8C-TDILA1
Series 8 nonredundant digital input IOTA
No online payment is requested. Final price and terms are supplied in a written quotation.
ISO 9001:2015 certified industrial automation spare parts supplier



Honeywell 8C-PDILA1 51454471-175 is the coated Series 8 digital input module for 32 discrete 24 VDC signals. It supports internal or external field power, direct or reverse indication and optional redundancy for the Series 8 I/O platform.
Version check: Confirm standard DI rather than SOE or pulse accumulation, the installed 8C-TDILA1 or 8C-TDILB1 IOTA, and internal or external field power before replacing 8C-PDILA1.
Lifecycle status: Unknown
Product image is representative; revision or series may vary.
Contact us to request a specific version.
12-month return-to-base cover.
Eligibility per quote.
DHL, FedEx or UPS.
Or use an agreed carrier account.
Bank transfer before dispatch,
unless agreed in writing.
Honeywell 8C-PDILA1 51454471-175 is the coated Series 8 standard digital input module for collecting equipment and process on/off states in an Experion control system. Its 32 channels accept nominal 24 VDC discrete signals and make those states available to the control application. Internal diagnostics support data integrity, while direct or reverse input indication allows the displayed state to follow the configured signal logic. Optional redundancy is supported. The standard DI role is important when selecting this model, because sequence-of-events recording and pulse accumulation belong to separately identified Series 8 input models.
Hardware specifications. The 8C-PDILA1 has 32 inputs, a 24 VDC voltage rating and an 18–30 VDC DI power range. Its module current rating is 95 mA. The specified ON threshold is at least 13 VDC or 3 mA; the OFF threshold is at most 5 VDC or 1.2 mA. Input impedance is 4.2 kΩ, and the input filter and isolation introduce an absolute delay of 5 ms ±20%. The module electronics are conformally coated.
| Parameter | Specification |
|---|---|
Product Identity |
|
| Product family | Series 8 I/O |
Functional Configuration |
|
| I/O function | 24 VDC digital input |
| Input channels | 32 |
| ON sense threshold | 13 VDC minimum or 3 mA minimum |
| OFF sense threshold | 5 VDC maximum or 1.2 mA maximum |
| Isolation technique | Optical, in the IOM |
| System-to-field isolation | 1000 VAC RMS or ±1500 VDC; external user-supplied field power required |
| Nonredundant IOTA | 8C-TDILA1, coated, 9 in |
| Redundant IOTA | 8C-TDILB1, coated, 12 in |
Performance & Power |
|
| Voltage rating | 24 VDC |
| DI power range | 18–30 VDC |
| Module current rating | 95 mA |
| Input impedance | 4.2 kΩ |
| Input filter and isolation delay | 5 ms ±20% |
Environment |
|
| Protection of electronics | Conformal coating |
System compatibility. The 8C-PDILA1 belongs to Honeywell’s Series 8 I/O platform used with the C300 controller. It supports direct or reverse input indication, onboard excitation, internal or external field power and optional redundancy. System-to-field isolation is available when external user-supplied power is used. If the application requires 1 ms event time tags or pulse accumulation, verify the dedicated function model rather than selecting on channel count alone.
Use the model-specific Series 8 IOTA and the installed system wiring documentation. The reference PDF provides the applicable connection limits, termination-assembly choices and configuration notes.
| Check | Requirement | Application |
|---|---|---|
| Field input | 24 VDC discrete | 18–30 VDC DI power |
| ON / OFF | ≥13 VDC / ≤5 VDC | Or ≥3 mA / ≤1.2 mA |
| IOTA | 8C-TDILA1 / 8C-TDILB1 | Nonredundant / redundant |
The module plugs onto its IOTA, where the field terminals and power distribution are located. Confirm the installed termination assembly before moving wiring.
Use 8C-TDILA1 for nonredundant operation or 8C-TDILB1 for redundant operation. These are the documented termination assemblies for 8C-PDILA1.
Check the internal or external field-power selection and the 18–30 VDC DI power range. The system-to-field isolation option requires external user-supplied power.
Check the connected device against the ON and OFF thresholds. Honeywell lists 300 Ω maximum field resistance at 15 VDC for guaranteed ON and 30 kΩ minimum at 30 VDC for guaranteed OFF.
Isolation condition. Do not assume isolated operation from the module name alone; the specified system-to-field isolation depends on the external field-power arrangement.
Response requirements. Include the specified 5 ms ±20% input filter and isolation delay when checking whether the application can detect short discrete signals.
It accepts 32 discrete 24 VDC input signals. Honeywell specifies an 18–30 VDC DI power range.
Honeywell’s function matrix identifies 8C-PDILA1 as the standard DI model. It assigns the SOE function to 8C-PDISA1, whose specification explicitly provides 1 ms event resolution. Do not assume the standard DI module provides that function.
Use the documented 8C-TDILA1 nonredundant IOTA or 8C-TDILB1 redundant IOTA. Their nominal sizes are 9 inches and 12 inches respectively.
The ON threshold is at least 13 VDC or 3 mA. The OFF threshold is at most 5 VDC or 1.2 mA. These guaranteed limits should be checked against the connected field device.
Yes, for the specified system-to-field isolation option. Honeywell’s footnote states that this option is available only with external user-supplied power; the module also supports an internal field-power arrangement.
Honeywell specifies an absolute delay of 5 ms ±20% across the input filter and isolation. This value is a hardware input delay, not a promise for the complete control-system response.
No. Honeywell lists 8C-PDIPA1 separately for pulse accumulation. Confirm the required input function and configured module type before choosing a replacement.
Yes. The input supports direct or reverse indication, so either contact state can correspond to an active indication.
Product identification and application notes, followed by selected Honeywell original pages covering Series 8 hardware, the matching IOTA and model-specific electrical limits.
PDF · 7 pages · 117.0 KB · Compiled by EWOLO CONTROL. Honeywell S803-150-530, May 2024, Version 1.0.
Preview Product Reference (PDF)Series 8 nonredundant digital input IOTA
Series 8 redundant digital input IOTA
Series 8 32-channel sequence-of-events input module
Series 8 digital input and pulse accumulation module
Series 8 16-channel differential HART analog input module
Series 8 16-channel single-ended HART analog input module
Series 8 16-channel single-ended analog input module
Series 8 16-channel RTD and thermocouple input module
Series 8 16-channel HART analog output module
Series 8 16-channel analog output module without HART
Series 8 32-channel 24 VDC digital output module
Series 8 nonredundant analog output IOTA
Series 8 redundant analog output IOTA
Series 8 nonredundant digital output IOTA
Series 8 redundant digital output IOTA
EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.
We source DCS, PLC and TSI spares for maintenance and replacement.
Pay by bank transfer before dispatch, unless agreed otherwise in writing.
Model, quantity and visible condition are checked against your order.
Packaging is selected for the product and agreed shipping method.
DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.
Commercial invoice and packing list supplied. Agree extra documents before ordering.
Eligible items: 12-month return-to-base warranty from dispatch, per quotation.
Send fault details and photos. Returns need prior written approval.
REQUEST A QUOTE
Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.
Request a Quote →Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.
No online payment is requested. Final price and terms are supplied in a written quotation.
Yokogawa AAI543-H50 is a 16-channel isolated 4–20 mA output module for CENTUM FIO. It supports HART communication and standard-response switching in a dual-redundant configuration. Version check: Match the -H50 standard switchover response, hardware Style and terminal option; a redundant pair must use the same response class.
Yokogawa AAI841-H00 is a non-isolated FIO module with eight 4–20 mA inputs and eight 4–20 mA outputs. It supports up to eight loops, HART communication and dual-redundant configurations. Version check: Confirm the legacy -H00 code, hardware Style, node and terminal option; HART in an ER-bus remote node requires EB401 Rev. 2 or later.
Yokogawa AAP135-S50 is an eight-channel isolated pulse input module for CENTUM FIO. It accepts contact, voltage-pulse and current-pulse signals, with frequency limits determined by the selected signal and redundancy configuration. Version check: Match pulse source, frequency, transmitter supply and redundancy mode; dry-contact limits are lower than the 10 kHz electronic-pulse limit.
Yokogawa ADV151-P60 is a 32-channel 24 V DC digital input module for CENTUM FIO. The P version supports pushbutton input, and suffix 6 provides input-status display without explosion protection. Version check: Confirm -P60 pushbutton capability, status display, hardware Style and input polarity; do not substitute an output or SOE-capture version.
Yokogawa ADV551-P60 is a 32-channel current-sink transistor output module for CENTUM FIO. It supports status, pulse-width and time-proportioning output patterns with output-status display. Version check: Match -P60, sink-output load and configured point-mode pattern; check paired-channel and redundancy restrictions before replacement.
Yokogawa ALR121-S50 is a two-port RS-422/RS-485 serial communication module for CENTUM N-IO/FIO systems. It exchanges subsystem data with the FCS using supported functions such as Modbus RTU and FA-M3 communication. Version check: Confirm RS-422/RS-485, the common protocol selected for both ports, baud rate, data mapping and the installed redundancy arrangement.
Yokogawa EC401-50 is a one-port ESB bus coupler for CENTUM N-IO/FIO. It links the field control unit to supported ESB nodes at 128 Mbps and supports single or dual-redundant module arrangements. Version check: For a CP471 system, require EC401 Style S3 or later; also match the one-port ESB topology, node types and redundancy arrangement.
Yokogawa EC402-50 is a two-port ESB bus coupler for CENTUM N-IO/FIO. Its upper and lower ESB connections link supported field control units to I/O nodes at 128 Mbps. Version check: Match the two-port ESB topology and system release; the 12-nodes-per-port exception applies only to the specified A2FV50 star configuration.
No online payment is requested. Final price and terms are supplied in a written quotation.
Scan to Wechat :