Allen-Bradley 1756-L72 ControlLogix 4 MB Controller

ControlLogix 5570 controller with 4 MB user memory, USB programming and Secure Digital nonvolatile storage.

Version check: Match 1756-L72 hardware series and project firmware; 1756-L72K is the separate conformal-coated variant. Confirm the fitted SD card and energy storage module, as standard, no-WallClockTime-backup and non-removable ESM options differ.

Download
  • Allen-Bradley 1756-L72 ControlLogix 4 MB Controller

    Allen-Bradley 1756-L72 is a ControlLogix 5570 programmable controller for coordinating application logic, modular I/O and supported integrated-motion functions. Its task structure allows control routines to run continuously, at scheduled intervals or in response to events, so different parts of a machine or process can be organized around their operating requirements. The controller supports several Logix programming languages and communicates with distributed equipment through the appropriate chassis communication modules. 1756-L72 is therefore the processing component of a configured ControlLogix system, rather than a complete controller-and-I/O package; network, motion and redundancy capabilities depend on the selected system configuration.

    Hardware specifications. The single-slot controller has 4 MB of user memory, 0.98 MB of I/O memory and a USB programming port. Secure Digital storage and a capacitor-based energy storage module support its memory architecture; Ethernet networking uses a separate communication module.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Allen-Bradley
    Complete part number 1756-L72
    Controller family ControlLogix 5570
    Module width 1 chassis slot

    Functional Configuration

    Built-in communication port 1 × USB
    USB communication USB 2.0 full speed, 12 Mbps; temporary programming only
    Nonvolatile memory Secure Digital; 1784-SD1 standard option
    Energy storage 1756-ESMCAP removable capacitor module; alternate ESM options available

    Performance & Power

    User memory 4 MB
    I/O memory 0.98 MB
    Maximum controller connections 500
    Controller tasks 32
    Programs per task Up to 1000 with Logix Designer v24 or later
    Backplane current at 5.1V DC 800 mA
    Backplane current at 1.2V DC 5 mA
    Power dissipation 2.5 W

    Environment

    Operating temperature 0…60 °C

    Compatibility & Selection Guide

    System and software compatibility. Use project firmware with a compatible RSLogix 5000 or Studio 5000 Logix Designer version. Logix Designer version 24 or later supports up to 1000 programs per task; redundancy requires a supported chassis configuration with compatible hardware and firmware.

    Wiring & Installation Reference

    The controller plugs into the ControlLogix backplane. Use USB for temporary workstation access and a suitable chassis communication module for the plant network.

    Interfaces and connections

    Interface Connection Check
    Backplane Power and chassis communication. Match the actual hardware series and system configuration.
    USB Temporary programming, configuration and firmware access. Match the actual hardware series and system configuration.
    SD card slot Nonvolatile project storage. Match the actual hardware series and system configuration.
    ESM Selected energy storage module. Match the actual hardware series and system configuration.

    Keep the USB connection temporary; the cable must be no longer than 3 m and must not include a hub.

    Allow the energy storage module to finish charging before removing power; CHRG or ESM Charging must no longer be displayed.

    View connection specifications (PDF)

    Mounting and connection

    1. Prepare the enclosure

      Install the chassis and power supply in the required enclosure.

    2. Fit the controller

      Align the board with the upper and lower guides and slide it in until it locks and sits flush.

    3. Check accessories

      Seat the specified ESM and SD card, insert the controller key, and verify status indicators after power-up.

    View chassis installation

    Power and handling precautions

    • Do not use USB in hazardous locations.

    • Remove power or verify the area is nonhazardous before making or breaking connections or inserting or removing the controller, SD card or ESM.

    • Use grounding and ESD precautions; avoid touching connectors and board components.

    • After power is removed, wait until the controller OK indicator changes from green to steady red and then turns off before removing a removable ESM. Do not remove a fitted 1756-ESMNRM, which is non-removable.

    • If an application requires a 1756-ESMNSE to deplete residual stored energy to 40 µJ or less before transport, turn off chassis power and wait at least 20 minutes before removing the ESM; the OK indicator does not measure this waiting period.

    Frequently Asked Questions

    How much memory does 1756-L72 have?

    It has 4 MB of user memory and 0.98 MB of I/O memory.

    Does 1756-L72 include a built-in Ethernet port?

    No. The built-in connector is USB. Add a suitable ControlLogix communication module for EtherNet/IP networking.

    Can the USB port on 1756-L72 remain connected permanently?

    No. It is intended for temporary local programming, configuration, firmware updates and online edits.

    Does 1756-L72 use a replaceable lithium battery?

    It uses a capacitor-based energy storage module. The standard removable option is 1756-ESMCAP.

    What is the difference between 1756-L72 and 1756-L72K?

    The K variant is conformal coated for additional protection in corrosive environments. Confirm the full catalog number required by the installation.

    Does 1756-L72 support controller redundancy?

    Yes. Use a supported redundant system configuration and matching hardware and firmware; redundancy requires more than adding a second controller.

    What operating temperature is specified for 1756-L72?

    The specified operating range is 0…60 °C.

    Which SD cards are specified for 1756-L72?

    1784-SD1 and 1784-SD2 are the specified Secure Digital options. Confirm the card supplied with the order separately.

    Manufacturer Documentation

    1756-L72 Product Reference

    Product identification, actual photograph and compatibility notes, followed by selected original manufacturer reference pages.

    PDF · 9 pages · 125.0 KB · Compiled by EWOLO CONTROL. 1756-TD001 W / October 2025; 1756-UM001 Q / December 2024

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Allen-Bradley 1756-L72

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.