ISO 9001:2015 certified industrial automation spare parts supplier

Vibro Meter GSI127 244-127-000-017 A1-B02 Galvanic Separation Unit

GSI127 244-127-000-017 A1-B02 is the standard GSI127 current-to-voltage isolation unit for an IPC or compatible VE210 measurement chain.

Version check: Match A1 standard approval and B02 current conversion; IQS current chains require a different transfer option.

Download
  • Vibro Meter GSI127 244-127-000-017 A1-B02 Galvanic Separation Unit

    Vibro Meter GSI127 244-127-000-017 A1-B02 provides power, signal conversion and electrical isolation in machinery monitoring measurement chains. This B02 configuration is intended for current-output IPC signal conditioners or a compatible VE210 velocity sensor. It converts the modulated sensor current into a voltage signal for the monitoring input while separating sensor-side ground from monitoring electronics. The A1 code identifies the standard version, making the full A1-B02 configuration important when replacing another visually similar GSI127.

    Hardware specifications. The unit accepts an 18–30 V DC supply. B02 conversion gain is 1 V/mA, with a 12 mA input corresponding to a nominal 7 V DC output. The sensor supply is nominally 20 V DC. Its signal bandwidth is DC–20 kHz within ±0.5 dB, and sensor-to-monitor isolation is rated at 4 kV RMS.

    Technical Specifications

    Parameter Specification

    Product Identity

    Complete configuration GSI127 244-127-000-017 A1-B02

    Functional Configuration

    Function Galvanic isolation, sensor power and current-to-voltage conversion
    B02 offset 12 mA input → 7 V DC ±200 mV
    Sensor/monitor isolation 4 kV RMS
    Version A1 standard; B02 IPC/VE210 current interface

    Performance & Power

    Supply voltage 18–30 V DC
    Transfer gain B02: 1 V/mA ±1%
    Sensor supply 20 V DC ±1 V
    Input current range 0–20 mA
    Signal bandwidth DC–20 kHz, ±0.5 dB

    Environment

    Operating temperature 0 to +70 °C

    Compatibility & Selection Guide

    System compatibility. Use B02 with the applicable current-output IPC704/IPC707 chain or VE210 configuration. Other GSI127 options have different transfer functions: current-output IQS conditioners use B03, while voltage-output chains use other options. The A1 standard unit must not be represented as the A2 Ex version. Match the upstream conditioner output and downstream voltage range together.

    Wiring & Installation Reference

    Connect the sensor, power and monitor sides according to the GSI127 terminal markings and isolation boundaries.

    Signal and power connections

    Keep the sensor-side and monitor-side circuits on their designated terminal groups.

    Use 18–30 V DC and a monitor input compatible with B02 voltage scaling.

    View terminal layout (PDF)

    DIN-rail mounting

    1. Identify the version

      Verify A1-B02 on the unit before connecting a measurement chain.

    2. Fit the rail holder

      Mount on the specified TH35 DIN rail and retain the unit securely.

    3. Connect terminal blocks

      Use the removable terminal blocks as shown in the front and mechanical drawings.

    View mounting diagram

    Power and handling precautions

    • A1 is a standard version; do not infer an A2 Ex approval.

    • Match B02 signal scaling before applying power to the completed chain.

    Frequently Asked Questions

    What is the function of GSI127 244-127-000-017 A1-B02?

    It powers the sensor-side chain, converts its current signal to a voltage signal and provides galvanic isolation from the monitoring side.

    Which signal conditioners can be used with GSI127 244-127-000-017 A1-B02?

    The B02 option is intended for a current-output IPC704 or IPC707 chain, or an applicable current-output VE210 velocity sensor. Confirm the actual output option and scaling of the connected device.

    What is the transfer function of GSI127 244-127-000-017 A1-B02?

    The B02 gain is 1 V/mA. A 12 mA nominal input corresponds to 7 V DC; an IPC707 diagnostic nominal current of 13 mA corresponds to 8 V DC.

    Can GSI127 244-127-000-017 A1-B02 replace a B03 unit for an IQS current signal?

    No automatic substitution is valid. B03 uses a different conversion gain and offset for IQS current-output chains. Match the complete transfer-function code.

    Does GSI127 244-127-000-017 A1-B02 provide Ex intrinsic-safety protection?

    A1 identifies the standard version. Do not use an A1 label as evidence of the A2 Ex approval or of an intrinsically safe complete measurement chain.

    What power supply does GSI127 244-127-000-017 A1-B02 require?

    Use 18–30 V DC. Maximum supply current is 80 mA with no load and 120 mA at a 20 mA sensor load.

    What isolation does GSI127 244-127-000-017 A1-B02 provide?

    The sensor-to-monitor isolation rating is 4 kV RMS. The power-to-output isolation rating is 50 V RMS; these are different isolation boundaries.

    What operating temperature applies to GSI127 244-127-000-017 A1-B02?

    The operating range is 0 to +70 °C, with relative humidity up to 90% without condensation. Storage limits must not be substituted for operating limits.

    What should be checked before ordering GSI127 244-127-000-017 A1-B02 as a replacement?

    Match A1 versus A2, the B02 transfer function, the upstream signal conditioner, monitor input scaling and supply. Similar GSI127 housings can contain different signal-conversion options.

    Manufacturer Documentation

    GSI127 244-127-000-017 A1-B02 Product Reference

    Actual product photograph, application and replacement notes, with selected manufacturer pages covering specifications and connection or mechanical details.

    PDF · 7 pages · 108.9 KB · Compiled by EWOLO CONTROL. DS 262-870 Version 11 (2022-05-12).

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Vibro Meter GSI127 244-127-000-017 A1-B02

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.