ISO 9001:2015 certified industrial automation spare parts supplier

Yokogawa AAI143-H50 16-Channel HART Analog Input Module

Yokogawa AAI143-H50 is a 16-channel isolated 4–20 mA input module for CENTUM FIO. It supports HART communication, per-channel two-wire or four-wire transmitter selection and dual-redundant configurations.

Version check: Confirm -H50, hardware Style, two-wire/four-wire channel settings and the existing single or dual terminal adapter.

Download
  • Yokogawa AAI143-H50 16-Channel HART Analog Input Module

    Yokogawa AAI143-H50 connects sixteen 4–20 mA transmitter signals to a CENTUM FIO control system, providing a compact input interface for process measurement. Its HART capability combines analog measurement with digital communication to compatible instruments. Each channel can be configured for a two-wire or four-wire transmitter using its setting pin, and the module supports dual-redundant arrangements. AAI143-H50 is an input module, so it should be distinguished from similarly named output modules when ordering replacement cards.

    Hardware specifications. AAI143-H50 has 16 isolated inputs, ±16 µA accuracy and a 10 ms data update period. The allowable input current is 24 mA. Transmitter supply is at least 19 V at 20 mA, with a 25 mA output current limit. Maximum consumption is 230 mA at 5 V DC and 540 mA at 24 V DC. Module dimensions are 32.8 × 130 × 107.5 mm (W × H × D).

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Yokogawa
    Complete model AAI143-H50
    Dimensions (W × H × D) 32.8 × 130 × 107.5 mm; module only

    Functional Configuration

    Function Analog input with HART communication
    Input channels 16; isolated input module
    Input signal 4–20 mA DC
    Transmitter selection Two-wire or four-wire; setting pin per channel

    Performance & Power

    Allowable input current 24 mA
    Accuracy ±16 µA
    Data update period 10 ms
    Transmitter supply ≥19 V at 20 mA; current limit 25 mA
    Maximum current consumption 230 mA at 5 V DC; 540 mA at 24 V DC

    Environment

    Protection option Standard version without explosion protection

    Compatibility & Selection Guide

    System compatibility. AAI143-H50 belongs to the CENTUM FIO platform. The Release 6 environment includes AFV30/AFV40 field control stations, VP6F1700 control functions and VP6E5100 engineering. The -H50 code selects HART, no explosion protection and the basic type. Replacement checks must include system release, hardware Style, transmitter configuration and the exact terminal-adapter option.

    Wiring & Installation Reference

    Use the matching Yokogawa system and connection instructions for the installed assembly. The checks below are specific to AAI143-H50.

    Signal and connection checks

    Item Requirement Check
    Signal 4–20 mA DC Allowable input current 24 mA
    Channel setting Two-wire / four-wire Set each channel for its transmitter
    Supply budget ≥19 V at 20 mA Include external wiring drop

    View connection specifications (PDF)

    Module fit and configuration

    1. Confirm the system position.

      Match the field control unit, node type, complete module code and existing configuration before replacement.

    2. Match termination and dimensions.

      Use the specified terminal/cable interface and check the module envelope against the installed assembly.

    3. Verify the configured function.

      Confirm -H50, hardware Style, two-wire/four-wire channel settings and the existing single or dual terminal adapter.

    View mounting dimensions (PDF)

    Power and handling precautions

    • Use an isolation barrier when an intrinsically safe interface is required; do not connect a Zener barrier.

    • Confirm each transmitter setting and the selected terminal adapter before applying field power.

    Frequently Asked Questions

    Is AAI143-H50 an input or output module?

    It is a 16-channel 4–20 mA analog input module. It receives transmitter signals; it is not the corresponding analog output module.

    Does AAI143-H50 include HART communication?

    Yes. H identifies the HART version. The -S version must not be treated as equivalent when digital HART communication is required.

    Can AAI143-H50 accept both two-wire and four-wire transmitters?

    Yes. A setting pin selects the transmitter arrangement separately for each channel. Match these settings to the connected instruments.

    What are the input limits of AAI143-H50?

    The nominal signal is 4–20 mA DC and the allowable input current is 24 mA. Do not use an output-module load specification as an input limit.

    What accuracy and update period does AAI143-H50 provide?

    Input accuracy is ±16 µA and the data update period is 10 ms. Overall measurement performance also depends on the field instrument and installation.

    How much transmitter voltage does AAI143-H50 provide?

    It provides at least 19 V at 20 mA and no more than 25.5 V at zero current. Its output current limit is 25 mA; allow for voltage lost in the field wiring.

    Can AAI143-H50 be used with a Zener barrier?

    No. Use an isolation barrier for intrinsically safe applications. A Zener barrier must not be connected to AAI143-H50.

    Can AAI143-H50 be used in a dual-redundant configuration?

    Yes. Use the matching redundancy arrangement and terminal hardware. The available terminal options include ATA4S-00 for single and ATA4D-00 for dual pressure-clamp termination.

    What should be matched before replacing AAI143-H50?

    Match the complete -H50 code, hardware Style, installed system release, channel transmitter settings and terminal-adapter option. A matching front connector alone does not establish interchangeability.

    Manufacturer Documentation

    AAI143-H50 Product Reference

    Product photograph, model identification and compatibility notes, followed by selected Yokogawa pages covering specifications, dimensions and ordering codes.

    PDF · 5 pages · 106.2 KB · Compiled by EWOLO CONTROL. Manufacturer extracts: GS 33J60F60-01EN, 6th Edition, 2017-03-20.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Yokogawa AAI143-H50

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.