ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T8314C Trusted Fibre TX/RX Unit

ICS Triplex T8314C is a coated Trusted fibre transmitter/receiver unit. It converts copper Expander Bus signals to single-mode fibre for a remote Trusted expansion link of up to 10 km, subject to the link timing requirements.

Version check: Confirm T8314C coating, six-unit link arrangement, single-mode SC fibre, cable pairing and the remote Expander Bus timing budget.

Download
  • ICS Triplex T8314C Trusted Fibre TX/RX Unit

    ICS Triplex T8314C is a conformally coated Trusted Fibre TX/RX unit for extending the Expander Bus between separated Trusted assemblies. It converts the bus's electrical signals to single-mode optical signals and converts received optical signals back to electrical form, allowing an expander chassis to operate beyond the normal copper-link distance. A complete triplicated connection uses three independent transmit/receive pairs, with each pair carrying one bus path. T8314C supports two 24 V DC power feeds and operates without a software configuration step; bus diagnostic information is provided by the associated Expander Interface and Expander Processor modules.

    Hardware specifications. The unit uses SC fibre connections, a 250 Mbit/s link and an 18–32 V DC supply with 1.7 W maximum consumption. One complete triplicated remote link requires three pairs of units and six fibres. The maximum link distance is 10 km, subject to timing limits.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Rockwell Automation, Inc.
    Model T8314C
    Platform Trusted TMR
    Product type Fibre transmitter/receiver unit
    Coating Conformal coating, C suffix
    Dimensions 84 × 110 × 40 mm

    Functional Configuration

    Optical medium Single-mode fibre, SC connections
    Units per triplicated link 6 units arranged as 3 pairs

    Performance & Power

    Link rate 250 Mbit/s
    Maximum link distance 10 km, subject to timing limits
    Supply voltage 18–32 V DC
    Maximum power consumption 1.7 W

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. T8314C operates with the Trusted Expander Interface and Expander Processor arrangement. The units need no configuration; link diagnostics are obtained through the expansion modules. Routes beyond 2 km require a site survey, and differential delay and round-trip timing must remain within the system limits.

    Wiring & Installation Reference

    PD_T8314, Issue 12, July 2016. Use the matching system and field-wiring configuration.

    Power and bus connections

    Connection Requirement Check
    Power pins 1 / 2 +24 V DC 1 / 0 V 1 First supply input
    Power pins 4 / 3 +24 V DC 2 / 0 V 2 Second diode-ORed supply input
    Fibre connections SC Tx / Rx Use the paired single-mode fibre route

    View terminal diagram (PDF)

    Mounting and handling

    1. Mount the unit

      Use TS32 or TS35 DIN rail in either horizontal or vertical orientation.

    2. Allow fibre space

      Leave at least 200 mm on either side and observe the fibre cable minimum bend radius.

    3. Verify the whole link

      Check all three pairs, correct cable direction, optical budget, skew and round-trip timing before commissioning.

    View mounting diagram

    Power and handling precautions

    • Do not connect or disconnect while live unless the area is known to be non-hazardous; maintenance is for qualified personnel.

    • The 10 km maximum does not remove the need for optical and timing checks.

    • Use the matching outgoing TC-302-01 and incoming TC-303-01 Trusted cable arrangements.

    Frequently Asked Questions

    How many T8314C units are needed for one remote link?

    A complete triplicated Trusted remote link needs six units arranged as three independent transmitter/receiver pairs, with six fibres in total.

    Does T8314C use multimode or single-mode fibre?

    It uses single-mode fibre with SC connectors. Match the fibre characteristics and optical budget to the Trusted link specification.

    Can T8314C operate over 10 km without further checks?

    No. The route must satisfy the optical and timing limits. A site survey is required for routes beyond 2 km; differential delay must not exceed 80 ns and the round-trip delay must remain within the IMB timeout.

    Does T8314C require software configuration?

    The unit itself requires no configuration. Check link operation and fault information through the Trusted Expander Interface and Expander Processor diagnostics.

    Can T8314C use two DC power sources?

    Yes. The two 24 V DC power inputs are diode ORed, permitting a single source or dual sources within the 18–32 V DC operating range.

    Which copper interconnect cables are used with T8314C?

    Use TC-302-01 for the outgoing connection from T8312 to the fibre TX/RX unit, and TC-303-01 for the incoming connection from the fibre TX/RX unit to T8310. Match each cable to its role in the remote link.

    How much fibre-cable clearance is needed beside T8314C?

    Allow at least 200 mm on either side of the unit for the fibre bend radius. The selected cable may require a larger bend radius, so check its requirements when planning the enclosure space.

    Can one T8314C unit be replaced while the Trusted system remains operating?

    Yes. Each unit operates independently within the complete redundant remote link, allowing an individual unit to be replaced without interrupting Trusted system operation. Retain the required three pairs of units and follow the approved system maintenance procedure.

    Manufacturer Documentation

    T8314C Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 7 pages · 70.4 KB · Compiled by EWOLO CONTROL. PD_T8314, Issue 12, July 2016

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T8314C

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.