ISO 9001:2015 certified industrial automation spare parts supplier

Yokogawa EC401-50 1-Port ESB Bus Coupler Module

Yokogawa EC401-50 is a one-port ESB bus coupler for CENTUM N-IO/FIO. It links the field control unit to supported ESB nodes at 128 Mbps and supports single or dual-redundant module arrangements.

Version check: For a CP471 system, require EC401 Style S3 or later; also match the one-port ESB topology, node types and redundancy arrangement.

Download
  • Yokogawa EC401-50 1-Port ESB Bus Coupler Module

    Yokogawa EC401-50 provides the ESB communication link between a CENTUM field control unit and supported I/O nodes, allowing field I/O data to pass through the system bus. Its single front ESB port serves one node connection path, and the module can be used in a single or dual-redundant arrangement. EC401-50 is an ESB bus coupler, not an Ethernet switch or a field analog I/O card. The hardware Style is particularly important when it is used with a CP471 processor.

    Hardware specifications. EC401-50 transfers I/O data at 128 Mbps and provides one ESB bus port. The maximum ESB cable length is 10 m, and up to nine specified ESB node/interface units can be connected. Current consumption is 0.5 A. Dimensions are 32.8 × 130 × 129.5 mm (W × H × D). The -50 code identifies the standard non-explosion-protected basic type.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model EC401-50
    Dimensions (W × H × D) 32.8 × 130 × 129.5 mm

    Functional Configuration

    Function ESB bus coupler for N-IO/FIO
    Ports 1 ESB bus port
    Maximum connected nodes 9 specified node/interface units
    Applicable node/interface types ANB10S/D, ANT401, ANT411, ANT421
    CP471 compatibility EC401 hardware Style S3 or later
    Single / redundant arrangement Single module in slot 7; redundant modules in slots 7 and 8

    Performance & Power

    I/O data transmission speed 128 Mbps
    Maximum ESB cable length 10 m
    Current consumption 0.5 A

    Environment

    Protection option Standard version without explosion protection

    Compatibility & Selection Guide

    System compatibility. EC401-50 supports the specified AFV30/AFV40, A2FV50 and A2FV70 field control units. A CP471 configuration requires EC401 hardware Style S3 or later. For the supported SEM function on Vnet/IP, EC401 Style 2 or later is required. Confirm the processor, system release, connected node types and redundancy arrangement before selecting a spare.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to EC401-50.

    Signal and connection checks

    Item Requirement Check
    ESB port One bus port Use the specified ESB cable
    Cable length 10 m maximum Check the complete ESB cable run
    Node count Up to 9 Only the specified node/interface types

    View connection specifications (PDF)

    Module fit and configuration

    1. Single configuration.

      Install the coupler in slot 7 with the specified dummy module in slot 8.

    2. Dual-redundant configuration.

      Use the specified pair in slots 7 and 8; confirm the existing node and bus arrangement.

    3. Check the system conditions.

      For a CP471 system, require EC401 Style S3 or later; also match the one-port ESB topology, node types and redundancy arrangement.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Verify EC401 Style S3 or later when the processor is CP471.

    • In a single configuration use slot 7 with the specified dummy module in slot 8; use slots 7 and 8 for the redundant arrangement.

    Frequently Asked Questions

    What does EC401-50 connect?

    It links a supported CENTUM field control unit to ESB-bus node/interface units for I/O-data communication.

    How many ESB ports does EC401-50 have?

    It has one ESB bus port. Do not confuse it with the two-port EC402 arrangement.

    What is the I/O-data rate of EC401-50?

    The ESB I/O-data transmission speed is 128 Mbps.

    What is the maximum ESB cable length for EC401-50?

    The maximum ESB bus cable length is 10 m.

    How many nodes can EC401-50 connect?

    It supports up to nine specified node/interface units. The listed types are ANB10S/D, ANT401, ANT411 and ANT421.

    Which EC401-50 hardware Style is needed with CP471?

    CP471 requires an EC401 with hardware Style S3 or later. Check the offered unit’s nameplate rather than relying only on the EC401-50 model code.

    Where is EC401-50 placed in a single configuration?

    The module occupies slot 7. Slot 8 is fitted with a dummy module in the specified single configuration.

    How is EC401-50 configured for dual redundancy?

    Use the specified two-module arrangement in slots 7 and 8. Confirm the existing field-control-unit and node configuration before replacement.

    What should be checked before buying EC401-50?

    Confirm the complete -50 code, hardware Style, processor type, system release, connected node/interface types and single or redundant arrangement. CP471 and SEM functions have specific Style requirements.

    Manufacturer Documentation

    EC401-50 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 4 pages · 86.2 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33J60E50-01EN, 5th Edition, 2020-11-05.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa EC401-50

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.