ISO 9001:2015 certified industrial automation spare parts supplier

Honeywell CC-PDIL01 51405040-176 24V Digital Input Module

Honeywell CC-PDIL01 51405040-176 is a 32-channel Series C 24V digital input IOM for Experion PKS. Verify the matching IOTA and field-power configuration.

Version check: Confirm the complete CC-PDIL01 51405040-176 part number, matching IOTA and redundancy configuration before ordering.

Download
  • CC-PDIL01 51405040-176 — Series C 24V discrete inputs with open-wire detection

    Honeywell CC-PDIL01 51405040-176 is a Series C digital input module for acquiring equipment and process on/off states in an Experion PKS system. It accepts 32 nominal 24 VDC discrete inputs and supplies their values and status to the control application. Internal diagnostics support data integrity, while open-wire detection can identify a broken field circuit and mark the affected process value invalid when that function is correctly implemented. Direct or reverse indication, selectable field-power arrangements and optional redundancy let this input interface match the required Series C application.

    Hardware specifications. The specified field-power range is 18-30 VDC. Honeywell gives an ON threshold of at least 13 V or 3 mA and an OFF threshold of at most 5 V or 1.2 mA, an input impedance of 4.2 kilohms and a 5 ms filter-plus-isolation delay with a tolerance of 20%. Optical isolation is within the IOM; this is not a claim of separate isolation between every channel.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer / complete model Honeywell / CC-PDIL01 51405040-176
    Product identity Series C 24 V digital input IOM; separate IOTA required

    Functional Configuration

    Input channels 32
    ON input threshold 13 VDC minimum or 3 mA minimum
    OFF input threshold 5 VDC maximum or 1.2 mA maximum
    Isolation Optical isolation in IOM; 1500 VAC RMS or +/-1500 VDC, referenced to common
    Guaranteed ON field resistance 300 ohms maximum at 15 VDC
    Guaranteed OFF field resistance 30 kilohms minimum at 30 VDC
    Open-wire detection Optional; requires appropriate field resistor and configuration; detected open wire invalidates input PV
    Non-redundant IOTA CC-TDIL01,9-inch
    Redundant IOTA CC-TDIL11,12-inch; appropriate module pair and configuration required
    Sequence of events Not the CC-PDIL01 function; use the applicable CC-PDIS01 selection evidence

    Performance & Power

    Nominal signal / field-power range 24 VDC / 18-30 VDC
    Input impedance 4.2 kilohms
    Filter plus isolation delay 5 ms, tolerance +/-20%
    Field power Internal or external, selected for the applicable IOTA

    Environment

    Enclosure requirement Series C open equipment for subpanel mounting inside a suitable enclosure.

    Compatibility & Selection Guide

    System compatibility. Series C I/O is used with Experion PKS and its C300 control architecture. CC-PDIL01 pairs with the 9-inch CC-TDIL01 non-redundant IOTA or 12-inch CC-TDIL11 redundant IOTA. A redundant arrangement requires the corresponding IOM pair and configuration. CC-PDIL51 has different diagnostic capability, while sequence-of-events acquisition belongs to CC-PDIS01; neither difference should be ignored when selecting a replacement.

    Wiring & Installation Reference

    Use the actual CC-TDIL01 or CC-TDIL11 terminal drawing and field-power arrangement. The compact PDF includes the non-redundant CC-TDIL01 TB3/field-circuit page and complete mounting/power-test warning; it does not include every channel screw table or redundant diagram.

    Field power and input circuit

    Item Connection / requirement Verification
    TB1 / TB2 TB1 channels 1-16; TB2 channels 17-32 Confirm individual screws against the complete OEM terminal map
    TB3 internal power Screw 1 internal 24 V; screw 2 internal return Match the internal field-power arrangement
    TB3 external power Screw 3 external 24 V; screw 4 external return Verify external supply and return before energizing
    Open-wire detection Specified 22-kilohm resistor in the field circuit Use the OEM field diagram and enable the appropriate diagnostic

    Diagnostic boundary: The resistor arrangement is specific to the low-voltage DI circuit. Do not copy a resistor value from Universal I/O or infer that CC-PDIL51 supports the same open-wire function.

    Open CC-TDIL01 TB3 and open-wire circuit (PDF page 5)

    Mounting and commissioning

    1. Isolate and inspect

      Turn off power for initial installation as required by the OEM procedure. Verify the exact IOM/IOTA, grounded enclosure, field-power selection and ESD precautions.

    2. Mount the IOTA, then the IOM

      Attach the IOTA to its backplane before mating the module circuit board to the IOTA connector. Secure the module with the specified side screws and long front plastic screw.

    3. Verify the input behavior

      Check each field point, direct/reverse indication and open-wire configuration before service. Confirm that configured failure handling is appropriate for the process.

    Open OEM mounting and power warnings (PDF pages 3-4)

    Installation precautions

    • Hazardous-area work: Do not connect or disconnect cables or install/remove components while powered unless the location is known to be non-hazardous and the applicable OEM procedure permits the operation.

    • Plastic fixing screw: Use only a No. 2 Phillips hand screwdriver. A No. 1 tip or powered driver can damage the long gray plastic screw.

    • Power testing: Never insert a test probe into the 24 V screw hole of an unattached IOTA. The probe can touch the back channel and short the carrier supply; use the designated OEM test locations.

    Frequently Asked Questions

    Is CC-PDIL01 51405040-176 an IOM or a termination assembly?

    It is the 32-channel digital input IOM, which contains the electronics. The separate IOTA provides the field terminals and mounting interface. CC-TDIL01 and CC-TDIL11 are the corresponding standard non-redundant and redundant IOTAs; their identity and inclusion must be checked separately.

    What input levels does CC-PDIL01 51405040-176 recognize?

    Honeywell specifies ON at a minimum 13 VDC or 3 mA, and OFF at a maximum 5 VDC or 1.2 mA. The field-power range is 18-30 VDC and input impedance is 4.2 kilohms. Verify the field device and wiring resistance against these conditions.

    How is open-wire detection enabled for CC-PDIL01 51405040-176?

    The low-voltage DI guide calls for the specified 22-kilohm resistor in the field wiring, shown in the CC-TDIL01 circuit, together with the appropriate channel configuration. A detected open wire invalidates the input process value; review the configured process response rather than treating it as an ordinary contact state.

    Can CC-PDIL01 51405040-176 be replaced by CC-PDIL51 without reviewing diagnostics?

    No interchangeability is assumed. The OEM identifies open-wire detection for CC-PDIL01 and excludes that function for CC-PDIL51. Their specified IOTAs also differ. Check the required diagnostics, exact termination assembly and system configuration before selecting a replacement.

    Does CC-PDIL01 51405040-176 provide sequence-of-events inputs?

    The Series C function matrix distinguishes CC-PDIS01 as the sequence-of-events input model. CC-PDIL01 is the standard 24 V digital input selection; do not infer SOE support from its 32-channel count or shared family.

    Which power and redundancy arrangements apply to CC-PDIL01 51405040-176?

    The applicable IOTA selects internal or external field power. CC-TDIL01 is the 9-inch non-redundant IOTA and CC-TDIL11 is the 12-inch redundant IOTA. Redundancy requires the appropriate two-module arrangement and configuration; one IOTA alone does not establish a complete redundant system.

    What is included in the CC-PDIL01 51405040-176 reference PDF?

    It contains a branded technical summary and three unchanged OEM pages: mounting, the continuing power-test caution, and the CC-TDIL01 TB3/open-wire field circuit. Use the complete Series C User Guide section 5.10 for the individual channel screw tables, redundant wiring and other IOTA arrangements.

    Which CC-GDIL assemblies does Honeywell list for a CC-PDIL01 51405040-176 with galvanic isolation?

    The 6-inch CC-GDIL21 is the nonredundant option. The 12-inch CC-GDIL11 is the redundant option.

    Manufacturer Documentation

    CC-PDIL01 51405040-176 Product Reference

    A compact product summary with selected original Honeywell mounting, power-test safety and CC-TDIL01 open-wire circuit pages.

    PDF · 5 pages · 99.7 KB · Compiled by EWOLO CONTROL. Honeywell EPDOC-X126-en-A, November 2019; selected pages73,74 and146.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Honeywell CC-PDIL01 51405040-176

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.