Use the specified terminal/cable interface and check the module envelope against the installed assembly.

    3. Verify the configured function.

      Confirm RS-422/RS-485, the common protocol selected for both ports, baud rate, data mapping and the installed redundancy arrangement.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Use the same communication function on both ports of one module.

    • Check the complete redundant-module and slot arrangement; one-shot data writing is unavailable during dual-redundant operation.

    Frequently Asked Questions

    Which interfaces does ALR121-S50 provide?

    It provides two RS-422/RS-485 serial ports. RS-422 supports point-to-point connection and RS-485 supports multipoint connection.

    Does ALR121-S50 support Modbus RTU?

    Yes. It supports Modbus RTU communication with applicable serial-interface subsystems, with up to 30 subsystem stations per port.

    Can ALR121-S50 run different protocols on its two ports?

    No. Both ports on the same module use the same communication function. The communication functions cannot be specified independently for the two ports.

    What Modbus baud rates does ALR121-S50 support?

    Modbus communication supports 1200, 2400, 4800, 9600 and 19200 bps. Do not apply the 38400 bps FA-M3 capability to Modbus.

    What is the maximum cable distance for ALR121-S50?

    The maximum total transmission distance is 1200 m. The chosen subsystem, cable and connection arrangement must also meet their applicable requirements.

    Does one ALR121-S50 provide a redundant pair because it has two ports?

    No. Redundant communication requires the supported two-module arrangement. During redundant switchover, both ports on the module switch together.

    Where are paired ALR121-S50 modules placed for redundancy?

    The pair is installed in adjacent odd/even slots in the same node or field-control-unit arrangement. Verify the supported communication function and system configuration before pairing.

    Which engineering environment is used for ALR121-S50?

    The Release 6 environment uses VP6E5100 Standard Builder Function and the control function appropriate to the installed AFV30/AFV40, A2FV50 or A2FV70 field control station.

    What should be confirmed before replacing ALR121-S50?

    Confirm the complete S50 code, hardware Style, RS-422/RS-485 interface, protocol and baud rate, subsystem address/data mapping, terminal wiring and redundancy configuration.

    Manufacturer Documentation

    ALR121-S50 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 6 pages · 121.4 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33J60G10-01EN, 5th Edition, 2019-07-18.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa ALR121-S50

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.