ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T9882 AADvance Dual Analog Output Termination Assembly

ICS Triplex T9882 is an AADvance dual analog output termination assembly. It provides eight field-output connections and supports two compatible analog output modules for a redundant output arrangement.

Version check: Confirm T9882 dual analog-output termination, the matched T9481/T9482 module arrangement, coding pegs and field-loop polarity before replacement.

Download
  • ICS Triplex T9882 AADvance Dual Analog Output Termination Assembly

    ICS Triplex T9882 is the dual analog-output termination assembly for an AADvance system, connecting a redundant pair of compatible analog output modules to the same field-output circuits. It provides eight field connection positions and forms the physical interface between the module pair and the controlled loops. In a dual arrangement, the associated output modules share the required loop current; T9882 provides their common termination rather than generating the output signal itself. Current regulation, diagnostics and output-state control remain functions of the analog output modules, making the distinction between this assembly and an active output module important when selecting a replacement.

    Hardware specifications. T9882 has eight field-output connections and supports two modules. Its assembly dimensions are 132 × 84 mm, and the field terminals accept conductors up to 1.31 mm² (16 AWG) with a 6 mm stripping length. Channel-isolation withstand is ±1.5 kV DC for one minute.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T9882
    Platform AADvance
    Product type Analog output termination assembly
    Dimensions, height × width 132 × 84 mm
    Base system AADvance I/O base arrangement

    Functional Configuration

    Redundancy arrangement Dual
    Field connections 8
    Output modules supported 2
    Compatible output family AADvance T9481 / T9482
    Maximum conductor cross-section 1.31 mm² (16 AWG)
    Conductor stripping length 6 mm

    Performance & Power

    Channel-isolation withstand ±1.5 kV DC for 1 minute

    Environment

    Installation enclosure AADvance open-type assembly requires an enclosure with adequate cooling and access clearance

    Compatibility & Selection Guide

    System compatibility. Use T9882 with the approved AADvance T9481/T9482 analog-output arrangement and matching I/O base. These output modules use current-sink circuits; in dual operation the two modules share the demanded current. Confirm module pairing, application fail-state settings and field-loop design before substitution.

    Wiring & Installation Reference

    The terminal diagram is from Rockwell Automation System Build Manual ICSTT-RM448N-EN-P, p. 111.

    Analog-output field connections

    Connection Requirement Check
    Field outputs 8 connections Observe channel +/− terminal identities
    Output arrangement Two compatible modules Current-sink loop arrangement
    Field wire Maximum 1.31 mm² / 16 AWG Strip 6 mm

    View Rockwell T9882 terminal diagram (PDF, p. 111)

    Mounting and handling

    1. Check the module group

      Confirm the dual analog-output arrangement and compatible I/O base positions.

    2. Match the coding

      Fit the analog-output termination assembly with the correct coding pegs and terminal polarity.

    3. Verify loop behavior

      Check the field loop and application fail-state settings before returning the circuit to service.

    View mounting diagram

    Power and handling precautions

    • The termination assembly does not replace the active output modules.

    • Follow the system isolation requirements before changing field wiring.

    • Use an appropriate enclosure and retain the AADvance cooling and access clearances.

    Frequently Asked Questions

    Is T9882 interchangeable with the simplex T9881?

    T9882 supports two output modules in a dual arrangement, while T9881 supports one module in a simplex arrangement. Select the termination assembly to match the actual redundancy and base configuration.

    Does T9882 itself generate a 4–20 mA output?

    No. T9882 provides field termination. The associated T9481/T9482 modules generate the controlled analog output through their current-sink circuits.

    How many field outputs does T9882 connect?

    T9882 provides eight field-output connections. Its two module positions support the dual module arrangement, rather than sixteen separate field outputs.

    How is output current shared with T9882 in dual operation?

    With the compatible dual T9481/T9482 arrangement, each module sinks half the demanded channel current. Verify the module pairing and complete field-loop design.

    Which wiring details matter when replacing T9882?

    Match the analog-output coding and terminal polarity, the dual module arrangement and the existing field wiring. The maximum conductor size is 1.31 mm² (16 AWG), with a 6 mm stripping length.

    What space should be reserved for a T9882 termination assembly?

    The T9882 assembly is 132 mm high and 84 mm wide. Check this dual-assembly width against the available base positions and enclosure clearances when replacing a simplex arrangement or expanding the system.

    Does T9882 determine the output state after a module failure?

    No. The associated T9481/T9482 output-module configuration determines the failure behavior: hold the last state, go to the fail-safe state, or use a specified output state. Verify those application settings for the required process response.

    Can T9882 span two adjacent T9300 I/O bases?

    Yes. AADvance dual termination assemblies can bridge adjacent T9300 bases. For example, two three-position bases can accommodate three dual assemblies. Match the module grouping and base layout to the intended redundant output configuration.

    Manufacturer Documentation

    T9882 Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 6 pages · 88.9 KB · Compiled by EWOLO CONTROL. ICSTT-RM447N-EN-P, February 2021 and ICSTT-RM448N-EN-P, September 2024

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T9882

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.