Allen-Bradley 1746-P4 SLC 500 Rack Mounting Power Supply

Allen-Bradley 1746-P4 is an AC-input rack power supply for an SLC 500 modular chassis. It provides 5 V and 24 V backplane power and a 24 V user output, subject to a combined 70 W limit.

Version check: Match the input-voltage selection and the complete 5 V/24 V load budget, including user power. For Series A, a 24 V user-output overload can shut down the supply and fault the CPU.

Download
  • Allen-Bradley 1746-P4 SLC 500 Rack Mounting Power Supply

    Allen-Bradley 1746-P4 is an AC-powered chassis supply for the SLC 500 modular control platform, providing the backplane power needed by the processor and I/O modules in the rack. It supplies the chassis's 5 V DC and 24 V DC power rails and also offers a separate 24 V DC user output for suitable field devices. The backplane and user-output loads share the supply's total power capacity, so both must be considered when matching 1746-P4 to an existing system. Its role is power conversion and distribution; the connected SLC processor and I/O modules perform the control and signal-processing functions.

    Hardware specifications. The 1746-P4 accepts 85–132 V AC or 170–250 V AC at 47–63 Hz. Rated capacities are 10 A at 5 V DC, 2.88 A at 24 V DC and 1 A for the 24 V user output, with all three outputs together limited to 70 W. The operating temperature is 0–60°C without output-current derating.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Allen-Bradley
    Catalog number 1746-P4

    Functional Configuration

    Product function SLC 500 rack power supply
    User-output protection Isolated, non-fused user supply

    Performance & Power

    Input voltage 85–132 V AC or 170–250 V AC, selected by jumper
    Input frequency 47–63 Hz
    5 V backplane capacity 10 A
    24 V backplane capacity 2.88 A
    24 V user output 1 A
    Combined output-power ceiling 70 W total across 5 V backplane, 24 V backplane and 24 V user power
    Maximum inrush current 45 A
    24 V user-output voltage range 20.4–27.6 V DC

    Environment

    Operating temperature 0–60°C; no current derating for 1746-P4
    Relative humidity 5–95%, noncondensing

    Compatibility & Selection Guide

    System compatibility. The 1746-P4 belongs to the SLC 500 modular chassis platform. Each chassis needs its own supply, so replacement selection requires a separate 5 V and 24 V load calculation for that chassis, including peripherals and user power. Other 1746-Px supplies have different input and output ratings; a shared family name alone does not establish an equivalent replacement.

    Wiring & Installation Reference

    Verify the 1746-P4 input selection and total power budget before energizing the chassis. Use the P4-specific terminal arrangement, not the diagram for another 1746-Px supply.

    Power connections

    Connection Function Check
    L1/L2 neutral AC input Select 85–132 V or 170–250 V with power removed before connecting the line.
    Chassis ground Protective grounding Connect to the nearest ground bus with short specified copper conductors.
    PWR OUT +24 V DC/COM User-device supply Limit to 1 A and include this load within the 70 W shared output budget; user output is not fused.

    View power connection requirements (PDF)

    Installation checks

    1. Prepare the chassis

      Check enclosure, grounding and any chassis interconnect cable before installing the supply.

    2. Fit the power supply

      Align the circuit board with the left-hand chassis guides, seat it flush and secure the mounting screws to a maximum 1.2 N·m.

    3. Set the input and connect power

      With incoming power removed, set the voltage jumper, connect ground and input wiring, and tighten terminals to 0.8 N·m. Remove the protective label before operation.

    View installation guide

    Power and handling precautions

    • Turn off incoming power before connecting wires. Do not insert/remove the supply or disconnect wiring under power in a hazardous location.

    • Use ESD precautions and a suitable tool-access enclosure. Keep the chassis and supply appropriately grounded.

    • Protect against inductive-load switching surges with the specified isolation-transformer arrangement. For Series A, a 24 V user-output overload can shut down the supply and fault the CPU; correct the condition and reload the user program as required.

    Frequently Asked Questions

    Does the 1746-P4 accept 24 V DC input?

    No. It takes 85–132 V AC or 170–250 V AC at 47–63 Hz. Its 24 V terminals are outputs; verify the selected AC input range before energizing it.

    Can the 1746-P4 deliver every output rating at the same time?

    Only while the combined output remains within 70 W. Add the 5 V backplane, 24 V backplane and 24 V user-output loads; also respect each individual current limit.

    Can the 1746-P4 power external 24 V sensors?

    Yes. The isolated 24 V user output supports up to 1 A and is not fused. Include its load in the shared 70 W budget and provide the required circuit protection.

    What happens if the 1746-P4 Series A user output is overloaded?

    The supply shuts down and the CPU faults. Correct the overcurrent condition and reload the user program during recovery. Retain a valid application backup before service.

    Is the 1746-P4 directly equivalent to a 1746-P2?

    No. Their 5 V/24 V current capacities and user-power limits differ. Compare the exact input range, each rail load and total output power before selecting a replacement.

    Can one 1746-P4 supply several SLC 500 chassis?

    Each modular chassis requires its own power supply. Calculate the loading for each chassis separately, even when the chassis are linked together.

    Can the 1746-P4 keep the CPU running through a brief loss of line power?

    At zero input voltage, rated CPU hold-up is 20 ms at full load and 3000 ms with no load. CPU operation during an interruption depends on the connected load and outage duration.

    Is the 1746-P4 mains fuse a plug-in replacement like the 1746-P2 fuse?

    The 1746-P4 input fuse is soldered in place. The 1746-P2 uses a replaceable 1746-F2 or equivalent fuse.

    Manufacturer Documentation

    1746-P4 Product Reference

    Product photograph, application notes and selected Rockwell Automation reference pages.

    PDF · 3 pages · 48.8 KB · Compiled by EWOLO CONTROL. 1747-SG001E-EN-E E

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Allen-Bradley 1746-P4

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.