Emerson KJ2231X1-EA1 DeltaV SIS Relay Module

Emerson KJ2231X1-EA1 is a DeltaV SIS relay module for switching field loads that require higher current or voltage than the logic solver output directly supports. It opens the field-power contacts when de-energized.

Version check: Confirm the KJ2231X1-EA1 nameplate, DeltaV SIS application, load voltage/current and required proof-test arrangement before ordering.

Download
  • Emerson KJ2231X1-EA1 DeltaV SIS Relay Module

    Emerson KJ2231X1-EA1 is a DeltaV SIS relay module that extends a logic solver's discrete output to field loads requiring higher switching current or voltage. It provides the relay interface between the safety-system command and the final load, opening the field-power contacts when de-energized. Three internal relays operate together during normal service and lose coil power on a shutdown demand; each can be proof-tested in the field. This makes the module relevant to safety applications that require relay switching beyond the native output capability.

    Hardware specifications. KJ2231X1-EA1 uses a 24 VDC, 70 mA input and provides relay contact ratings of 2.5 A at 30 VDC or 250 VAC. The SIS relay design contains three relays, each capable of being proof-tested in the field.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Emerson
    Complete identification KJ2231X1-EA1
    Product type SIS relay module
    Dimensions (H × W × D) 100 × 22.5 × 114 mm

    Functional Configuration

    System DeltaV SIS
    AC contact rating 250 VAC at 2.5 A
    DC contact rating 30 VDC at 2.5 A
    Operating action Field-power contacts open when de-energized
    Internal relay arrangement Three relays; each field proof-testable
    Mounting Horizontal or vertical DIN rail
    Family software prerequisite DeltaV v8.3 or later

    Performance & Power

    Input power 24 VDC, 70 mA

    Environment

    Operating temperature −40 to +70 °C horizontal; −40 to +60 °C vertical
    Relative humidity 5–95%, non-condensing
    Protection IP20

    Compatibility & Selection Guide

    System compatibility. KJ2231X1-EA1 is a conditioning component for the DeltaV SIS system. Emerson lists DeltaV v8.3 or later for this component family. Confirm the logic-solver application, load rating and proof-test procedure; the module rating alone does not establish the integrity level of the complete safety function.

    Wiring & Installation Reference

    Use the DeltaV SIS relay documentation and the approved safety application procedure. The linked original pages show relay ratings and the mounting-orientation limits; they are product references rather than wiring diagrams.

    Supply and relay load

    Input supply: 24 VDC at 70 mA.

    Contact rating: 2.5 A at 30 VDC or 250 VAC. Match the relevant AC or DC rating to the load.

    View product reference (PDF)

    Mounting and safe handling

    1. Apply the orientation limit.

      Horizontal DIN-rail mounting permits -40 to +70 C; vertical mounting is limited to -40 to +60 C.

    2. De-energize before replacement.

      The July 2021 ATEX18 instruction permits removal or insertion with system power energized only where the area is known to be non-hazardous. Follow the applicable DeltaV SIS installation instructions.

    View product reference (PDF)

    Power and handling precautions

    • Use the approved field proof-test procedure for the relay arrangement. The component rating does not establish the integrity level of a complete safety function.

    • Do not disassemble the module. Verify the actual unit identification and the documented load before connection.

    Frequently Asked Questions

    What does KJ2231X1-EA1 do in a DeltaV SIS application?

    It switches higher-current or higher-voltage field loads and opens field-power contacts when de-energized.

    What contact load can KJ2231X1-EA1 switch?

    The relay contacts are rated at 2.5 A at 30 VDC or 250 VAC. The application must respect the relevant AC or DC rating.

    What input supply does KJ2231X1-EA1 require?

    It requires 24 VDC at 70 mA.

    Does the mounting orientation affect KJ2231X1-EA1 temperature limits?

    Yes. The operating temperature range is −40 to +70 °C when mounted horizontally and −40 to +60 °C when mounted vertically.

    Can KJ2231X1-EA1 be proof-tested in the field?

    Yes. The module contains three relays, each of which can be proof-tested in the field. Use the approved application procedure.

    Can KJ2231X1-EA1 be removed while system power is on?

    De-energize system power before removal or insertion unless the area is known to be non-hazardous. Confirm the site classification and follow the applicable installation procedure.

    How do the three relay coils in KJ2231X1-EA1 respond to a demand from the logic solver?

    All three coils are energized in normal operation. The logic solver cuts power to all three simultaneously on demand.

    At what temperatures can a spare KJ2231X1-EA1 be stored?

    The storage temperature range is −40 to +85 °C.

    Manufacturer Documentation

    KJ2231X1-EA1 Product Reference

    Product identification, actual photograph and compatibility notes, followed by selected original manufacturer reference pages.

    PDF · 5 pages · 124.0 KB · Compiled by EWOLO CONTROL. DeltaV SIS Conditioning Components November 2022; ATEX18 July 2021

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Emerson KJ2231X1-EA1

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.