133819-01
3500/60 non-isolated RTD/TC I/O, internal terminations
No online payment is requested. Final price and terms are supplied in a written quotation.
ISO 9001:2015 certified industrial automation spare parts supplier





Bently Nevada 136711-01 is the non-isolated RTD/TC I/O module with internal barriers and internal terminations for the 3500/60 temperature monitor. The barrier-specific sensor and earthing requirements apply.
Version check: Confirm 136711-01 for the 3500/60 non-isolated RTD/TC internal-barrier arrangement; the 3500/61 spare has a different part number.
Lifecycle status: Unknown
Product image is representative; revision or series may vary.
Contact us to request a specific version.
12-month return-to-base cover.
Eligibility per quote.
DHL, FedEx or UPS.
Or use an agreed carrier account.
Bank transfer before dispatch,
unless agreed in writing.
Bently Nevada 136711-01 is the non-isolated RTD/TC I/O module with internal barriers and internal terminations for the 3500/60 temperature-monitoring assembly. It provides the rear sensor interface and barrier function for the approved temperature-transducer arrangement. The front 3500/60 monitor conditions the temperature inputs and compares them with programmed alarm setpoints, supporting six-channel machinery temperature monitoring. This exact spare belongs to the 3500/60 arrangement without recorder outputs; it is separate from the 136711-02 version for the 3500/61 and must be matched to the supported intrinsic-safety transducer configuration.
Hardware specifications. The internal-barrier I/O measures 241.3 x 24.4 x 163.1 mm (H x W x D), with a published operating range of 0 to +65 degrees C for the barrier configuration. The barrier compatibility list includes the specified three-wire RTD and thermocouple systems and excludes four-wire RTDs and thermocouples. Do not apply the broader non-barrier sensor list to 136711-01.
| Parameter | Specification |
|---|---|
Product Identity |
|
| Part number | 136711-01 |
| Component | RTD/TC I/O with internal barriers and internal terminations |
| Isolation designation | Non-isolated |
| I/O dimensions (H x W x D) | 241.3 x 24.4 x 163.1 mm |
| Rack space | One full-height rear slot |
Functional Configuration |
|
| Applicable monitor | 3500/60 temperature monitor |
| Four-wire inputs | Four-wire RTDs and thermocouples excluded by barrier-system document |
| IS earthing | Required in each rack with internal barriers |
Performance & Power |
|
| Recorder outputs | 3500/60 arrangement is without recorder outputs |
Environment |
|
| Supported barrier temperature inputs | Specified three-wire RTD and thermocouple systems |
| Operating temperature | 0 to +65 degrees C with internal-barrier I/O |
| Storage temperature | -40 to +85 degrees C |
System compatibility. The associated 3500/60 monitor uses 3500 Rack Configuration Software for RTD or thermocouple temperature measurements. The non-isolated RTD/TC design permits the supported input types according to the monitor and barrier configuration. Internal-barrier applications also have documented software/firmware, IS earthing and system restrictions; the barrier option is not the same as galvanically isolated TC I/O.
Use the current manufacturer reference to check the exact module, its documented system position and applicable termination arrangement.
Check the permitted three-wire RTD or thermocouple configuration in the internal-barrier compatibility table.
Keep 136711-01 matched to the 3500/60-specific arrangement rather than the /61 or TC-isolated spare.
136711-01 is the non-isolated internal-barrier RTD/TC version. Use the manufacturer barrier-compatible three-wire temperature inputs; four-wire RTDs and thermocouples are excluded.
Confirm the dedicated 3500/04-01 IS Earthing Module position.
Apply the manufacturer routing and minimum separation requirements, with space for the deeper barrier I/O.
Provide the required IS earthing arrangement and maintain the safe/hazardous wiring separation. The barrier I/O is deeper than the standard I/O and has a 0 to +65 degrees C operating range.
Maintain the required IS earth and separation of safe and hazardous circuits. Internal barriers do not make 136711-01 a TC-isolated I/O, and four-wire RTDs/thermocouples are outside the documented barrier compatibility.
No. The exact spare listing identifies 136711-01 as an RTD/TC I/O module with internal barriers and internal terminations, and explicitly marks it non-isolated. The TC-isolated I/O versions are separately identified.
No. The internal-barrier document excludes four-wire RTDs and thermocouples for the /60 and /61 applications. Its compatibility list identifies the permitted three-wire temperature transducers. Use that barrier-specific scope rather than the broader monitor-family input list.
No. The manufacturer lists 136711-01 under 3500/60-specific parts and 136711-02 under 3500/61-specific parts. The /60 monitor has no recorder outputs, while the /61 provides them. Match the installed monitor and exact I/O number.
A rack containing internal-barrier I/O requires a 3500/04-01 IS Earthing Module in a dedicated monitor position. The manufacturer also excludes external-termination and TMR options for internal-barrier I/O.
Use the barrier-specific limit. The manufacturer lists 0 to +65 degrees C when the temperature monitor is used with internal-barrier I/O, compared with the wider non-barrier range. The internal-barrier module also has a deeper 163.1 mm envelope.
The internal-barrier document requires 3500 Rack Configuration Software revision 2.3 or later and lists 3500/60 firmware version 1.06, revision E or later, for enabling the barrier option. Confirm the actual installed monitor revision and complete application before modification.
The approved transducer list includes three-wire 10 Ω copper, 100 Ω platinum and 120 Ω nickel RTDs.
Set the channel full-scale range through 3500 Configuration Software. The monitor signal-conditioning procedure calls for configuration of the range without field calibration.
Product photograph, identification and technical reference, with selected manufacturer pages covering the documented component and its system requirements.
PDF · 6 pages · 126.3 KB · Compiled by EWOLO CONTROL. Manufacturer references: 141540 Rev. L; 141495 Rev. R.
Preview Product Reference (PDF)3500/60 non-isolated RTD/TC I/O, internal terminations
3500/60 non-isolated RTD/TC I/O, external terminations
3500/60 isolated TC I/O, internal terminations
3500/60 isolated TC I/O, external terminations
3500/60 temperature monitor without recorder outputs
3500/61 RTD/TC I/O with internal barriers
3500/61 temperature monitor with recorder outputs
3500/40M Proximitor I/O, internal terminations
3500/40M Proximitor I/O, external terminations
3500/40M Proximitor I/O with internal barriers
3500/40M Proximitor monitor
3500/25 Keyphasor I/O, internal terminations
3500/25 Keyphasor I/O, external terminations
3500/25 isolated Keyphasor I/O, internal terminations
3500/25 isolated Keyphasor I/O, external terminations
EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.
We source DCS, PLC and TSI spares for maintenance and replacement.
Pay by bank transfer before dispatch, unless agreed otherwise in writing.
Model, quantity and visible condition are checked against your order.
Packaging is selected for the product and agreed shipping method.
DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.
Commercial invoice and packing list supplied. Agree extra documents before ordering.
Eligible items: 12-month return-to-base warranty from dispatch, per quotation.
Send fault details and photos. Returns need prior written approval.
REQUEST A QUOTE
Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.
Request a Quote →Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.
No online payment is requested. Final price and terms are supplied in a written quotation.
Bently Nevada 133819-01 is the internal-termination, non-isolated RTD/TC I/O module for the 3500/60 temperature-monitoring system. It forms the rear-rack sensor interface for a six-channel temperature monitor used to evaluate machinery temperatures and compare them with user-programmed alarm limits. Version check: Confirm the 3500/60 monitor, non-isolated RTD/TC input and internal termination arrangement before replacing 133819-01.
Bently Nevada 133827-01 is the external-termination, non-isolated RTD/TC I/O module for the 3500/60 temperature-monitoring system. It forms the rear-rack sensor interface for a six-channel temperature monitor used to evaluate machinery temperatures and compare them with user-programmed alarm limits. Version check: Confirm the 3500/60 monitor, non-isolated RTD/TC input and external termination arrangement before replacing 133827-01.
Bently Nevada 135489-01 is the Prox/Accel I/O module with internal barriers and internal terminations for the 3500/42M machinery-protection monitor. It combines the rear-rack field interface with the internal-barrier option required by a correctly engineered intrinsically safe transducer system. Version check: Confirm the 3500/42M monitor, four Prox/Accel channels and approved internal-barrier circuit before replacing 135489-01.
Bently Nevada 135489-04 is the Proximitor I/O module with internal barriers and internal terminations for the 3500/40M machinery-protection monitor. It combines the rear-rack field interface with the internal-barrier option required by a correctly engineered intrinsically safe transducer system. Version check: Confirm the 3500/40M monitor, Proximitor configuration and approved internal-barrier circuit before replacing 135489-04.
Bently Nevada 138708-01 is the internal-termination Shaft Absolute I/O module for the 3500/42M machinery-protection monitor. It provides the dedicated rear-rack interface for an appropriately configured shaft-absolute measurement assembly, with supported proximity/acceleration, Velomitor or Seismoprobe transducers. Version check: Confirm the 3500/42M M-version monitor, shaft-absolute sensor arrangement and required firmware/software revisions before replacing 138708-01.
Bently Nevada 140471-01 is the internal-termination Prox/Velom I/O module for the 3500/42M machinery-protection monitor. It provides the rear-rack interface for supported Prox/Accel, Velomitor and High Temperature Velocity Sensor (HTVS) applications. Version check: Confirm the Prox/Accel, Velomitor or HTVS transducers, internal terminations and 3500/42M configuration before replacing 140471-01.
Bently Nevada 140482-01 is the external-termination Prox/Velom I/O module for the 3500/42M machinery-protection monitor. It provides the rear-rack interface for supported Prox/Accel, Velomitor and High Temperature Velocity Sensor (HTVS) applications. Version check: Confirm the Prox/Accel, Velomitor or HTVS transducers, external terminations and 3500/42M configuration before replacing 140482-01.
Bently Nevada 149992-01 is the standard 16-channel relay output module used in the 3500/33 machinery-protection relay assembly. It provides the rear-rack switching interface for relay actions configured from the 3500 system's monitoring information. Version check: Confirm standard relay contacts, the minimum load, 149986-01 control module and required energized/de-energized logic before replacing 149992-01.
No online payment is requested. Final price and terms are supplied in a written quotation.
Scan to Wechat :
Scan to WhatsApp :