ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T8403 Trusted TMR 24V DC Digital Input Module

ICS Triplex T8403 is a Trusted TMR digital input module for forty nominal 24 V DC field inputs. It provides input-state, line-fault and module diagnostic information to the Trusted system.

Version check: Match T8403 hardware/software revision, field termination and cable keying; T8403C is the official replacement and still requires system compatibility review.

Download
  • ICS Triplex T8403 Trusted TMR 24V DC Digital Input Module

    ICS Triplex T8403 is a 40-channel Trusted Triple Modular Redundant (TMR) digital input module for nominal 24 V DC field signals. It measures each input through triplicated circuitry and uses configurable thresholds to determine the state passed to the safety-system application. When the required line-monitoring device is fitted at the field switch, T8403 can also identify open- and short-circuit conditions. Automatic diagnostics, channel-state and wiring-fault indicators help locate abnormal conditions, while onboard Sequence of Events reporting records input-state changes with 1 ms resolution for event analysis and maintenance of the Trusted system.

    Hardware specifications. T8403 provides 40 inputs with a -6 to +36 V DC measurement range and 5 kΩ nominal input impedance. Thresholds are configurable, and sequence-of-events reporting has 1 ms resolution. The module operates from the 20–32 V DC Inter-Module Bus supply.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T8403
    Platform Trusted TMR
    Product type 24 V DC digital input module

    Functional Configuration

    Inputs 40
    Thresholds User configurable

    Performance & Power

    Nominal field voltage 24 V DC
    Input measurement range -6 to +36 V DC
    Nominal input impedance 5 kΩ
    SOE resolution 1 ms
    IMB supply 20–32 V DC
    Channel-to-channel isolation None

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. Configure T8403 using the Trusted IEC 61131 TOOLSET and System Configuration Manager, including chassis/slot assignment, thresholds, filtering and diagnostic variables. T8403 is discontinued; Rockwell identifies T8403C as its direct replacement. Match the installed hardware/software and termination arrangement before changing versions.

    Wiring & Installation Reference

    ICSTT-RM271Q-EN-P, August 2021. Use the matching system and field-wiring configuration.

    Input and termination checks

    Connection Requirement Check
    Field signals 40 nominal 24 V DC inputs Match the actual FTA and cable
    Thresholds Configured per channel Check supply and line-monitor network
    Cable keying Remove pins 1, 3 and 5 Key both strips for companion slots

    View terminal diagram (PDF)

    Mounting and handling

    1. Inspect the module

      Use static precautions. Do not install a damaged housing or bent connector pins, and do not open the housing.

    2. Check cable and slot keys

      Fit the correct field cable and check the module-specific key positions before inserting the module.

    3. Seat and lock

      Open the ejector tabs, insert without force, press the top and bottom fascia fully home, then close both ejectors until locked.

    View mounting diagram

    Power and handling precautions

    • Observe static precautions and do not touch exposed connector pins.

    • Do not force a module into the chassis or straighten damaged pins.

    • The field connector table spans the original installation pages; verify the complete terminal assignment before wiring.

    Frequently Asked Questions

    Is T8403 a digital or analog input module?

    T8403 is a 40-channel digital input module for nominal 24 V DC field signals. Its voltage and diagnostic data support input-state and line-fault evaluation; it is not a 4–20 mA process-input module.

    What replaces the discontinued T8403?

    Rockwell identifies T8403C as the direct replacement for T8403. Before ordering, confirm the installed hardware/software revision, field termination, cable keying and system compatibility requirements.

    Can the switching thresholds of T8403 be adjusted?

    Yes. Configure per-channel thresholds and noise filtering through the Trusted System Configuration Manager, with the module and variables defined in the IEC 61131 TOOLSET.

    Are T8403 input channels individually isolated from each other?

    No. Channel-to-channel isolation is not provided. Check the field wiring, common references and isolation requirements of the complete input circuit.

    Can T8403 detect field-line faults?

    Yes, with the appropriate field-monitoring arrangement and configured threshold levels. Match the monitoring components to the active/standby module arrangement and the actual field supply.

    Can T8403 record the time of an input state change?

    Yes. T8403 timestamps input state changes with its onboard clock. The TMR processor retrieves the input state and timestamp for the system Sequence of Events log; enable SOE logging for the required inputs.

    Why can inserting a standby T8403 change the measured input voltage?

    In a line-monitored application, inserting the standby module places the input terminations in parallel and reduces the voltage seen by the active module. Check the line-monitoring network and threshold settings for the intended active/standby arrangement before replacement.

    What does a flashing red Healthy indicator on T8403 mean?

    It can indicate a fault on a slice that is still operating, or the loss of one 24 V chassis power feed. A steady red Healthy indicator instead identifies a fatal fault with the affected slice disabled. Check diagnostics and both power feeds to distinguish the causes.

    Manufacturer Documentation

    T8403 Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 6 pages · 114.9 KB · Compiled by EWOLO CONTROL. ICSTT-RM271Q-EN-P, August 2021

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T8403

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.