ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T9832 AADvance Dual Analog Input Termination Assembly

ICS Triplex T9832 is an AADvance dual analog input termination assembly. It provides sixteen field-input connections and the termination interface for two compatible analog input modules in a redundant arrangement.

Version check: Confirm T9832 dual analog-input termination, matched T9431 or T9432 module types, coding pegs and the existing field-loop fuse arrangement.

Download
  • ICS Triplex T9832 AADvance Dual Analog Input Termination Assembly

    ICS Triplex T9832 is the dual analog-input termination assembly for an AADvance controller, providing the field connection point for a redundant pair of compatible analog input modules. It serves a common group of field inputs so that the two modules receive the same signals; the dual arrangement does not double the number of field channels. T9832 provides sixteen input connections and individual sensor-supply fuse protection, supporting a clearly defined interface between the field loops and the input modules. Signal measurement and processing are performed by the associated modules, while this assembly provides the termination and connection functions.

    Hardware specifications. T9832 provides 16 field-input connections with a 50 mA fuse for each sensor signal. It supports two input modules, uses a nominal 135 Ω channel load and accepts conductors up to 1.31 mm² (16 AWG) with a 6 mm stripping length.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T9832
    Platform AADvance
    Product type Analog input termination assembly
    Base system AADvance T9300 I/O base

    Functional Configuration

    Redundancy arrangement Dual
    Field connections 16 analog inputs
    Input modules supported 2
    Compatible input family T9431 / T9432, matched types per group
    Maximum conductor cross-section 1.31 mm² (16 AWG)
    Conductor stripping length 6 mm

    Performance & Power

    Sensor-input fuse 50 mA, 125 V, Type T
    Nominal channel load 135 Ω ±0.2%

    Environment

    Installation enclosure AADvance open-type assembly requires an enclosure with adequate cooling and access clearance

    Compatibility & Selection Guide

    System compatibility. Use T9832 with the matching AADvance T9431 or T9432 analog input module arrangement on T9300 I/O base units. Do not mix 8-channel and 16-channel input modules within one redundant group. Match the termination coding and installed controller/application configuration before replacement.

    Wiring & Installation Reference

    The terminal diagram is from Rockwell Automation System Build Manual ICSTT-RM448N-EN-P, p. 104.

    Analog-input terminations

    Connection Requirement Check
    Field inputs 16 connections Follow the printed channel +/− identity
    Module arrangement Dual matched analog inputs Do not mix 8- and 16-channel modules
    Field wire Maximum 1.31 mm² / 16 AWG Strip 6 mm

    View Rockwell T9832/T9833 terminal diagram (PDF, p. 104)

    Mounting and handling

    1. Check the base arrangement

      Use the matching T9300 I/O base and verify the two-module redundant group.

    2. Match coding and connections

      Check the analog-input coding pegs and printed terminal identities before fitting.

    3. Verify the completed assembly

      Check field wiring, fuse ratings and the controller/application assignment before energizing.

    View mounting diagram

    Power and handling precautions

    • Do not remove or replace fuses while energized.

    • Use the specified 50 mA, 125 V, Type T input fuses.

    • AADvance is open-type equipment and requires an appropriate enclosure with adequate cooling and access clearances.

    Frequently Asked Questions

    Is T9832 an analog input processing module?

    No. T9832 is the field termination assembly for a dual analog input arrangement. The connected T9431 or T9432 modules perform the input processing.

    Does T9832 provide 32 inputs because it supports two modules?

    No. It provides 16 field-input connections. The two module positions support redundancy for the connected input group, not 32 independent field channels.

    Can T9832 mix a T9431 and a T9432 in one redundant group?

    No. Do not mix 8-channel and 16-channel input modules within the same redundant group. Match the input module types, application configuration and termination arrangement.

    What fuse does T9832 use for each sensor input?

    Each sensor input uses a 50 mA, 125 V, Type T fuse. The replacement-fuse catalog item is T9901; use the specified fuse and follow the circuit-isolation requirements.

    Does replacing a T9832 fuse require removing the input modules?

    The fuses are accessible without removing the I/O modules or termination assembly. Do not remove or replace a fuse while energized; use the approved isolation procedure and correct replacement type.

    What channel load should be included when selecting a loop for T9832?

    The termination assembly channel load is 135 Ω with a tolerance of ±0.2%. Include this load, along with the rest of the field circuit, when checking the transmitter loop-voltage budget.

    Does T9832 provide isolated field-input terminations?

    Yes. T9832 supports isolated analog-input terminations, unlike the non-isolated simplex T9831 arrangement. Its channel-isolation withstand rating is ±1.5 kV DC for one minute; this test rating is not a normal operating loop voltage.

    Does a T9832 arrangement require a complete T9300 base to itself?

    No. A three-position T9300 base can hold one dual termination arrangement and one simplex arrangement. Dual assemblies can also bridge adjacent bases; plan the module grouping and available base positions for the complete controller.

    Manufacturer Documentation

    T9832 Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 8 pages · 98.9 KB · Compiled by EWOLO CONTROL. ICSTT-RM447N-EN-P, February 2021 and ICSTT-RM448N-EN-P, September 2024

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T9832

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.