Allen-Bradley 1756-DMD30 ControlLogix SD3000 Drive Interface Module

Allen-Bradley 1756-DMD30 is a ControlLogix drive interface module for SD3000 DC drive systems. It connects an individual PMI chassis through fiber-optic Drive Communication and supports SynchLink synchronization.

Version check: Match the SD3000 drive type, installed module firmware and project electronic keying. The 1756-DMF30 serves SF3000 field supplies and is not the same interface.

Download
  • Allen-Bradley 1756-DMD30 ControlLogix SD3000 Drive Interface Module

    Allen-Bradley 1756-DMD30 is the ControlLogix drive-interface module for Reliance Electric SD3000 six-pulse and twelve-pulse DC drive equipment. It links the control platform to an individual Power Module Interface chassis and performs velocity, position and outer torque control for that drive. The module uses an optical Drive Communication link for the PMI connection and provides SynchLink communication for synchronization and data transfer with other supported nodes. Local status indicators help identify drive-communication and synchronization conditions. These functions make 1756-DMD30 specific to an SD3000 drive application; the similarly named 1756-DMF30 serves SF3000 field-supply equipment instead.

    Hardware specifications. The 1756-DMD30 has separate fiber-optic links for Drive Communication at 10 Mbps and SynchLink at 5 Mbps. Backplane demand is 1.35 A at 5.1 V DC plus 3 mA at 24 V DC, with maximum power dissipation of 6.96 W. Its operating range is 0–60°C, and the two optical interfaces use different fiber types and wavelengths.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Allen-Bradley
    Catalog number 1756-DMD30

    Functional Configuration

    System ControlLogix
    Applicable drive equipment SD3000 six-pulse S6/S6R and twelve-pulse S12/S12R DC drives
    SynchLink data rate 5 Mbps
    Drive Communication data rate 10 Mbps
    SynchLink fiber 200/230 µm hard-clad silica; 650 nm
    Drive Communication fiber 62.5/125 µm glass; 820 nm
    Optical cable length 1–300 m; maximum 300 m with no more than one splice or one adapter
    Drive Communication nodes One PMI chassis

    Performance & Power

    Module supply From1756 chassis backplane
    Backplane current 1.35 A at 5.1 V DC; 3 mA at 24 V DC
    Maximum power dissipation 6.96 W

    Environment

    Operating temperature 0–60°C
    Relative humidity 5–95%, noncondensing

    Compatibility & Selection Guide

    System and software compatibility. The 1756-DMD30 works within a ControlLogix system using RSLogix 5000 and DriveExecutive for configuration. For a module running firmware 2.05, the compatible baselines are RSLogix 5000 8.02.00, RSLinx 2.30 and DriveExecutive 1.01 or later. Match the installed firmware and project electronic keying before replacement; the photographed unit firmware has not been confirmed.

    Wiring & Installation Reference

    Confirm the SD3000 equipment, available backplane power and the correct fiber for each optical interface before connection.

    Optical connections

    Connection Function Check
    Drive Comm Individual PMI chassis link Use the specified 62.5/125 µm glass fiber and SC/ST connection arrangement.
    Synch Comm SynchLink synchronization/data Use specified 200/230 µm hard-clad silica fiber; do not interchange the two optical cable types.
    Transmit/receive Transmit at rear; receive at front Follow the original connection diagram and retain dust caps when disconnected.

    View optical connection diagram (PDF)

    Installation checks

    1. Check the chassis budget

      Allow 1.35 A at 5.1 V DC and 3 mA at 24 V DC in addition to all other installed modules.

    2. Seat and lock the module

      Align the circuit board with the upper and lower guides, then slide the module in until both locking tabs click.

    3. Connect and verify the optical links

      Connect the specified Drive Comm and SynchLink fibers according to the transmit/receive diagram, then check the module and link indicators.

    View installation guide

    Power and handling precautions

    • Remove power or verify the area is nonhazardous before insertion, removal or disconnection. RIUP can still cause unintended machine motion or loss of process control.

    • Never look into module optical ports or cable connectors; intense light and invisible radiation can cause permanent eye damage.

    • Use ESD protection, avoid connector pins and circuit components, and keep optical dust covers installed when unused. Use a suitable tool-access enclosure for this open industrial equipment.

    Frequently Asked Questions

    Which drive equipment uses the 1756-DMD30?

    SD3000 six-pulse DC drives S6/S6R and twelve-pulse DC drives S12/S12R use this interface. SF3000 three-phase field supplies use 1756-DMF30 instead.

    Do the two optical interfaces on the 1756-DMD30 use the same fiber?

    No. SynchLink uses 200/230 µm hard-clad silica at 650 nm; Drive Communication uses 62.5/125 µm glass at 820 nm. Match the specified cable and connector arrangement to each port.

    What software is compatible with 1756-DMD30 firmware 2.05?

    For firmware 2.05, use RSLogix 5000 8.02.00 or later, RSLinx 2.30 or later, DriveExecutive 1.01 or later and, when applicable, RSNetWorx for ControlNet 3.00 or later. Confirm the actual firmware before applying these requirements.

    What should I check before replacing a 1756-DMD30?

    Match the SD3000 equipment and the project’s catalog number, major/minor firmware revision and electronic keying requirements. Do not treat 1756-DMF30 as the same interface or disable keying merely to force a connection.

    Can the 1756-DMD30 be removed with chassis power on?

    RIUP is supported, but insertion or removal can cause arcing and unintended machine motion. Remove power or ensure the area is nonhazardous, make the process safe and disconnect the fibers before removal.

    What does a solid red OK indicator mean on the 1756-DMD30?

    A solid red OK indicator indicates a nonrecoverable fault; remove the module from service. Do not confuse it with the brief red indication during power-up self-test.

    How long can the 1756-DMD30 optical links be?

    Each interface permits 1–300 m of the specified fiber. The 300 m maximum allows no more than one splice or one adapter; cable type and the relevant SynchLink topology limits still apply.

    How does 1756-DMD30 firmware 2.04 handle a momentary resolver read error?

    If one 4 ms scan returns an invalid resolver reading, firmware 2.04 calculates a substitute value. Invalid readings on two consecutive scans trigger a shutdown.

    Manufacturer Documentation

    1756-DMD30 Product Reference

    Product photograph, application notes and selected Rockwell Automation reference pages.

    PDF · 3 pages · 62.1 KB · Compiled by EWOLO CONTROL. 1756-IN577B-EN-P B

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Allen-Bradley 1756-DMD30

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.