ISO 9001:2015 certified industrial automation spare parts supplier

GE IS220PPRFH1A PROFIBUS Master Gateway I/O Pack

GE IS220PPRFH1A is a Mark VIe PROFIBUS DPV0 Class 1 master gateway. It maps I/O from PROFIBUS slave devices into Mark VIe controllers over the I/O Ethernet network, providing the interface between the two networks.

Version check: Confirm PROFIBUS DPV0 slave requirements, the SPIDG1A identification board and the intended single-pack or active/standby arrangement.

Download
  • GE IS220PPRFH1A PROFIBUS Master Gateway I/O Pack

    GE IS220PPRFH1A is the Mark VIe PROFIBUS Master Gateway I/O pack, linking PROFIBUS slave-device data to the controller's I/O Ethernet network. It operates as a PROFIBUS DPV0 Class 1 master, exchanging the configured input and output data so that external PROFIBUS equipment can participate in the Mark VIe control application. The gateway supports a single Ethernet connection, dual Ethernet connections or a paired hot-backup arrangement. In the hot-backup configuration, one pack is the active master while the second remains ready to take over communication after an active-master failure.

    Hardware specifications. The IS220PPRFH1A provides a DE-9 RS-485 PROFIBUS connection and two RJ45 I/O Ethernet connectors. GE specifies transmission rates from 9.6 kbaud to 12 Mbaud, up to 125 slaves, and up to 244 input bytes and 244 output bytes per slave.

    Technical Specifications

    Parameter Specification

    Product Identity

    Control system GE Mark VIe

    Functional Configuration

    Product function PROFIBUS master gateway
    PROFIBUS role DPV0 Class 1 master
    Per-slave data Up to 244 input bytes and 244 output bytes
    PROFIBUS connector DE-9 RS-485
    I/O Ethernet 2 RJ45 connectors
    ID / mounting board SPIDG1A
    Engineering tool ToolboxST

    Performance & Power

    Data rate 9.6 kbaud to 12 Mbaud
    Slave capacity Up to 125 slaves

    Environment

    Internal temperature monitoring The pack monitors its internal temperature and reports it through the fixed I/O point IOPackTmpr.

    Compatibility & Selection Guide

    System and software compatibility. Configuration is performed in ToolboxST for the actual Mark VIe application. Supported arrangements include one pack with a single or dual Ethernet connection, or two packs in an active/standby hot-backup arrangement. The PPRF interface is DPV0; the communication component inside it does not establish DPV1 support for the complete pack.

    Wiring & Installation Reference

    Use the GE PPRF instructions for the specific PROFIBUS segment and Mark VIe configuration.

    Network and power connections

    Connection Purpose Requirement
    DE-9 PROFIBUS RS-485 Correct polarity and segment termination
    ENET1 / ENET2 Mark VIe I/O Ethernet Configured network arrangement
    Three-pin supply Pack power Nominal 28 V DC

    Terminate the PROFIBUS segment at both ends and retain the verified slave addressing.

    View network diagram (PDF)

    Mounting and configuration

    1. Check the ID board

      Verify the SPIDG1A identification and mounting board.

    2. Fit the pack

      Align the pack and its mounting supports without forcing the connector.

    3. Configure and verify

      Use ToolboxST to confirm slave definitions, I/O mapping and the single-pack or hot-backup role.

    View installation instructions (PDF)

    Power and handling precautions

    • Follow GE isolation and handling instructions before changing connections.

    • Do not substitute a dual/TMR scheme for the documented PPRF hot-backup configuration.

    Frequently Asked Questions

    Does IS220PPRFH1A support PROFIBUS DPV1?

    The complete PPRF pack is documented as a DPV0 Class 1 master. Do not infer DPV1 support from the capabilities of its internal communication component.

    How many slaves can IS220PPRFH1A connect?

    GE specifies up to 125 PROFIBUS slaves with up to 244 input bytes and 244 output bytes per slave. Actual system configuration and cycle-time requirements must also be checked.

    What is the redundancy arrangement for IS220PPRFH1A?

    GE documents a single pack with one or two Ethernet connections and an active/standby hot-backup pair. Hot backup is not the same as the standard dual or TMR control mode of other I/O packs.

    Which identification board is used with IS220PPRFH1A?

    The documented identification and mounting board is SPIDG1A. Verify its installed code before ordering a replacement assembly.

    How is IS220PPRFH1A configured?

    Use ToolboxST with the correct slave definitions and the application configuration. Retain the existing device addresses and I/O mapping during a planned replacement.

    What should be checked if IS220PPRFH1A cannot communicate with slaves?

    Verify the configured bus rate and addresses, device definitions, wiring polarity and termination at both ends of the PROFIBUS segment; use the pack communication diagnostics to isolate the fault.

    Which updated model does GE list for IS220PPRFH1A?

    GE lists IS220PPRFH1B as the updated catalog option. Review the installed ControlST version and the applicable BPPC I/O upgrade procedure with GE before changing the pack; the replacement requires a system compatibility check.

    How does IS220PPRFH1A identify which PROFIBUS slave has reported a diagnostic?

    A general diagnostic flag indicates that at least one station has reported a fault. Separate station flags identify the affected slaves. ToolboxST Advanced Diagnostics displays their diagnostic data.

    Manufacturer Documentation

    IS220PPRFH1A Product Reference

    Product photograph, identification and compatibility notes, with selected manufacturer specifications and connection information.

    PDF · 6 pages · 56.9 KB · Compiled by EWOLO CONTROL. GEH-6721G G; revised 30 April 2008

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    GE IS220PPRFH1A

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.