ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T8461C Trusted TMR 24/48V DC Digital Output Module

ICS Triplex T8461C is a coated Trusted TMR digital output module for 24/48 V DC loads. Its forty outputs are arranged in five power groups, with output-state, voltage, current and line-fault diagnostics.

Version check: Match T8461C revision, 24/48 V field supply, per-channel load and FTA/cable keying; retain the configured fail-safe output states.

Download
  • ICS Triplex T8461C Trusted TMR 24/48V DC Digital Output Module

    ICS Triplex T8461C is a conformally coated digital output module for the Trusted Triple Modular Redundant (TMR) system, providing 40 output channels to control 24/48 V DC field devices. Its triplicated channel architecture and automatic diagnostics monitor output voltage, current and switching behavior, while line monitoring detects open- and short-circuit faults in field wiring and connected loads. T8461C also provides group fail-safe switching and front-panel indicators for output status and wiring faults. Onboard Sequence of Events (SOE) reporting records output-state changes with 1 ms resolution, supporting fault investigation and maintenance of the Trusted system.

    Hardware specifications. The outputs are arranged in five groups of eight. Field power operates from 18–58 V DC, while the IMB supply is 20–32 V DC. Each channel supports 0.75 A continuous current with a 25 mA minimum load and electronic short-circuit protection.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T8461C
    Platform Trusted TMR
    Product type 24/48 V DC digital output module
    Coating Conformal coating, C suffix

    Functional Configuration

    Outputs 40
    Power groups 5 groups of 8

    Performance & Power

    Field supply range 18–58 V DC
    IMB supply 20–32 V DC
    Continuous current per channel 0.75 A
    Minimum load current 25 mA
    Short-circuit protection Electronic, latching

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. Configure T8461C through the Trusted IEC 61131 TOOLSET and System Configuration Manager. The processor applies the downloaded module definition, diagnostics and fail-safe states. Match the FTA, cable, field power groups and installed hardware/firmware before replacing a module.

    Wiring & Installation Reference

    ICSTT-RM451D-EN-P, March 2021. Use the matching system and field-wiring configuration.

    Field-power and output checks

    Connection Requirement Check
    Outputs 5 groups × 8 channels Check each power group and return
    Field supply 18–58 V DC Nominal 24/48 V DC loads
    Unused output 10 kΩ, 0.5 W to 0 V Command off in the application

    View terminal diagram (PDF)

    Mounting and handling

    1. Inspect the module

      Use static precautions. Do not install a damaged housing or bent connector pins, and do not open the housing.

    2. Check cable and slot keys

      Fit the correct field cable and check the module-specific key positions before inserting the module.

    3. Seat and lock

      Open the ejector tabs, insert without force, press the top and bottom fascia fully home, then close both ejectors until locked.

    View mounting diagram

    Power and handling precautions

    • Keep the field supply distinct from the IMB system supply.

    • For T8461 cable keying, remove pins 1, 5 and 7; key both strips for companion-slot installations.

    • Use static precautions, inspect pins and do not force insertion.

    Frequently Asked Questions

    Does T8461C support both 24 V and 48 V DC loads?

    Yes. The field-power operating range is 18–58 V DC for nominal 24/48 V DC service. Check the load rating and field power-group wiring separately from the 20–32 V DC IMB supply.

    How much current can each T8461C output deliver?

    Each channel is rated for 0.75 A continuous output. The minimum load is 25 mA; also check the group and total supply limits, cable voltage drop and load capacitance.

    How should unused T8461C outputs be handled?

    Command unused outputs off in the application and connect each through a 10 kΩ, 0.5 W resistor to zero volts.

    Can T8461C output defaults be configured?

    Yes. Define the module and I/O variables in the Trusted IEC 61131 TOOLSET, then set per-channel default/fail-safe states and other parameters in System Configuration Manager.

    What must be checked before replacing T8461C?

    Match the coated model, hardware/firmware, FTA and cable arrangement, field supply and load limits. Preserve the intended fail-safe states and verify the cable keying for the replacement position.

    How is a latched short-circuit fault cleared on T8461C?

    After resolving the field fault and following the approved operating procedure, the latch can be cleared with the system Fault Reset control or by changing the commanded channel state. Sustained overcurrent latches the fault and de-energizes the affected output.

    How does T8461C distinguish an open load from missing field power?

    Its application diagnostics report numerical output state 3 for no load or an open field circuit, and state 1 for no field-supply voltage. Both set the line-fault status, so use the numerical state as well as the fault flag when troubleshooting.

    Why can a group of eight T8461C outputs switch off together?

    Each group of eight outputs has Group Fail-Safe Switches. Multiple module faults, such as output switches that cannot turn off normally, can cause these switches to remove power from the entire group. Investigate the group and module diagnostics before attempting to restore the outputs.

    Manufacturer Documentation

    T8461C Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 7 pages · 108.4 KB · Compiled by EWOLO CONTROL. ICSTT-RM451D-EN-P, March 2021

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T8461C

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message