ISO 9001:2015 certified industrial automation spare parts supplier

ICS Triplex T3411F Regent Type F Monitored Digital Input Module

ICS Triplex T3411F is a 16-channel Regent Type F monitored digital input module. Its externally powered 24/48 V DC field circuits support switch-state monitoring and line-fault detection with the appropriate monitoring network.

Version check: Confirm the full T3411F suffix, external field-supply voltage, monitoring network and upper 9/lower 7 slot keys before replacement.

Download
  • ICS Triplex T3411F Regent Type F Monitored Digital Input Module

    ICS Triplex T3411F is the externally powered, 16-channel Type F monitored digital input module for Regent control systems. It receives field-switch signals from circuits whose power supply feeds the switches directly, making it distinct from the internally regulated T3411. For suitable DC circuits equipped with the required line-monitoring devices, T3411F reports open- and short-circuit conditions as well as the switch states used by the application logic. Automatic input-circuit testing and front-panel channel, line-fault and module indicators support fault diagnosis, while the controller receives the input and diagnostic information needed to respond to changing field conditions.

    Hardware specifications. T3411F supports nominal 24 or 48 V DC field operation within a 15–80 V DC supply range. Its input current is 8 mA, maximum on/off response is 10 ms, and field-to-logic isolation is at least 2500 V.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Industrial Control Services
    Model T3411F
    Platform ICS Regent
    Product type Type F monitored digital input module
    Slot key positions Upper 9; lower 7

    Functional Configuration

    Inputs 16

    Performance & Power

    Nominal field voltage 24/48 V DC
    Field supply range 15–80 V DC
    Field-switch power External supply
    Input current 8 mA
    Maximum on/off response 10 ms
    Field-to-logic isolation 2500 V minimum

    Environment

    Operating temperature 0–60 °C

    Compatibility & Selection Guide

    System compatibility. Select T3411F in the WINTERPRET I/O Configuration Editor and retain the application’s input/fault variables and voting arrangement. Same-type modules support redundant configurations. Do not substitute T3411 or the 120 V AC T3418F solely because the housings look similar.

    Wiring & Installation Reference

    PD-6027, Issue 1, March 2006. Use the matching system and field-wiring configuration.

    External field-power connections

    Connection Requirement Check
    Nominal field supply 24/48 V DC 15–80 V DC allowable range
    Field switch Externally powered Switched side returns to the input
    Line-monitor device Voltage/configuration specific Match the redundancy arrangement

    View terminal diagram (PDF)

    Mounting and handling

    1. Check exact type

      Identify T3411F and its external field supply; do not use T3411 or T3418F wiring.

    2. Verify slot keying

      Set upper key 9 and lower key 7 in the existing Regent chassis position.

    3. Check input diagnostics

      Use the matching line-monitor network and configure input, fault and voting variables in WINTERPRET.

    View mounting diagram

    Power and handling precautions

    • Energize-to-trip safety circuits require line monitoring and an alarm on line-fault status.

    • Do not connect 120 V AC to the T3411F DC input module.

    • The module has no user-replaceable internal parts; follow approved isolation procedures.

    Frequently Asked Questions

    Does T3411F supply a regulated 24 V output to field switches?

    No. The external field power supply is wired directly to the field switches; the switched signal returns to the input module. This differs from the internally regulated field-switch supply used by T3411.

    Is T3411F suitable for 120 V AC inputs?

    No. T3411F is the nominal 24/48 V DC model. T3418F is the separate 120 V AC Type F model; do not apply its ratings to T3411F.

    How many inputs does T3411F provide?

    T3411F provides 16 monitored digital inputs. Its maximum on/off response is 10 ms and its input current is 8 mA.

    Can T3411F support line-fault monitoring?

    Yes. For DC-powered inputs, fit a suitable monitoring device across the field switch and select it for the supply voltage and redundancy arrangement. Energize-to-trip safety inputs also require configured fault variables and alarms.

    What must match when replacing T3411F?

    Match the full Type F catalog number, external field supply, input monitoring network and application configuration. The chassis key positions are upper 9 and lower 7.

    Can redundant T3411F modules share one field switch?

    Yes. Two or three modules of the same type can be connected in parallel for fault-tolerant sensing. In this arrangement, a failed module can be replaced while the remaining modules continue to monitor the input.

    What supply regulation does T3411F need for line monitoring?

    Line monitoring requires a DC supply regulated within ±5%. The external supply powers the field switches and must also connect to the module field-power terminals. Confirm this supply condition before relying on line-fault detection.

    How do I distinguish a T3411F module fault from a field-line fault?

    A module fault lights the red FAULT indicator and extinguishes the green ACTIVE indicator. A channel red line-status indicator instead identifies an open or shorted field circuit when line monitoring is enabled. The yellow contact indicator alone cannot distinguish a closed contact from a shorted line.

    Manufacturer Documentation

    T3411F Product Reference

    Product photograph, identification and system notes, followed by selected original manufacturer pages for field connections, mounting and technical reference.

    PDF · 10 pages · 126.6 KB · Compiled by EWOLO CONTROL. PD-6027, Issue 1, March 2006

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    ICS Triplex T3411F

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message