ICS Triplex T8431C Trusted TMR 40-Channel Analog Input Module

ICS Triplex T8431C is a coated Trusted TMR analog input module for forty process signals. It is typically used with 4–20 mA field loops and reports channel values, line faults and module diagnostics.

Version check: Match T8431C hardware, firmware and FTA; for Series C units dated T2108 or later, check product notice 2025-08-002 and the applicable firmware correction.

Download
  • ICS Triplex T8431C Trusted TMR 40-Channel Analog Input Module

    ICS Triplex T8431C is a conformally coated, 40-channel Trusted TMR analog input module for acquiring measurements from sourcing field devices. It acts as the current-sink input stage and processes each channel through a triplicated architecture before making the measurement available to the Trusted application. Built-in line monitoring detects open- and short-circuit conditions according to the channel configuration, and automatic diagnostics monitor the module's internal operation. T8431C also reports threshold-related input-state changes through its Sequence of Events facility, while front-panel indicators provide a local view of channel condition and module health for fault investigation.

    Hardware specifications. Typical input operation is 4–20 mA, with a measurement range of 0–22 mA or 0–5.5 V. Current measurement resolution is 3.906 µA, and a 250 Ω field termination resistor is used for current-to-voltage conversion. Channel-to-channel isolation is not provided.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T8431C
    Platform Trusted TMR
    Product type Analog input module
    Coating Conformal coating, C suffix

    Functional Configuration

    Input channels 40
    Typical process signal 4–20 mA
    FTA current-conversion resistor 250 Ω

    Performance & Power

    Measurement range 0–22 mA / 0–5.5 V
    Current resolution 3.906 µA
    IMB supply 20–32 V DC
    Channel-to-channel isolation None

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. Use the Trusted IEC 61131 TOOLSET and System Configuration Manager for module assignment, engineering units, thresholds and diagnostic variables. Match the FTA, cable and hardware/firmware revision. For Series C units dated T2108 or later, verify the applicable correction for product notice 2025-08-002 before deployment.

    Wiring & Installation Reference

    ICSTT-RM273Q-EN-P, August 2021. Use the matching system and field-wiring configuration.

    Analog-loop and termination checks

    Connection Requirement Check
    Process loops 40 analog inputs Typical 4–20 mA service
    FTA conversion 250 Ω Check loop loading with redundant modules
    Cable keying Remove pins 1, 4 and 5 Key both strips for companion slots

    View terminal diagram (PDF)

    Mounting and handling

    1. Inspect the module

      Use static precautions. Do not install a damaged housing or bent connector pins, and do not open the housing.

    2. Check cable and slot keys

      Fit the correct field cable and check the module-specific key positions before inserting the module.

    3. Seat and lock

      Open the ejector tabs, insert without force, press the top and bottom fascia fully home, then close both ejectors until locked.

    View mounting diagram

    Power and handling precautions

    • Use static precautions and inspect connector pins before installation.

    • Do not force the module into a slot or remove its housing.

    • Review the complete FTA wiring and applicable product-notice/firmware status before commissioning.

    Frequently Asked Questions

    Is T8431C a 4–20 mA input or output module?

    T8431C is an analog input module. It accepts 40 process-input channels; 4–20 mA is the typical operating signal and the measurement range is 0–22 mA.

    Does T8431C provide isolation between individual input channels?

    No. Channel-to-channel isolation is not provided. Check the field-loop grounding and any required external isolation before selecting it.

    Which termination details matter when replacing T8431C?

    Match the approved FTA and cable arrangement, the 250 Ω current-conversion resistance and the active/standby configuration. A parallel partner module changes the effective input impedance, so the complete loop must be checked.

    How is T8431C configured?

    Define the module position and I/O variables in the Trusted IEC 61131 TOOLSET. Use System Configuration Manager for thresholds, noise filtering and indicator settings; the processor transfers the configuration to the module.

    What additional revision check applies to T8431C Series C?

    Series C units with date code T2108 or later fall within product notice 2025-08-002 for a possible slice shutdown. Confirm the installed firmware and applicable correction with Rockwell Automation or Sensia support before deployment. Do not assume a firmware version is corrected solely because it is newer.

    Why can T8431C report a value of zero for a 4 mA signal?

    With the 250 Ω field-loop configuration and the module engineering-unit scaling, 4 mA corresponds to 0 and 20 mA corresponds to 4096. A zero engineering-unit value therefore does not mean zero loop current; verify the application scaling before diagnosing the transmitter.

    Can T8431C log input-status and line-fault changes as events?

    Yes. Enable Sequence of Events for the relevant Boolean Input Status and Line Fault Status variables in the Data Dictionary. The module reports timestamped state changes, which the TMR processor records in the system SOE log.

    Does a flashing red Healthy indicator on T8431C always mean the slice has stopped?

    No. It can mean a slice fault while that slice remains operational, or failure of one 24 V chassis power feed. A steady red Healthy indicator identifies a fatal fault with the slice disabled. Use the diagnostic information and power-feed checks to identify the cause.

    Manufacturer Documentation

    T8431C Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 7 pages · 125.8 KB · Compiled by EWOLO CONTROL. ICSTT-RM273Q-EN-P, August 2021

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T8431C

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.