ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T8442C Trusted TMR Speed Monitor Module

ICS Triplex T8442C is a coated Trusted TMR speed monitor for rotating machinery. It supports three machine groups and provides overspeed and over-acceleration protection using the matching speed-input and shutdown-output termination assemblies.

Version check: Confirm T8442C revision, probe type, gear-tooth count, trip settings and the T8846/T8891 termination arrangement before replacement.

Download
  • ICS Triplex T8442C Trusted TMR Speed Monitor Module

    ICS Triplex T8442C is a conformally coated Trusted TMR speed-monitoring module for rotating machinery, including steam and gas turbines driving pumps, compressors or generators. It measures shaft speed and acceleration and provides shutdown outputs for overspeed and overacceleration protection through dedicated termination assemblies. T8442C forms a self-contained, fault-tolerant subsystem within the Trusted platform, with separate machine groups that combine triplicated speed inputs and redundant shutdown outputs. Speed-control functions are independent of the machinery-protection functions, while Sequence of Events reporting and front-panel diagnostics help operators investigate trips and identify abnormal channel or module conditions.

    Hardware specifications. The module supports three machine groups, each with three redundant speed inputs and two shutdown-output drives. Active and passive speed probes are supported through the T8846 input FTA. The maximum input frequency is 30 kHz and the IMB operating supply is 20–32 V DC.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T8442C
    Platform Trusted TMR
    Product type Speed monitor module
    Coating Conformal coating, C suffix

    Functional Configuration

    Machine groups 3
    Speed inputs 3 per group; 9 total
    Shutdown-output drives 2 per group; 6 total
    Probe types Active and passive, through T8846 FTA

    Performance & Power

    Maximum input frequency 30 kHz
    IMB supply 20–32 V DC
    Typical IMB power 22 W at 24 V DC

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. T8442C uses the Trusted System Configuration tool; settings are included in System.INI and transferred through the TMR processors. Gear-tooth count, probe limits and overspeed thresholds must match the machine. The system uses T8846 input and T8891 output FTAs with the appropriate TC801 cable assembly.

    Wiring & Installation Reference

    ICSTT-RM276I-EN-P, PD-T8442 Issue 10. Use the matching system and field-wiring configuration.

    Probe and shutdown connections

    Connection Requirement Check
    Speed inputs T8846 SIFTA Match active/passive probes
    Shutdown outputs T8891 SOFTA Use the three-group output arrangement
    Module interconnection TC801 assembly No direct field-device back-connector wiring

    View terminal diagram (PDF)

    Mounting and handling

    1. Inspect the module

      Use static precautions. Do not install a damaged housing or bent connector pins, and do not open the housing.

    2. Check cable and slot keys

      Fit the correct field cable and check the module-specific key positions before inserting the module.

    3. Seat and lock

      Open the ejector tabs, insert without force, press the top and bottom fascia fully home, then close both ejectors until locked.

    View mounting diagram

    Power and handling precautions

    • Use only the specified termination and cable arrangement.

    • Validate tooth count, speed thresholds and trip behavior against the machine safety requirements.

    • Use static precautions and do not touch connector pins or force module insertion.

    Frequently Asked Questions

    How many machines can T8442C monitor?

    T8442C supports three machine groups. Each group has three redundant speed inputs and two shutdown-output drives; configure each group for its own machine and protection settings.

    Can sensors be wired directly to the rear connector of T8442C?

    No. Use the T8846 speed-input FTA, the T8891 speed-output FTAs and the appropriate TC801 cable assembly. Direct field-device connection to the module backplane connector is not supported.

    Can T8442C use passive magnetic pickups?

    Yes. Active and passive probes are supported through the T8846 input FTA. Match the probe type, signal characteristics and minimum-speed settings to the machine.

    Why must the gear-tooth count be correct for T8442C?

    The configured tooth count scales the incoming pulse frequency into RPM. A value of zero treats that input as disconnected and at zero speed, so an incorrect setting can invalidate the machine-speed interpretation.

    How are T8442C trip settings transferred?

    The Trusted System Configuration tool places the settings in System.INI. The file is transferred to the TMR processors, which pass the settings to the speed monitor during initialization. Observe the zero-speed restrictions on changing protection settings.

    Does T8442C support SmartSlot online replacement?

    No. Online replacement uses the Companion Slot method, with the standby module educated from the active module before changeover. The Trusted SmartSlot method is not supported for this speed monitor.

    Can T8442C protection limits be increased while the machine is running?

    The safety parameters for a speed group cannot be changed while any input in that group is above zero speed. Overspeed and over-acceleration thresholds cannot be increased beyond the safety limits loaded at initialization; permitted threshold adjustments can only move in a safe direction within those limits.

    Does T8442C protect against excessive acceleration as well as overspeed?

    Yes. Each of its three galvanically isolated speed groups has three speed inputs and two relay-output drives: one for overspeed and one for over-acceleration. Configure the protection settings for the machine assigned to each group.

    Manufacturer Documentation

    T8442C Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 9 pages · 118.4 KB · Compiled by EWOLO CONTROL. ICSTT-RM276I-EN-P, PD-T8442 Issue 10

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T8442C

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.