ISO 9001:2015 certified industrial automation spare parts supplier

Allen-Bradley 1756-L82E ControlLogix 5580 Controller

ControlLogix 5580 controller with 5 MB user memory, an embedded Gigabit EtherNet/IP port and USB programming.

Version check: Match the full 1756-L82E catalog number, hardware series and project firmware; node limits and redundancy depend on the Logix Designer version. Standard Series C chassis permit 0…60 °C, while standard Series B chassis limit operation to 0…50 °C.

Download
  • Allen-Bradley 1756-L82E ControlLogix 5580 Controller

    Allen-Bradley 1756-L82E is a ControlLogix 5580 controller for executing standard automation logic and coordinating local I/O, networked equipment and supported motion applications. An embedded Gigabit Ethernet port provides an EtherNet/IP connection in supported operating configurations, while continuous, periodic and event tasks organize application execution around the process or machine requirements. The controller works within the modular ControlLogix architecture, so I/O and other communication functions can be selected for the system. The operating configuration remains important: redundancy mode disables the embedded Ethernet port and integrated motion, so those functions must not be assumed to operate together on a redundant 1756-L82E system.

    Hardware specifications. The single-slot controller provides 5 MB of user memory, an embedded Ethernet port supporting up to 1 Gbps, and a USB programming port. It uses Secure Digital nonvolatile storage and an embedded, non-removable energy storage module.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Allen-Bradley
    Complete part number 1756-L82E
    Controller family ControlLogix 5580
    Module width 1 chassis slot
    Approximate weight 0.394 kg

    Functional Configuration

    Built-in Ethernet 1 port; 10/100/1000 Mbps capability
    Local programming interface USB 2.0 full speed, 12 Mbps; temporary use
    Nonvolatile storage Secure Digital; current specified standard card 1784-SD4, 4 GB
    Energy storage module Embedded, non-removable

    Performance & Power

    User memory 5 MB
    EtherNet/IP nodes 175 with Logix Designer v30 or later; 80 with v29.00.02
    Controller tasks 32
    Programs per task 1000
    Backplane current at 5.1V DC 1.20 A
    Backplane current at 1.2V DC 5.0 mA
    Power dissipation 6.2 W

    Environment

    Operating temperature 0…60 °C with standard Series C chassis; 0…50 °C with standard Series B chassis

    Compatibility & Selection Guide

    System and software compatibility. Studio 5000 Logix Designer version 30 or later supports 175 EtherNet/IP nodes. Redundancy requires version 33.00.02 or later and a compatible system configuration; enabling it disables the embedded Ethernet port and integrated motion.

    Wiring & Installation Reference

    Use the chassis backplane for power and the RJ45 port for EtherNet/IP. USB is temporary local programming only.

    Interfaces and connections

    Interface Connection Check
    RJ45 Ethernet Connect the required EtherNet/IP network cable. Match the actual hardware series and system configuration.
    USB Temporary workstation connection. Match the actual hardware series and system configuration.
    Backplane Compatible ControlLogix chassis connection. Match the actual hardware series and system configuration.

    Verify the chassis series and operating-temperature limit before installation.

    View connection requirements (PDF)

    Mounting and connection

    1. Seat the controller

      Align the board with the chassis guides and slide the controller in until it locks and sits flush.

    2. Complete connections

      Install the key and supported SD card as required; connect the RJ45 network cable and check the display after applying power.

    View installation guide

    Power and handling precautions

    • Use ESD precautions and an appropriate enclosure.

    • Remove power or confirm a nonhazardous area before insertion, removal or connection changes.

    • Do not use USB in hazardous locations; limit its cable to 3 m without hubs.

    Frequently Asked Questions

    How much user memory does 1756-L82E provide?

    It provides 5 MB of user memory.

    How many EtherNet/IP nodes does 1756-L82E support?

    It supports 175 nodes with Logix Designer version 30 or later. Version 29.00.02 has an 80-node limit.

    Can 1756-L82E operate at 60 °C in any ControlLogix chassis?

    No. The 0…60 °C range requires a standard Series C chassis. A standard Series B chassis limits the controller to 0…50 °C.

    Does 1756-L82E have a removable energy storage module?

    No. Its energy storage module is embedded and non-removable.

    What is the difference between 1756-L82E and 1756-L82EK?

    1756-L82EK is the conformal-coated variant. The standard 1756-L82E is not conformal coated.

    Does 1756-L82E support redundancy?

    Yes, with Logix Designer version 33.00.02 or later and a supported redundancy configuration. When redundancy is enabled, the embedded Ethernet port is disabled and integrated motion is unavailable.

    Can 1756-L82E use USB for a permanent plant connection?

    No. USB is limited to temporary programming, configuration, firmware updates and online edits.

    Which nonvolatile storage is specified for 1756-L82E?

    It supports a 4 GB 1784-SD4 Secure Digital card for nonvolatile storage. Confirm the card included with the supplied controller separately.

    Manufacturer Documentation

    1756-L82E Product Reference

    Product identification, actual photograph and compatibility notes, followed by selected original manufacturer reference pages.

    PDF · 3 pages · 76.5 KB · Compiled by EWOLO CONTROL. 1756-TD001 W / October 2025

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Allen-Bradley 1756-L82E

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.