Vibro Meter IQS450 204-450-000-002 A2-B24-H10-I1 Proximity Signal Conditioner

IQS450 204-450-000-002 A2-B24-H10-I1 is the 4 mm current-output IQS450 configuration for a 10 m TQ402/TQ412 proximity measurement chain.

Version check: Confirm B24 current output, H10 total cable length, I1 mounting and target-material calibration; B23 voltage units are not interchangeable by appearance.

Download
  • Vibro Meter IQS450 204-450-000-002 A2-B24-H10-I1 Proximity Signal Conditioner

    Vibro Meter IQS450 204-450-000-002 A2-B24-H10-I1 conditions the high-frequency signal from a TQ402 or TQ412 proximity probe for non-contact shaft vibration and position monitoring. The B24 option is a current-output configuration with a 4 mm measurement range, while H10 identifies a 10 m total measuring-system length. Its modulator/demodulator excites the probe and produces an output proportional to the target gap. This configured unit is intended for a matched probe-and-cable chain, rather than as a universal proximity input module.

    Hardware specifications. B24 sensitivity is 1.25 µA/µm. The typical working gap is 0.3–4.3 mm, corresponding to −15.5 to −20.5 mA. The conditioner uses a −20 to −32 V DC supply, subject to its power-temperature derating curve. The body is rated IP40, and the I1 option includes the MA130 DIN-rail adapter.

    Technical Specifications

    Parameter Specification

    Product Identity

    Complete configuration IQS450 204-450-000-002 A2-B24-H10-I1

    Functional Configuration

    Measurement principle Eddy-current proximity signal conditioning
    Output option B24: current output, 4 mm measurement range
    Nominal sensitivity 1.25 µA/µm
    Typical working gap 0.3–4.3 mm
    Corresponding output −15.5 to −20.5 mA
    Total system length H10: 10 m; probe integral cable plus extension
    Mounting option I1: MA130 DIN-rail adapter

    Performance & Power

    Supply voltage −20 to −32 V DC, subject to thermal derating

    Environment

    Operating temperature −35 to +85 °C; apply supply-voltage derating
    Body protection IP40
    Environment option A2; assess the complete intrinsically safe chain

    Compatibility & Selection Guide

    System compatibility. Use the matching TQ402/TQ412 probe, EA402 extension arrangement and H10 total-system length. A B23 voltage-output unit is not an electrical substitute for this B24 current-output configuration. For a galvanically isolated current chain, select the appropriate IQS transfer function, such as GSI127 B03, and verify A2 intrinsic-safety conditions across the complete system.

    Wiring & Installation Reference

    Use the IQS450 terminal/mounting drawing and the adjacent power-temperature derating curve.

    Signal and supply

    Connect the matched probe chain to the self-locking miniature coaxial input.

    Use the marked output/power terminals and observe the negative supply polarity and B24 current interface.

    View terminal diagram (PDF)

    Mounting and temperature

    1. Check the adapter

      Verify the I1 MA130 adapter and the specified TH35 rail.

    2. Connect the matched chain

      Use the intended TQ402/TQ412 and EA402 lengths for H10.

    3. Check derating

      Apply the supply-voltage versus ambient-temperature curve before energising.

    View mounting diagram

    Power and handling precautions

    • Read the power-temperature curve on the preceding manufacturer page; the voltage and temperature maxima are not independently interchangeable.

    • A2 suitability requires the complete Ex i chain and applicable certificate conditions.

    Frequently Asked Questions

    What does IQS450 204-450-000-002 A2-B24-H10-I1 do?

    It excites a matched proximity probe and converts the returning signal into a current output proportional to the metal target gap, for shaft position and relative vibration measurement.

    Is IQS450 204-450-000-002 A2-B24-H10-I1 a voltage-output or current-output conditioner?

    B24 is the current-output option. It provides 1.25 µA/µm sensitivity over a nominal 4 mm measurement range; B23 is a different voltage-output option.

    What measuring gap is supported by IQS450 204-450-000-002 A2-B24-H10-I1?

    The typical working gap is 0.3–4.3 mm, corresponding to a −15.5 to −20.5 mA output. Target material and the matched system calibration must also be correct.

    Does H10 on IQS450 204-450-000-002 A2-B24-H10-I1 mean a 10 m extension cable?

    No. H10 specifies the total measuring-system length, including the probe integral cable and the extension cable.

    Can IQS450 204-450-000-002 A2-B24-H10-I1 directly replace a B23-configured IQS450?

    No. B23 provides a voltage signal while B24 provides a current signal. Verify the monitoring input, separation unit and complete configured chain before substitution.

    What supply polarity is required by IQS450 204-450-000-002 A2-B24-H10-I1?

    The conditioner requires a negative DC supply in the −20 to −32 V range. Apply the power-temperature derating curve rather than assuming every voltage is valid at the maximum temperature.

    Which DIN-rail option is included with IQS450 204-450-000-002 A2-B24-H10-I1?

    I1 identifies the MA130 mounting adapter for the specified TH35 DIN-rail types. I0 is the version without that adapter.

    Can IQS450 204-450-000-002 A2-B24-H10-I1 use the GSI127 B02 transfer option?

    B02 is intended for IPC or applicable VE210 current chains. A current-output IQS chain uses the appropriate IQS conversion option, such as GSI127 B03, after complete chain verification.

    What must be matched before ordering IQS450 204-450-000-002 A2-B24-H10-I1?

    Match the complete 002 hardware part number, A2 environment option, B24 current output, H10 total length, I1 mounting arrangement, probe type and target-material calibration.

    Manufacturer Documentation

    IQS450 204-450-000-002 A2-B24-H10-I1 Product Reference

    Actual product photograph, application and replacement notes, with selected manufacturer pages covering specifications and connection or mechanical details.

    PDF · 7 pages · 110.4 KB · Compiled by EWOLO CONTROL. DS 265-062 Version 7 (2015-03-05).

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Vibro Meter IQS450 204-450-000-002 A2-B24-H10-I1

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.