8C-TAOXA1
Series 8 nonredundant analog output IOTA
No online payment is requested. Final price and terms are supplied in a written quotation.
ISO 9001:2015 certified industrial automation spare parts supplier



Honeywell 8C-PAOHA1 51454469-275 is a Series 8 analog output module for 16 current-output loops. It provides 4–20 mA outputs with HART support for actuators and recording or indicating devices, with optional redundancy and per-channel safe-state configuration.
Version check: Confirm the 8C-PAOHA1 label, HART output requirement, installed 8C-TAOXA1 or 8C-TAOXB1 IOTA and channel FAILOPT settings before replacement.
Lifecycle status: Unknown
Product image is representative; revision or series may vary.
Contact us to request a specific version.
12-month return-to-base cover.
Eligibility per quote.
DHL, FedEx or UPS.
Or use an agreed carrier account.
Bank transfer before dispatch,
unless agreed in writing.
Honeywell 8C-PAOHA1 51454469-275 is the coated Series 8 analog output module for sending control commands from an Experion system to field devices. It provides sixteen 4–20 mA outputs for actuators and recording or indicating instruments, with HART communication available for supported smart-device functions. The module combines current-output control with self-diagnostics and open-wire indication, helping operators identify a signal-path problem as well as control the process. Each channel has configurable failure behavior, and the supported redundant arrangement provides an additional selection option for the system design.
Hardware specifications. The 8C-PAOHA1 provides 16 channels, a 24 VDC voltage rating and a 205 mA module current rating. The specified load range is 50–800 Ω with a 22–28 VDC supply. Calibrated accuracy is ±0.2% of full scale at 25°C, including linearity, and an output change settles within 1% of its final value in 80 ms. The electronics have conformal coating.
| Parameter | Specification |
|---|---|
Product Identity |
|
| Manufacturer | Honeywell |
| Complete part number | 8C-PAOHA1 51454469-275 |
| Product family | Series 8 I/O |
Functional Configuration |
|
| I/O function | HART analog output |
| Output channels | 16 |
| Nominal output | 4–20 mA |
| Directly settable output range | 2.9–21.1 mA |
| Redundancy switchover gap | 10 ms maximum at 0 mA; redundant configuration only |
| Nonredundant IOTA | 8C-TAOXA1, coated, 6 in |
| Redundant IOTA | 8C-TAOXB1, coated, 12 in |
Performance & Power |
|
| Voltage rating | 24 VDC |
| Module current rating | 205 mA |
| Load resistance | 50–800 Ω with a 22–28 VDC supply |
| Calibrated accuracy | ±0.2% of full scale at 25°C, including linearity |
| Maximum compliant output voltage | 16 V with a 22–28 VDC supply |
| Output response | Within 1% of final value in 80 ms |
Environment |
|
| Protection of electronics | Conformal coating |
System compatibility. The 8C-PAOHA1 is documented in Honeywell’s Series 8 I/O and C300 controller platform. It supports HART-capable multivariable devices, open-wire detection and optional redundancy. Each channel can hold its last value or move to a configured safe value through FAILOPT; an IOM electronics failure instead forces the output to zero. Select this model when the existing application requires HART output functionality and confirm the installed Series 8 configuration before replacement.
Use the model-specific Series 8 IOTA and the installed system wiring documentation. The reference PDF provides the applicable connection limits, termination-assembly choices and configuration notes.
| Check | Requirement | Application |
|---|---|---|
| Signal | 4–20 mA with HART | 16 output channels |
| Load | 50–800 Ω | At 22–28 VDC supply |
| IOTA | 8C-TAOXA1 / 8C-TAOXB1 | Nonredundant / redundant |
The module plugs onto its IOTA, where the field terminals and power distribution are located. Confirm the installed termination assembly before moving wiring.
Use the documented 8C-TAOXA1 nonredundant IOTA or 8C-TAOXB1 redundant IOTA. The IOM plugs onto the IOTA; field terminations remain on that assembly.
Check the load against the specified 50–800 Ω range at 22–28 VDC. Honeywell lists 16 V maximum compliant output voltage under these supply conditions.
Check each channel’s FAILOPT selection and configured safe value. An IOM electronics failure forces the output to zero regardless of hold-last-value configuration.
Output interruption. A redundant switchover can produce a gap of up to 10 ms at zero output current; check the connected process device’s requirements.
Cabinet conditions. Honeywell’s Series 8 environmental limits are tied to the specified cabinet conditions. The reference distinguishes 0–50°C external ambient from 0–60°C internal ambient and includes humidity derating above 40°C.
It provides sixteen 4–20 mA analog outputs with HART support. Honeywell describes its function as supplying constant current to actuators and recording or indicating devices.
Honeywell lists 8C-PAOHA1 as the HART model and 8C-PAONA1 as the model without HART. Both are shown with the same two AO IOTA options, but that alone does not establish a direct replacement. Check the configured module type and whether the application uses HART before changing models.
The specified IOTAs are 8C-TAOXA1 for nonredundant operation and 8C-TAOXB1 for redundant operation. Their nominal sizes are 6 inches and 12 inches respectively.
The specified load resistance is 50–800 Ω with a 22–28 VDC supply. Honeywell lists a maximum compliant output voltage of 16 V under those supply conditions.
FAILOPT can be configured per channel to hold the last value or move to a safe value. If the IOM electronics fails, Honeywell states that the output always goes to zero. These are separate cases and must both be considered in the application.
Yes. Honeywell specifies open-wire detection with a Channel Soft Failure indication.
No zero-gap claim is supported. The specification allows a maximum 10 ms gap at 0 mA when a redundant pair switches over.
The specified ripple across a 250 Ω load is below 100 mV peak-to-peak at the power-line frequency.
Product identification and application notes, followed by selected Honeywell original pages covering Series 8 hardware, the matching IOTA and model-specific electrical limits.
PDF · 8 pages · 115.3 KB · Compiled by EWOLO CONTROL. Honeywell S803-150-530, May 2024, Version 1.0.
Preview Product Reference (PDF)Series 8 nonredundant analog output IOTA
Series 8 redundant analog output IOTA
Series 8 16-channel analog output module without HART
Series 8 16-channel differential HART analog input module
Series 8 16-channel single-ended HART analog input module
Series 8 16-channel single-ended analog input module
Series 8 16-channel RTD and thermocouple input module
Series 8 32-channel 24 VDC digital input module
Series 8 32-channel sequence-of-events input module
Series 8 digital input and pulse accumulation module
Series 8 32-channel 24 VDC digital output module
Series 8 nonredundant digital input IOTA
Series 8 redundant digital input IOTA
Series 8 nonredundant digital output IOTA
Series 8 redundant digital output IOTA
EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.
We source DCS, PLC and TSI spares for maintenance and replacement.
Pay by bank transfer before dispatch, unless agreed otherwise in writing.
Model, quantity and visible condition are checked against your order.
Packaging is selected for the product and agreed shipping method.
DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.
Commercial invoice and packing list supplied. Agree extra documents before ordering.
Eligible items: 12-month return-to-base warranty from dispatch, per quotation.
Send fault details and photos. Returns need prior written approval.
REQUEST A QUOTE
Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.
Request a Quote →Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.
No online payment is requested. Final price and terms are supplied in a written quotation.
Yokogawa AAI543-H50 is a 16-channel isolated 4–20 mA output module for CENTUM FIO. It supports HART communication and standard-response switching in a dual-redundant configuration. Version check: Match the -H50 standard switchover response, hardware Style and terminal option; a redundant pair must use the same response class.
Yokogawa AAI841-H00 is a non-isolated FIO module with eight 4–20 mA inputs and eight 4–20 mA outputs. It supports up to eight loops, HART communication and dual-redundant configurations. Version check: Confirm the legacy -H00 code, hardware Style, node and terminal option; HART in an ER-bus remote node requires EB401 Rev. 2 or later.
Yokogawa AAP135-S50 is an eight-channel isolated pulse input module for CENTUM FIO. It accepts contact, voltage-pulse and current-pulse signals, with frequency limits determined by the selected signal and redundancy configuration. Version check: Match pulse source, frequency, transmitter supply and redundancy mode; dry-contact limits are lower than the 10 kHz electronic-pulse limit.
Yokogawa ADV151-P60 is a 32-channel 24 V DC digital input module for CENTUM FIO. The P version supports pushbutton input, and suffix 6 provides input-status display without explosion protection. Version check: Confirm -P60 pushbutton capability, status display, hardware Style and input polarity; do not substitute an output or SOE-capture version.
Yokogawa ADV551-P60 is a 32-channel current-sink transistor output module for CENTUM FIO. It supports status, pulse-width and time-proportioning output patterns with output-status display. Version check: Match -P60, sink-output load and configured point-mode pattern; check paired-channel and redundancy restrictions before replacement.
Yokogawa ALR121-S50 is a two-port RS-422/RS-485 serial communication module for CENTUM N-IO/FIO systems. It exchanges subsystem data with the FCS using supported functions such as Modbus RTU and FA-M3 communication. Version check: Confirm RS-422/RS-485, the common protocol selected for both ports, baud rate, data mapping and the installed redundancy arrangement.
Yokogawa EC401-50 is a one-port ESB bus coupler for CENTUM N-IO/FIO. It links the field control unit to supported ESB nodes at 128 Mbps and supports single or dual-redundant module arrangements. Version check: For a CP471 system, require EC401 Style S3 or later; also match the one-port ESB topology, node types and redundancy arrangement.
Yokogawa EC402-50 is a two-port ESB bus coupler for CENTUM N-IO/FIO. Its upper and lower ESB connections link supported field control units to I/O nodes at 128 Mbps. Version check: Match the two-port ESB topology and system release; the 12-nodes-per-port exception applies only to the specified A2FV50 star configuration.
No online payment is requested. Final price and terms are supplied in a written quotation.