ISO 9001:2015 certified industrial automation spare parts supplier

Allen-Bradley 1756-IA16I ControlLogix Isolated AC Input Module

Allen-Bradley 1756-IA16I is a ControlLogix 16-point, individually isolated 120V AC input module. It monitors separate AC field signals and transfers their states to the controller.

Version check: Confirm 1756-IA16I, individual-input isolation and the 36-position RTB. It uses different terminal grouping from 1756-IA16.

Download
  • Allen-Bradley 1756-IA16I ControlLogix Isolated AC Input Module

    Allen-Bradley 1756-IA16I is a 16-channel, individually isolated AC digital input module for bringing nominal 120 V AC field states into a ControlLogix controller. Each input has its own isolation from the other inputs and the backplane, supporting applications where the field circuits must remain electrically separate. The module converts the incoming on/off conditions into controller input data and provides selectable input filtering, configurable change-of-state reporting and input time stamps. These features help the application qualify and identify field-state changes. The individual isolation is a defining feature of 1756-IA16I and must not be assumed for other sixteen-channel AC input models.

    Hardware specifications. The 1756-IA16I provides 16 inputs with a nominal 120V AC, 50/60Hz rating. Its operating input range is 79–132V AC at 47–63Hz. Input filtering is selectable, and the module supports change-of-state reporting and input timestamps. It occupies one chassis slot and uses a 1756-TBCH or 1756-TBS6H 36-position removable terminal block.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Allen-Bradley
    Catalog number 1756-IA16I
    Chassis width 1 slot

    Functional Configuration

    Input points 16, individually isolated
    Nominal input voltage 120V AC, 50/60Hz
    Operating input range 79–132V AC at 47–63Hz
    Isolation 125V continuous, input-to-backplane and input-to-input
    Removable terminal block 1756-TBCH or 1756-TBS6H; 36 positions

    Performance & Power

    Off-to-on delay 10ms maximum hardware delay plus selectable 1ms or 2ms filter
    On-to-off delay 8ms maximum hardware delay plus selectable 9ms or 18ms filter
    Maximum off-state voltage 20V AC
    Maximum off-state current 2.5mA
    On-state current 5mA minimum at 79V AC; 15mA maximum at 132V AC
    Backplane current 125mA at 5.1V DC; 3mA at 24V DC

    Environment

    Operating temperature 0–60°C

    Compatibility & Selection Guide

    System compatibility. The 1756-IA16I is part of the ControlLogix AC input family. For replacement, match the individual-input isolation, AC signal range, filter configuration and terminal arrangement to the existing application. A 1756-IA16 grouped-input module has a different terminal block and grouping, so the similar catalog number does not establish interchangeability.

    Wiring & Installation Reference

    Keep the individual AC input and return pairs separate when the application requires input-to-input isolation.

    Signal and terminal selection

    Connection Use Check
    IN-0 to IN-15 AC input signal terminals Match each field circuit to its designated input.
    L2-0 to L2-15 Corresponding AC returns Preserve individual return wiring for isolated circuits.
    1756-JMPR Optional L2 commoning Use only for an intentional nonisolated wiring arrangement.

    View terminal diagram (PDF)

    Installation checks

    1. Prepare and isolate

      Install the chassis and power supply, then establish a safe power and equipment state before inserting the module or wiring the RTB.

    2. Match the RTB

      Use the 36-position 1756-TBCH or 1756-TBS6H. Set mechanical keying to match the module and follow the individual-input diagram.

    3. Secure and verify

      Provide strain relief, assemble the housing, close the cover and fully seat and lock the RTB. Verify each field voltage and input filter in the project.

    View installation guide

    Power and handling precautions

    • Remove field power before RTB handling; remove power or confirm a nonhazardous area before module insertion, removal or disconnection.

    • Follow electrostatic-discharge precautions and prevent unintended machine motion while I/O is disconnected.

    Frequently Asked Questions

    Are the 16 inputs of the 1756-IA16I individually isolated?

    Yes. Each of the 16 inputs is isolated from the other inputs, with a 125V continuous isolation rating to the backplane and between inputs.

    Can the 1756-IA16I accept 24V DC input signals?

    It is a 120V AC input module with a 79–132V AC operating input range. Select an appropriate DC input module for a 24V DC field signal.

    Is the 1756-IA16I interchangeable with 1756-IA16?

    Do not assume a direct interchange. The 1756-IA16I has individually isolated inputs and a 36-position RTB; 1756-IA16 uses grouped inputs and a different terminal arrangement. Check the wiring and project configuration before selecting a replacement.

    Which terminal block is required for the 1756-IA16I?

    Use a 1756-TBCH or 1756-TBS6H 36-position removable terminal block. Confirm the correct mechanical keying and whether the terminal block is included.

    How fast does the 1756-IA16I respond to an input change?

    Off-to-on response includes up to 10ms of hardware delay plus the selected 1ms or 2ms filter. On-to-off response includes up to 8ms of hardware delay plus the selected 9ms or 18ms filter.

    Can the 1756-IA16I inputs share a common AC return?

    The inputs can be wired with individual returns. A 1756-JMPR jumper can connect L2 returns for a nonisolated input arrangement; use that configuration only when shared returns are appropriate for the circuit.

    What should be checked before removing the 1756-IA16I terminal block?

    Remove field-side power and keep controlled equipment in a safe state. In a hazardous location, remove power or confirm that the area is nonhazardous before disconnecting; an energized connection can produce an arc.

    What housing is available if 1756-IA16I field wiring needs more room?

    The 1756-TBE extended-depth terminal-block housing provides more room for routing field conductors. The wire-size limits of the selected terminal block still apply.

    Manufacturer Documentation

    1756-IA16I Product Reference

    Product photograph, application notes and selected Rockwell Automation pages covering the current module.

    PDF · 3 pages · 78.3 KB · Compiled by EWOLO CONTROL. 1756-TD002U-EN-E U

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Allen-Bradley 1756-IA16I

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message