ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T3411 Regent 16-Channel Monitored Digital Input Module

ICS Triplex T3411 is a Regent 16-channel monitored digital input module for 24 V DC field-switch signals. It supports input-line fault detection when the correct monitoring devices and application logic are used.

Version check: Confirm T3411 versus externally powered T3411F, the slot key positions and the installed field-switch monitoring arrangement.

Download
  • ICS Triplex T3411 Regent 16-Channel Monitored Digital Input Module

    ICS Triplex T3411 is a 16-channel monitored digital input module for Regent control systems, receiving on/off signals from field switches and reporting their states to the controller application. Its internally regulated 24 V DC switch supply distinguishes it from the externally powered T3411F. With the appropriate line-monitoring device at each field switch, T3411 can distinguish an open or short circuit from a normal switch state. Automatic testing checks the input circuitry, while front-panel indicators show channel states, line faults and module condition, helping maintenance teams identify whether a problem originates in the field circuit or the module.

    Hardware specifications. T3411 accepts a 15–80 V DC field supply and regulates the switch supply internally to 24 V DC. The module provides 16 inputs, 10 ms maximum on/off response and at least 2500 V isolation between field and logic circuits.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Industrial Control Services
    Model T3411
    Platform ICS Regent
    Product type Monitored digital input module
    Slot key positions Upper 4; lower 7

    Functional Configuration

    Inputs 16

    Performance & Power

    Field-switch supply 24 V DC, internally regulated
    Field supply range 15–80 V DC
    Maximum field-supply current 450 mA
    Input current 5 mA
    Maximum on/off response 10 ms
    Field-to-logic isolation 2500 V minimum

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. The Regent WINTERPRET I/O Configuration Editor uses the T3411 module definition. Single, dual and triple arrangements require the corresponding wiring and application voting logic; redundancy uses additional modules of the same type. T3411F has a different field-power arrangement and is not an unqualified substitute.

    Wiring & Installation Reference

    PD-6031, Issue 1, March 2006. Use the matching system and field-wiring configuration.

    Field wiring and line monitoring

    Connection Requirement Check
    Field supply 15–80 V DC Module regulates switch supply to 24 V DC
    Single sensor/module T0412 Resistor line-monitor network
    Shared sensor/redundant modules T0413 Zener line-monitor network

    View terminal diagram (PDF)

    Mounting and handling

    1. Confirm the slot

      Use the Regent I/O chassis position wired for T3411; inspect the existing field connections.

    2. Set the keys

      Use upper key position 4 and lower key position 7; retain the correct connector orientation.

    3. Verify monitoring

      Match single or redundant wiring to the corresponding diagram and configure input/fault variables before commissioning.

    View mounting diagram

    Power and handling precautions

    • For energize-to-trip safety inputs, line monitoring and fault alarms are required.

    • Do not assume T3411F wiring or keying applies to T3411.

    • Use the site-approved isolation and safety procedures before changing field wiring.

    Frequently Asked Questions

    How does T3411 differ from T3411F?

    T3411 regulates the field-switch supply to 24 V DC internally. T3411F uses an external supply wired directly to the field switches. Their slot key positions also differ; check the installed wiring and exact catalog number before replacement.

    Can T3411 detect broken or shorted field wiring?

    Yes, when the correct line-monitor device is fitted across the field switch. Use T0412 for a single module/sensor arrangement and T0413 for a single sensor shared by redundant modules, following the matching wiring scheme.

    Can two T3411 modules share one sensor?

    Yes. Two or three modules of the same type can be connected to one sensor for a fault-tolerant input arrangement. The application must use the corresponding voting and fault-handling logic.

    Which configuration entry should I use for T3411?

    Select the T3411 module type in the Regent WINTERPRET I/O Configuration Editor and assign the input and fault variables required by the application.

    What is required for T3411 energize-to-trip inputs?

    Fit line-monitor devices at the field switches, configure the Fault Name variables and alarm line-fault status to plant operations. Assess sensor failure modes and proof-testing requirements as part of the safety application.

    What do the ACTIVE and FAULT indicators on T3411 mean?

    During normal operation, the green ACTIVE indicator flashes at the controller scan rate. A module fault turns on the red FAULT indicator and turns off the green ACTIVE indicator.

    Does a yellow channel indicator on T3411 always mean a healthy closed contact?

    No. The yellow indicator lights for either a closed contact or a shorted line. With line monitoring enabled, the red line-status indicator identifies an open or short circuit, so check both indicators when diagnosing the input.

    Can a failed T3411 be replaced without interrupting input monitoring?

    Yes, in the supported fault-tolerant configuration with redundant monitored input modules. The remaining module or modules continue sensing the inputs while the failed unit is replaced. This does not establish uninterrupted operation for a simplex input arrangement.

    Manufacturer Documentation

    T3411 Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 9 pages · 125.9 KB · Compiled by EWOLO CONTROL. PD-6031, Issue 1, March 2006

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T3411

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.