ISO 9001:2015 certified industrial automation spare parts supplier

Allen-Bradley 1756-L63 ControlLogix 8 MB Controller

ControlLogix 5560 controller with 8 MB user memory, an RS-232 port and chassis-based I/O and communication expansion.

Version check: Match the hardware series and project firmware; 1756-L63 Series B requires firmware 13.40 or later with compatible RSLogix 5000 software. Series B uses a 1756-BA2 battery, while Series A battery arrangements differ.

Download
  • Allen-Bradley 1756-L63 ControlLogix 8 MB Controller

    Allen-Bradley 1756-L63 is a ControlLogix 5560 programmable controller that serves as the application-processing element of a modular automation system. It executes control logic, works with local and distributed I/O, and exchanges data through the communication options selected for the chassis. Programs can combine ladder logic, structured text, function block diagrams and sequential function charts to organize different control functions. The controller also supports integrated motion within the applicable system configuration. These capabilities position 1756-L63 as a controller for an existing ControlLogix 5560 architecture, with the installed hardware series, firmware and project configuration determining the correct replacement match.

    Hardware specifications. The single-slot controller provides 8 MB of user memory, 478 KB of I/O memory and one RS-232 serial port. It supports an optional 128 MB 1784-CF128 CompactFlash card for nonvolatile storage.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Allen-Bradley
    Complete part number 1756-L63
    Controller family ControlLogix 5560
    Module width 1 chassis slot
    Approximate weight 0.35 kg (Series B)

    Functional Configuration

    Built-in communication port 1 × RS-232 serial
    Optional nonvolatile storage 1784-CF128, 128 MB CompactFlash
    Programming languages Relay ladder, structured text, function block diagram and SFC
    Replacement battery 1756-BA2 (Series B photographed unit)

    Performance & Power

    User memory 8 MB
    I/O memory 478 KB
    Maximum controller connections 250
    Controller tasks 32; up to 100 programs per task
    Backplane current at 5.1V DC 1200 mA
    Backplane current at 24V DC 14 mA
    Power dissipation 3.5 W

    Environment

    Operating temperature 0…60 °C

    Compatibility & Selection Guide

    System and software compatibility. Series B requires firmware revision 13.40 or later and a compatible RSLogix 5000 software version. Select the controller firmware for the installed project and use the appropriate ControlLogix communication modules for the required industrial networks.

    Wiring & Installation Reference

    The 1756-L63 receives power through the ControlLogix backplane. Its front serial interface is for RS-232 communication; field I/O connects through the separately selected I/O modules.

    Interfaces and connections

    Interface Connection Check
    Backplane Install in a compatible powered ControlLogix chassis. Match the actual hardware series and system configuration.
    RS-232 Connect a programming workstation or serial device with the appropriate serial cable. Match the actual hardware series and system configuration.
    CompactFlash Fit the supported memory card using the procedure for the controller series. Match the actual hardware series and system configuration.

    A 1756-CP3 cable is suitable for workstation connection. The alternative 1747-CP3 cable can prevent the controller door from closing.

    Confirm controller hardware series and firmware compatibility before loading a saved project.

    View serial connection diagram (PDF)

    Mounting and connection

    1. Prepare the chassis

      Install and ground the specified chassis and power supply before fitting the controller.

    2. Seat the controller

      Set the key to PROG, align the circuit board with both chassis guides, and slide the controller in until both latches engage.

    3. Connect and verify

      Confirm the module is flush with adjacent modules, connect the serial cable as required, and inspect the controller status indicators.

    View chassis installation

    Power and handling precautions

    • Remove power or establish that the location is nonhazardous before inserting or removing the controller, memory card, battery or serial connection.

    • Use ESD controls and avoid touching the circuit board contacts.

    • Use an appropriate enclosure that prevents access to live parts; enclosure access must require a tool.

    Frequently Asked Questions

    How much user memory does 1756-L63 provide?

    It provides 8 MB of user memory and 478 KB of I/O memory.

    Does 1756-L63 have a built-in Ethernet port?

    No. Its built-in port is RS-232; an appropriate ControlLogix communication module provides EtherNet/IP connectivity.

    Which nonvolatile memory card can 1756-L63 use?

    The controller supports the optional 1784-CF128 CompactFlash card. Use the card installation procedure for the actual hardware series.

    Which battery is used with 1756-L63 Series B?

    Series B uses the 1756-BA2 battery. Do not select a Series A battery arrangement solely from the base catalog number.

    What firmware is required for 1756-L63 Series B?

    Series B requires firmware revision 13.40 or later. The chosen firmware must also match the project and RSLogix 5000 software version.

    How many chassis slots does 1756-L63 occupy?

    It occupies one slot and may be placed in any supported ControlLogix chassis slot.

    What is the operating temperature range of 1756-L63?

    The specified operating range is 0…60 °C. The installation must also meet the enclosure and environmental requirements.

    Can a 1747-CP3 cable connect a workstation to 1756-L63?

    Yes. A 1747-CP3 cable can provide the serial connection, although the controller door may not close with that cable fitted. A 1756-CP3 cable is also specified.

    Manufacturer Documentation

    1756-L63 Product Reference

    Product identification, actual photograph and compatibility notes, followed by selected original manufacturer reference pages.

    PDF · 8 pages · 125.6 KB · Compiled by EWOLO CONTROL. 1756-TD001L-EN-P L / June 2016; 1756-IN101 L / June 2008

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Allen-Bradley 1756-L63

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message