ISO 9001:2015 certified industrial automation spare parts supplier

Bently Nevada 129486-01 High Voltage DC Power Supply Module

Bently Nevada 129486-01 is the legacy high-voltage DC power supply module for the 3500/15 system. It is the front power-supply assembly, distinct from the rear high-voltage DC PIM.

Version check: Confirm 129486-01 is the required legacy high-voltage DC power supply and match the installed legacy PIM before ordering.

Download
  • Bently Nevada 129486-01 High Voltage DC Power Supply Module

    Bently Nevada 129486-01 is the legacy high-voltage DC power-supply module for a 3500 machinery-monitoring rack. Working with the matching 129478-01 Power Input Module, it converts the incoming DC power into the internal voltages required by the other 3500 modules. A suitable 3500 supply can power the full rack, and a two-supply arrangement provides a primary and backup source. The 129486-01 is the front power-conversion component of the legacy 88–140 VDC option, so its generation and matching PIM must be distinguished from later high-voltage DC supply designs.

    Hardware specifications. The applicable legacy high-voltage DC option accepts 88 to 140 Vdc. The power-supply module measures 120.7 x 50.8 x 251.5 mm (H x W x D), and the high-voltage DC full-rack current-draw limit is 2.5 A maximum. The Supply OK indicator is used to indicate correct supply operation. The current-draw figure is not an output rating for an arbitrary external load.

    Technical Specifications

    Parameter Specification

    Product Identity

    Part number 129486-01
    Component Legacy high-voltage DC power supply module
    Supply dimensions (H x W x D) 120.7 x 50.8 x 251.5 mm

    Functional Configuration

    Family 3500/15
    Applicable legacy input 88 to 140 Vdc
    Rack arrangement Primary supply in lower slot; optional backup in upper slot

    Performance & Power

    Full-rack current draw 2.5 A maximum, high-voltage DC option
    Supply indicator Supply OK LED

    Environment

    Operating temperature -30 to +65 degrees C
    Storage temperature -40 to +85 degrees C
    Humidity 95%, non-condensing

    Compatibility & Selection Guide

    System compatibility. A 3500 rack may use one or two power supplies; with two fitted, the lower supply is primary and the upper is backup. The current manufacturer document classifies 129486-01 as a legacy component and warns that newer DC supplies and PIMs are not compatible with legacy versions. Preserve the correct supply/PIM generation and the existing redundancy arrangement when selecting a spare.

    Wiring & Installation Reference

    Use the current manufacturer reference to check the exact module, its documented system position and applicable termination arrangement.

    DC supply and PIM matching

    1. Identify the front supply

      Confirm 129486-01 rather than the rear PIM part number.

    2. Verify the legacy input assembly

      Check the paired legacy high-voltage DC PIM and do not mix newer-generation DC hardware.

    The legacy high-voltage DC input range is 88-140 Vdc. Match the front supply and rear PIM by their documented generation.

    View legacy power layout (PDF)

    Primary and backup positions

    1. Check the redundancy arrangement

      Determine whether a second supply is actually present before planning service.

    2. Use the specified space

      Allow for the power-supply envelope of 120.7 x 50.8 x 251.5 mm; the rear PIM has different dimensions.

    The supply is a half-height module in a designated left-side rack slot. With two supplies installed, the lower one is primary and the upper one is backup.

    View mounting reference (PDF)

    Selection and handling notes

    • The newer high- and low-voltage DC power supplies and PIMs are not compatible with the legacy DC supplies and PIMs. Confirm the installed legacy generation.

    • A power supply can be removed without interrupting rack operation only when the other supply is installed. Do not extend that condition to PIM removal or live input wiring.

    Frequently Asked Questions

    Is 129486-01 the front supply or the rear power input module?

    129486-01 is the high-voltage DC power supply module. The corresponding legacy high-voltage DC input component is separately listed as 129478-01. Match the location and complete part number of the assembly being replaced.

    Can 129486-01 power a complete 3500 rack on its own?

    The manufacturer states that either supply can power a full rack and that a rack can contain one or two supplies. An installed second supply acts as backup. Verify the actual rack arrangement and applicable input requirements rather than assuming a redundant supply is present.

    Is 129486-01 interchangeable with the newer high-voltage DC power supply?

    The current datasheet explicitly states that the newer DC supplies and PIMs are not compatible with legacy DC supplies and PIMs. It lists 129486-01 as legacy and separately identifies the newer high-voltage DC supply. Voltage similarity alone is insufficient for replacement.

    What does the Supply OK indication mean on 129486-01?

    The legacy power-supply datasheet describes the Supply OK LED as indicating that the power supply is operating properly. It does not certify the condition or configuration of every other module in the rack.

    When can removal of 129486-01 leave the rack operating?

    The manufacturer states that removing or inserting either power-supply module does not disrupt the rack while a second supply is installed. Confirm the actual backup arrangement and follow the system service instructions; do not apply this statement to energized PIM field-wire work.

    Does the legacy 3500/15 supply 129486-01 need a minimum rack load?

    The 3500/15 legacy power-supply specification sets no minimum rack load.

    Where is the input protection fuse in an assembly using front power supply 129486-01?

    The input protection fuse is in the matching rear power-input module. For the 129478-01 high-voltage DC input module, the listed fuse is 01720045.

    What is the published module weight for the 129486-01 front power supply?

    The legacy front power-supply module weighs 1.39 kg (3.06 lb).

    Manufacturer Documentation

    129486-01 Product Reference

    Product photograph, identification and technical reference, with selected manufacturer pages covering the documented component and its system requirements.

    PDF · 4 pages · 123.8 KB · Compiled by EWOLO CONTROL. Manufacturer references: 141530-01 Rev. C (07/09); 141530 Rev. P.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Bently Nevada 129486-01

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.