ISO 9001:2015 certified industrial automation spare parts supplier

Emerson KJ3241X1-BK1 12P4710X032 DeltaV S-series Serial Interface Card

Emerson KJ3241X1-BK1 12P4710X032 is a DeltaV S-series serial interface card for bringing data from compatible PLCs, analyzers and other serial equipment into the control system. Standard Modbus RTU and ASCII drivers support communication through individually configurable ports.

Version check: Confirm KJ3241X1-BK1 12P4710X032, the S-series carrier, D4 terminal key, serial driver and port mode; check the slave device’s dual-port support if redundancy is required.

Download
  • Emerson KJ3241X1-BK1 12P4710X032 DeltaV S-series Serial Interface Card

    Emerson KJ3241X1-BK1 12P4710X032 is a DeltaV S-series serial interface card for exchanging data with compatible PLCs, analyzers and other serial equipment. It brings external device information into DeltaV control modules, operator displays and historical records, and can pass supervisory commands back to connected equipment. Two individually configurable ports support the standard Modbus RTU and ASCII protocols, with master or slave operation selected for each port. The card is intended for integrating serial devices into the controller's I/O subsystem while retaining their existing communication interface.

    Hardware specifications. KJ3241X1-BK1 12P4710X032 provides two serial ports for RS232 or RS422/485 half- or full-duplex operation. The interface supports 300–115200 baud and 32 data sets, with 16 per port. Its exact card rating is 12 VDC at 300 mA on the LocalBus.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Emerson
    Complete identification KJ3241X1-BK1 12P4710X032
    Platform DeltaV S-series

    Functional Configuration

    Serial ports 2 independently configured ports
    Port modes RS232; RS422/485 half duplex or full duplex
    Standard protocol Modbus RTU and Modbus ASCII
    Protocol roles Master or slave per port
    Baud rates 300 to 115200 baud, configured discrete rates
    Data sets 32 total, 16 per port
    Terminal key D4
    Isolation Each port isolated from system and other port; external grounding required

    Performance & Power

    LocalBus power 12 VDC at 300 mA

    Environment

    Operating temperature −40 to +70 °C
    Relative humidity 5–95%, non-condensing
    Protection IP20

    Compatibility & Selection Guide

    System compatibility. KJ3241X1-BK1 12P4710X032 is intended for the S-series controller and I/O-carrier architecture. Match the serial driver, master/slave role and electrical mode to the connected device. A redundant pair additionally requires a redundant terminal block and a slave device with two suitable serial ports.

    Wiring & Installation Reference

    Use the exact KJ3241X1-BK1 S-series instruction sheet and the applicable S-series hardware manual. Confirm the serial electrical mode and the connected device pin assignment before wiring; the reference is an instruction sheet, not a serial pinout drawing.

    Serial interface checks

    Port configuration: Match RS232 or RS422/485, duplex mode, protocol and master/slave role to the connected device.

    Termination and grounding: Use the D4 terminal key. Each serial port is isolated from the system and the other port, and requires external grounding.

    View product reference (PDF)

    Removal and installation

    1. Remove field power.

      Disconnect field power supplied at the terminal or through the carrier before removing or connecting the device.

    2. De-energize system power.

      The exact KJ3241X1-BK1 instruction sheet prohibits removing or inserting this unit with system power energized.

    View product reference (PDF)

    Power and handling precautions

    • Do not disassemble the card; it has no user-serviceable parts. Calibration is not required.

    • For redundant serial operation, confirm the matching redundant terminal block and the slave device’s two-port capability with its manufacturer.

    Frequently Asked Questions

    Which serial standards does KJ3241X1-BK1 12P4710X032 support?

    Its two ports support RS232, RS422/485 half duplex and RS422/485 full duplex. Configure each port to match the field device.

    Can KJ3241X1-BK1 12P4710X032 operate as a Modbus master or slave?

    Yes. Each port can be configured as a master or slave using the standard Modbus RTU or ASCII protocol.

    How many data sets can KJ3241X1-BK1 12P4710X032 exchange?

    The interface supports 32 data sets, allocated as 16 per serial port.

    What is needed for redundant communication with KJ3241X1-BK1 12P4710X032?

    Use a pair of serial cards and the matching redundant terminal block. The slave needs two serial ports and confirmed redundant-Modbus capability.

    Is KJ3241X1-BK1 12P4710X032 an M-series card?

    No. It is a DeltaV S-series serial interface card.

    Can KJ3241X1-BK1 12P4710X032 be removed with system power energized?

    No. De-energize system power and remove field power, whether supplied at the field terminal or through the carrier, before removing or inserting the card.

    What message timeout can I set on KJ3241X1-BK1 12P4710X032?

    The timeout is adjustable from 100 to 25,500 ms in steps of 100 ms.

    Can KJ3241X1-BK1 12P4710X032 start without sending output values to the connected device?

    Yes. Disable Send Outputs on Startup in DeltaV Explorer to suppress output transmission during interface initialization.

    Manufacturer Documentation

    KJ3241X1-BK1 12P4710X032 Product Reference

    Product identification, actual photograph and compatibility notes, followed by selected original manufacturer reference pages.

    PDF · 3 pages · 124.3 KB · Compiled by EWOLO CONTROL. ATEX55 July 2021

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Emerson KJ3241X1-BK1 12P4710X032

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.