Honeywell CC-PAOH51 51410070-275 is a Series C high-level analog output module for Experion PKS. It supplies 16 current-output channels for actuators and recording or indicating devices, with HART configuration and status support.
Version check: Match the complete module code, CC-TAOX51/CC-TAOX61 termination assembly and installed system configuration. Other Series C output modules use different IOTAs and are not assumed to be interchangeable.
Lifecycle status: Unknown
Product image is representative; revision or series may vary.
Contact us to request a specific version.
12-month return-to-base cover.
Eligibility per quote.
DHL, FedEx or UPS.
Or use an agreed carrier account.
Bank transfer before dispatch,
unless agreed in writing.
Honeywell CC-PAOH51 51410070-275 is a Series C HART analog output module for driving actuators and recording or indicating instruments from an Experion PKS control application. Its sixteen 4–20 mA channels carry the commanded process outputs, while HART communication supports field-device configuration and status information. Open-wire indication and internal self-diagnostics help identify channel or module problems. Each output can be configured to hold its last value or move to a selected safe value under the applicable failure condition, and the module supports the corresponding redundant Series C arrangement.
Honeywell specifies a directly settable output of 0 mA or 2.9–21.1 mA, calibrated accuracy of ±0.35% of full scale at 25°C including linearity, and an 800-ohm maximum resistive load with a 22–28 VDC supply. Output response settles within 1% of its final value in 80 ms. These limits apply under the stated manufacturer conditions.
| Parameter | Specification |
|---|---|
Product Identity |
|
| Manufacturer / complete model | Honeywell / CC-PAOH51 51410070-275 |
| Product family | Experion PKS Series C high-level analog output |
Functional Configuration |
|
| Output channels / nominal signal | 16 / 4–20 mA |
| HART function | Configuration and status; model-specific function matrix applies |
| Maximum resistive load | 800 ohms with 22–28 VDC supply |
| Redundant switchover output gap | 10 ms maximum; redundancy only |
| Non-redundant / redundant IOTA | CC-TAOX51, 6-inch / CC-TAOX61, 12-inch |
| Channel failure behavior | FAILOPT: hold last value or shed to safe value; IOM electronics failure drives output to zero |
Performance & Power |
|
| Directly settable output current | 0 mA; 2.9–21.1 mA |
| Calibrated output accuracy | ±0.35% of full scale at 25°C, including linearity |
| Output current linearity | ±0.05% of full scale, nominal |
| Output readback accuracy | ±4% of full scale |
| Output temperature drift | 0.005% of full scale per °C |
| Maximum output compliant voltage | 16 V with 22–28 VDC supply |
| Maximum open-circuit voltage | 22 V |
| Output response | Settles within 1% of final value in 80 ms |
Environment |
|
| Enclosure requirement | Series C open equipment for subpanel mounting inside a suitable enclosure. |
The Series C specification covers Experion I/O and the C300 controller. CC-PAOH51 uses the 6-inch CC-TAOX51 non-redundant IOTA or the 12-inch CC-TAOX61 redundant IOTA; a redundant arrangement also requires the corresponding module pair and configuration. Its HART function is configuration/status, so do not infer HART control-variable or fast-control support from other Series C models.
Verify the exact CC-TAOX51 or CC-TAOX61 assembly and field-loop design before wiring. The compact reference contains OEM mounting, power-test warnings and HART output-protection information; it does not include the complete terminal drawings.
| Item | Required check | Applicable limit |
|---|---|---|
| Load budget | Include the field device and wiring resistance | Maximum 800 ohms with 22–28 VDC supply |
| Signal polarity | Match the IOTA OUT+ and OUT− terminals | Use the terminal drawing for the actual non-redundant or redundant IOTA |
| External reverse polarity | Follow the OEM protection condition | A reverse-polarity external source requires current limited to 500 mA to protect IOTA surge diodes |
Protection scope: The OEM permits a short across a field-wiring pair without damaging the module or IOTA and without affecting other channels. This is a fault-protection statement, not permission to omit isolation or hazardous-area precautions.
Turn off power at the installation location as required by the OEM procedure. Apply ESD precautions and confirm that the area and work permit the installation.
Mount the correct IOTA on its backplane before fitting the module. Confirm primary and redundant positions against the system design; do not choose an IOTA by physical fit alone.
Mate the circuit board and IOTA connector, then secure the side screws and long front plastic screw. Use a No. 2 Phillips hand screwdriver; a No. 1 tip or power driver can damage the plastic screw.
Power and hazardous areas: Do not connect or disconnect cables, or install or remove components, while the control system is powered unless the location is known to be non-hazardous and the applicable OEM procedure permits the operation.
Busbar measurements: Never probe the 24 V screw hole of an unattached IOTA. The probe can contact the back channel assembly and short the carrier supply; use the designated OEM test points.
Commissioning and replacement: Verify channel mapping, load resistance, HART requirements and configured FAILOPT behavior before returning the loop to service. Use the complete OEM guide for terminal drawings and redundant wiring.
It provides 16 high-level current-output channels with a nominal 4–20 mA signal. The directly settable values are 0 mA or 2.9–21.1 mA; do not substitute a voltage-output specification from another module.
The manufacturer function matrix identifies HART configuration and status for CC-PAOH51. It does not identify this model as supporting HART on control or HART fast control. Confirm the required HART function before selecting a replacement.
Honeywell lists CC-TAOX51 for a 6-inch non-redundant arrangement and CC-TAOX61 for a 12-inch redundant arrangement. A redundant installation also requires the appropriate module pair and system configuration; a redundant IOTA by itself does not establish a complete redundant system.
The specified maximum resistive load is 800 ohms with a supply between 22 and 28 VDC. Include field-device and wiring resistance in the loop budget. The maximum output compliant voltage is 16 V under the same supply condition.
FAILOPT is configured per channel to hold the last value or shed to a safe value. The specification separately states that an IOM electronics failure drives the output to zero. Review the process consequences and configured strategy before commissioning or replacing the module.
Honeywell specifies output readback accuracy as ±4% of full scale, while calibrated output accuracy is ±0.35% of full scale at 25°C including linearity. These describe different measurements; do not use the readback figure as the calibrated output-accuracy claim.
No. It contains one branded summary and three unchanged OEM pages covering mounting, the continuing power warning and HART output protection. Use the complete Series C I/O User Guide section 5.6 for CC-TAOX51/CC-TAOX61 terminal drawings and the applicable redundant arrangement.
At the power-line frequency, the ripple is less than 100 mV peak to peak across 250 Ω.
A concise product summary with selected Honeywell mounting, power-warning and HART analog output-protection pages. Terminal drawings remain in the complete OEM guide.
PDF · 5 pages · 54.0 KB · Compiled by EWOLO CONTROL. Honeywell EPDOC-X126-en-A, November 2019; selected pages 73, 74 and 128.
Preview Product Reference (PDF)Non-redundant termination assembly for CC-PAOH51
Redundant termination assembly for CC-PAOH51
Series C HART analog output with its own IOTA requirements
Non-redundant IOTA for CC-PAOH01/CC-PAOX01
Redundant IOTA for CC-PAOH01/CC-PAOX01
Series C analog output without HART
Series C non-HART analog output
Non-redundant termination assembly for CC-PAON01
Redundant termination assembly for CC-PAON01
Analog input with HART configuration and status
Series C non-HART current-input module
Series C HART analog input module
Series C universal I/O module
Series C low-voltage digital input module
Series C bussed digital output module
EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.
We source DCS, PLC and TSI spares for maintenance and replacement.
Pay by bank transfer before dispatch, unless agreed otherwise in writing.
Model, quantity and visible condition are checked against your order.
Packaging is selected for the product and agreed shipping method.
DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.
Commercial invoice and packing list supplied. Agree extra documents before ordering.
Eligible items: 12-month return-to-base warranty from dispatch, per quotation.
Send fault details and photos. Returns need prior written approval.
REQUEST A QUOTE
Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.
Request a Quote →Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.
No online payment is requested. Final price and terms are supplied in a written quotation.
Yokogawa AAI543-H50 is a 16-channel isolated 4–20 mA output module for CENTUM FIO. It supports HART communication and standard-response switching in a dual-redundant configuration. Version check: Match the -H50 standard switchover response, hardware Style and terminal option; a redundant pair must use the same response class.
Yokogawa AAI841-H00 is a non-isolated FIO module with eight 4–20 mA inputs and eight 4–20 mA outputs. It supports up to eight loops, HART communication and dual-redundant configurations. Version check: Confirm the legacy -H00 code, hardware Style, node and terminal option; HART in an ER-bus remote node requires EB401 Rev. 2 or later.
Yokogawa AAP135-S50 is an eight-channel isolated pulse input module for CENTUM FIO. It accepts contact, voltage-pulse and current-pulse signals, with frequency limits determined by the selected signal and redundancy configuration. Version check: Match pulse source, frequency, transmitter supply and redundancy mode; dry-contact limits are lower than the 10 kHz electronic-pulse limit.
Yokogawa ADV151-P60 is a 32-channel 24 V DC digital input module for CENTUM FIO. The P version supports pushbutton input, and suffix 6 provides input-status display without explosion protection. Version check: Confirm -P60 pushbutton capability, status display, hardware Style and input polarity; do not substitute an output or SOE-capture version.
Yokogawa ADV551-P60 is a 32-channel current-sink transistor output module for CENTUM FIO. It supports status, pulse-width and time-proportioning output patterns with output-status display. Version check: Match -P60, sink-output load and configured point-mode pattern; check paired-channel and redundancy restrictions before replacement.
Yokogawa ALR121-S50 is a two-port RS-422/RS-485 serial communication module for CENTUM N-IO/FIO systems. It exchanges subsystem data with the FCS using supported functions such as Modbus RTU and FA-M3 communication. Version check: Confirm RS-422/RS-485, the common protocol selected for both ports, baud rate, data mapping and the installed redundancy arrangement.
Yokogawa EC401-50 is a one-port ESB bus coupler for CENTUM N-IO/FIO. It links the field control unit to supported ESB nodes at 128 Mbps and supports single or dual-redundant module arrangements. Version check: For a CP471 system, require EC401 Style S3 or later; also match the one-port ESB topology, node types and redundancy arrangement.
Yokogawa EC402-50 is a two-port ESB bus coupler for CENTUM N-IO/FIO. Its upper and lower ESB connections link supported field control units to I/O nodes at 128 Mbps. Version check: Match the two-port ESB topology and system release; the 12-nodes-per-port exception applies only to the specified A2FV50 star configuration.
No online payment is requested. Final price and terms are supplied in a written quotation.
Scan to Wechat :
Scan to WhatsApp :