GE IC695ALG608-HC 8-Channel Analog Input Module

GE IC695ALG608-HC is the PACSystems RX3i non-isolated analog input module for voltage and current signals. It provides eight single-ended inputs or four differential inputs, allowing the channel arrangement to match the installed measurement circuits.

Version check: Retain the -HC revision and verify single-ended/differential configuration, terminal block and PNS001/CEP001 compatibility; ALG608 is not a HART module.

Download
  • GE IC695ALG608-HC 8-Channel Analog Input Module

    GE IC695ALG608-HC is a PACSystems RX3i analog input module for acquiring voltage and current measurements from field instruments. Its non-isolated input arrangement can be configured as eight single-ended channels or four differential channels to suit the required measurement circuits. Per-channel scaling and offsets convert the acquired values for use in the control application, while configurable limit alarms, rate-of-change alarms and open-circuit detection support signal supervision. The complete -HC identity identifies the documented hardware/firmware release; HART communication is a feature of other models in the same manual, not of the ALG608.

    Hardware specifications. The IC695ALG608-HC supports 0-20 mA, 4-20 mA and ±20 mA current ranges, plus ±10 V, 0-10 V, ±5 V, 0-5 V and 1-5 V voltage ranges. It uses a 24-bit A/D converter and provides 32-bit floating-point or 16-bit integer data in a 32-bit field. This ALG608 version does not provide HART communication.

    Technical Specifications

    Parameter Specification

    Product Identity

    Platform PACSystems RX3i
    Complete revision IC695ALG608-HC

    Functional Configuration

    Product function Non-isolated analog input module
    Input channels 8 single-ended or 4 differential
    A/D converter 24 bit
    Data format 32-bit floating point or 16-bit integer in a 32-bit field
    HART Not supported by ALG608
    Backplane RX3i Universal Backplane
    Terminal block IC694TBB032 / TBB132 / TBS032 / TBS132; selected separately

    Performance & Power

    Current ranges 0-20 mA; 4-20 mA; ±20 mA
    Voltage ranges ±10 V; 0-10 V; ±5 V; 0-5 V; 1-5 V

    Environment

    Hazardous-location restrictions Units marked for Class I, Division 2, Groups A–D are suitable for those locations or nonhazardous areas. In hazardous areas, isolate power before replacement or wiring.

    Compatibility & Selection Guide

    System and software compatibility. IC695ALG608-HC uses an RX3i Universal Backplane and a separately selected high-density terminal block. GFK-2372K lists programmer version 5.0 SP3 or newer and RX3i CPU firmware 3.00 or newer for ALG608. The -HC release addresses the earlier device-identification mismatch with IC695PNS001 and IC695CEP001; verify the complete revision when replacing an older unit.

    Wiring & Installation Reference

    Choose the documented single-ended or differential wiring for the configured channel mode.

    Analog field connections

    Single-ended voltage inputs connect between Channel IN+ and Common. Current inputs use IN+ and the corresponding Current Return with the documented return-to-common jumper.

    Differential channels use paired IN+ / IN- terminals. For current measurements, fit the specified short jumper between IN- and the corresponding Current Return.

    Use the correct door-card wiring diagram for the selected mode.

    View single-ended wiring (PDF)

    Backplane and terminal block

    1. Confirm the base

      Use an RX3i Universal Backplane and an approved high-density terminal block.

    2. Match the channel mode

      Verify signal type, configured range and single-ended/differential arrangement before landing wires.

    3. Verify the configuration

      Check the full -HC code, CPU/programmer compatibility and controller diagnostics after configuration.

    View differential wiring (PDF)

    Power and handling precautions

    • Follow the manufacturer installation and hazardous-location conditions before insertion, removal or wiring.

    • Channels are non-isolated from one another; do not infer individual channel isolation from the backplane isolation rating.

    Frequently Asked Questions

    Does IC695ALG608-HC support HART transmitters digitally?

    No. ALG608 is the non-HART member. Do not transfer the HART capabilities of ALG626 or ALG628 to this model.

    Why does the -HC suffix matter on IC695ALG608-HC?

    GFK-2372K identifies -HC as the release correcting the device-ID mismatch affecting earlier ALG608-FB through -GB modules in PNS001 or CEP001 racks. Preserve the full suffix when matching a replacement.

    How many differential inputs does IC695ALG608-HC provide?

    Four differential inputs, or eight single-ended inputs. Differential mode uses adjacent input terminals as a channel pair.

    Can IC695ALG608-HC be used on any RX3i backplane?

    It requires an RX3i Universal Backplane. Confirm the base and high-density terminal block before ordering.

    Which software is documented for IC695ALG608-HC?

    The ALG608 compatibility table specifies programmer version 5.0 SP3 or newer and RX3i CPU firmware 3.00 or newer. Additional controller or network configuration requirements still apply to the installed system.

    Can an earlier ALG608 be field-upgraded to the IC695ALG608-HC release?

    GFK-2372K states that earlier versions cannot be upgraded in the field to this firmware revision. Select the correct hardware/revision rather than assuming a firmware-only conversion.

    What does a red TB indicator on IC695ALG608-HC mean?

    The terminal block is missing or not fully seated. The TB indicator turns green when the module detects an installed block.

    When is the extended terminal block preferable for IC695ALG608-HC?

    The extended box and spring versions provide extra shroud depth for shielded field wiring. Cable shields terminate at the ground bar below the backplane.

    Manufacturer Documentation

    IC695ALG608-HC Product Reference

    Product photograph, identification and compatibility notes, with selected manufacturer specifications and connection information.

    PDF · 8 pages · 125.3 KB · Compiled by EWOLO CONTROL. GFK-2372K K; December 2014

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    GE IC695ALG608-HC

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.