ISO 9001:2015 certified industrial automation spare parts supplier

Honeywell CC-PAIN01 51410069-176 Analog Input Module

Honeywell CC-PAIN01 51410069-176 is a Series C high-level analog input module for Experion PKS. It accepts 16 single-ended 4–20 mA process signals through a matching non-HART termination assembly.

Version check: Confirm the complete module code, installed IOTA and system configuration before ordering. CC-PAIN01 is the non-HART current-input model; HART and universal I/O models are separate products.

Download
  • Series C analog input for 4–20 mA process signals

    Honeywell CC-PAIN01 51410069-176 is a Series C high-level analog input module for bringing current-loop measurements into an Experion PKS control system. Its sixteen single-ended channels accept 4–20 mA signals from two-wire or self-powered transmitters, converting field measurements into input data for the control application. The module combines analog acquisition with self-diagnostics, a 50 ms input scan and individually protected transmitter-power circuits. It serves standard analog loops without HART communication and supports a redundant arrangement when the corresponding Series C termination assembly and system configuration are used.

    The module uses single-ended inputs, an internal 200-ohm sense resistor and a 16-bit analog-to-digital converter. Honeywell specifies a 50 ms input scan rate and supports two-wire and self-powered transmitters. Input accuracy is ±0.075% of full scale at 23.5 ±2°C and ±0.15% over 0–60°C.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer / model Honeywell / CC-PAIN01 51410069-176
    Product family Experion PKS Series C high-level analog input

    Functional Configuration

    Input channels 16, single-ended
    Nominal input signal 4–20 mA; non-HART
    Supported transmitter arrangements Two-wire and self-powered transmitters
    Sense resistance 200 ohms, internal
    Input filter Single pole; −3 dB at 6 Hz
    Common-mode rejection 70 dB from DC to 60 Hz with 500-ohm source imbalance
    Non-redundant IOTA CC-TAIN01, 6-inch assembly
    Redundant IOTA CC-TAIN11, 12-inch assembly; redundant system requirements apply

    Performance & Power

    ADC resolution / scan rate 16 bits / 50 ms
    Accuracy at reference temperature ±0.075% of full scale at 23.5 ±2°C
    Accuracy over operating range ±0.15% of full scale from 0 to 60°C
    Maximum normal-mode input voltage ±30 V

    Environment

    Enclosure requirement Series C open equipment for subpanel mounting inside a suitable enclosure.

    Compatibility & Selection Guide

    Series C I/O modules mount onto an I/O Termination Assembly that provides field connections and power distribution. CC-PAIN01 uses CC-TAIN01 for a non-redundant arrangement or CC-TAIN11 for a redundant arrangement; redundancy also requires the corresponding second module and system configuration. Verify the termination assembly and Experion release requirements for the installed system rather than assuming that other Series C analog modules are interchangeable.

    Wiring & Installation Reference

    Use the Honeywell Series C I/O User Guide for the exact CC-TAIN01/CC-TAIN11 assembly. The reference PDF includes unchanged OEM mounting pages and a three-wire transmitter example; it is a selected reference, not the complete installation manual.

    Field wiring and transmitter checks

    Arrangement Connection check Important condition
    Two-wire transmitter Use the specified signal and return terminals All 16 channels support two-wire instruments
    System-ground self-powered transmitter Confirm the system-ground wiring arrangement For loop-powered or three-wire system-ground arrangements, channels 1–12 need a Series C ground terminal; the OEM recommends channels 13–16 for the three-wire example
    Three-wire example OEM example uses channel 13 TB1-25, TB1-26 and TB2-1 refer to the illustrated IOTA example, not a universal pinout

    Loop budget: Check transmitter minimum voltage and cable resistance against the OEM loop calculation; do not assume every cable length or transmitter will operate correctly.

    Open the OEM three-wire example (PDF pages 5–6)

    Mounting sequence

    1. Isolate and prepare

      Remove power as instructed by the manufacturer. Use ESD protection and verify the installation area is safe before installing or removing modules.

    2. Secure the termination assembly

      Install the correct IOTA on its backplane before attaching the I/O module. Confirm the assembly and primary/redundant module positions against the system design.

    3. Seat and fasten the module

      Mate the module to the IOTA and secure the side and front screws. Use a No. 2 Phillips hand screwdriver; do not use a No. 1 tip or a power driver.

    Open OEM mounting and power warnings (PDF pages 3–4)

    Installation precautions

    • Power and hazardous areas: Do not connect or disconnect wiring, or install or remove equipment, with power applied unless the area is known to be non-hazardous and the manufacturer procedure permits the operation.

    • Use designated test points: Never probe the 24 V screw hole of an unattached IOTA to test the busbar. Follow the OEM test-point procedure and the complete warning on the following source page.

    • Match the exact assembly: Confirm terminal numbers, grounding, loop resistance and the redundant/non-redundant IOTA before energizing. Consult the complete OEM guide for terminal drawings and conditions outside the selected PDF pages.

    Frequently Asked Questions

    What does CC-PAIN01 51410069-176 do in an Experion PKS system?

    It is a Honeywell Series C high-level analog input module that measures 16 single-ended 4–20 mA process signals. The matching IOTA provides field terminations and power connections.

    Does CC-PAIN01 51410069-176 support HART communication?

    No. Honeywell identifies CC-PAIN01 as the non-HART current-input model. A HART input requirement must be checked against a suitable HART module, termination assembly and system configuration.

    Which termination assemblies are used with CC-PAIN01 51410069-176?

    The manufacturer specification lists CC-TAIN01 for the non-redundant arrangement and CC-TAIN11 for the redundant arrangement. A redundant installation also needs the required second module and configuration; the IOTA designation alone does not establish a complete redundant system.

    Can CC-PAIN01 51410069-176 accept self-powered transmitters?

    Yes. Standard self-powered transmitters can use all 16 channels without custom wiring. For self-powered transmitters with loop power (system ground), and for three-wire transmitters using system ground, channels 1–12 need a screw terminal at Series C ground for one transmitter lead. The OEM guide recommends channels 13–16 for its three-wire example. Verify the exact arrangement and IOTA terminal drawing.

    What input accuracy and scan rate apply to CC-PAIN01 51410069-176?

    Honeywell specifies a 50 ms scan rate, 16-bit ADC resolution, ±0.075% full-scale accuracy at 23.5 ±2°C and ±0.15% full-scale accuracy over 0–60°C. These are specified measurement conditions, not a guarantee for an unverified field installation.

    Is the CC-PAIN01 51410069-176 reference PDF the complete user manual?

    No. It contains one branded product summary and four unchanged OEM pages covering module mounting, the continuing power warning and a three-wire transmitter example. The full Honeywell specification and user guide are identified in the PDF for additional terminal drawings and system requirements.

    What should be checked before replacing CC-PAIN01 51410069-176?

    Compare the full printed module code, IOTA type, channel signal arrangements and Experion configuration. Confirm module revision and the actual scope of supply when requesting a quotation. Do not assume that a HART or universal I/O model is a direct replacement.

    How much coupling between input channels is specified for CC-PAIN01 51410069-176?

    Channel-to-channel crosstalk is −60 dB from DC through 60 Hz.

    Manufacturer Documentation

    CC-PAIN01 51410069-176 Product Reference

    A concise product summary with selected Honeywell mounting, power-warning and three-wire transmitter reference pages. Includes the continuation of the OEM connection table.

    PDF · 6 pages · 73.9 KB · Compiled by EWOLO CONTROL. Selected Honeywell OEM pages; not the complete manual.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Honeywell CC-PAIN01 51410069-176

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.