ISO 9001:2015 certified industrial automation spare parts supplier

Bently Nevada 125720-01 Four-Channel Relay Output Module

Bently Nevada 125720-01 is the four-channel relay output spare listed for the 3500/32M family. The current manufacturer datasheet identifies this exact part as available for repair only.

Version check: Confirm 125720-01 and the installed 3500/32M relay assembly. The manufacturer spare entry lists this part as available for repair only.

Download
  • Bently Nevada 125720-01 Four-Channel Relay Output Module

    Bently Nevada 125720-01 is the four-channel relay output component used with the 3500/32M relay control assembly to turn machinery-monitoring conditions into external relay signals. The assembly's programmable alarm-drive logic can combine Alert, Danger and Not-OK conditions from selected monitor channels, allowing each relay to respond to the application's alarm requirements. The 125720-01 provides the output-side hardware; the separately listed 149986-02 is the relay control module. This distinction matters when sourcing a replacement, and the current spare-parts listing identifies 125720-01 as available for repair only.

    Hardware specifications. The relay family uses single-pole, double-throw contacts. Its I/O module envelope is 241 x 24.4 x 99.1 mm (H x W x D). Contact limits depend on the load and application: the standard-system ratings differ from the restricted ratings for hazardous-area and functional-safety systems. A contact-life test value is not an unrestricted switching-current rating.

    Technical Specifications

    Parameter Specification

    Product Identity

    Part number 125720-01
    Component Four-channel relay output module
    I/O dimensions (H x W x D) 241 x 24.4 x 99.1 mm
    Rack space One full-height rear slot
    Manufacturer spare listing Available for repair only

    Functional Configuration

    Associated family 3500/32M
    Relay type Single-pole, double-throw (SPDT)

    Performance & Power

    Standard-system resistive DC limits 2 A at 0-30 Vdc; 0.75 A at 48 Vdc; 0.2 A at 125 Vdc

    Environment

    Operating temperature -30 to +65 degrees C
    Storage temperature -40 to +85 degrees C
    Humidity 95%, non-condensing
    Hazardous / functional-safety limits Restricted to 30 Vdc / 30 Vac; observe the complete ratings and approval conditions

    Compatibility & Selection Guide

    System compatibility. The associated 3500/32M control module provides programmable alarm-drive voting logic using 3500 Rack Configuration Software and requires a compatible 3500/22 TDI environment. For an existing system, review the control module, firmware, configured relay logic and approval requirements together. The separately listed 125720-02 has a specified hazardous-area and functional-safety role; the datasheet alone does not establish unconditional interchangeability with 125720-01.

    Wiring & Installation Reference

    Use the current manufacturer reference to check the exact module, its documented system position and applicable termination arrangement.

    Contact and load selection

    1. Identify the circuit

      Confirm AC or DC, resistive-load requirements and the installed approval category.

    2. Apply the correct limits

      Use the restricted voltage limits where required; do not use the contact-life test current as the circuit rating.

    Match the field load to the applicable manufacturer contact-rating table. Standard, hazardous-area and functional-safety applications have different limits.

    View relay module layout (PDF)

    Relay assembly and rear slot

    1. Verify both assemblies

      Distinguish output module 125720-01 from control module 149986-02.

    2. Review host requirements

      Check the existing 3500/32M TDI and software environment against the manufacturer ordering notes.

    The output I/O occupies one full-height rear slot. Match it to the associated relay control assembly and retain the intended alarm-drive configuration.

    View mounting reference (PDF)

    Selection and handling notes

    • Relay field wiring can present a shock hazard. Do not exceed the applicable rated voltages; hazardous-area and functional-safety systems have restricted limits.

    Frequently Asked Questions

    Is 125720-01 the relay control board or the output module?

    It is the four-channel relay output spare. The current datasheet separately lists 149986-02 as the relay control module, so the output module and control board should not be ordered as though they were the same assembly.

    Can 125720-01 still be ordered as a normal new manufacturer spare?

    The current 3500/32M manufacturer datasheet marks 125720-01 as available for repair only. This statement is separate from a distributor having unused stock. Confirm the identity and offered condition of any sourced unit.

    Does the 5 A contact-life figure mean 125720-01 can switch every 5 A load?

    No. The contact-life test condition and the permitted switching ratings are separate entries. The standard-system resistive-load limits include 2 A at 0-30 Vdc, with lower current at higher DC voltage; AC limits are also specified. Apply the correct table and application restrictions.

    Can 125720-01 be replaced by 125720-02 without further checks?

    Do not assume an unconditional substitution. The manufacturer lists 125720-02 for hazardous-area and functional-safety systems, while 125720-01 is repair-only. Review the installed relay assembly, approvals, load ratings and required configuration before choosing a replacement.

    Where is the alarm-drive logic for an assembly using 125720-01 configured?

    The 3500/32M relay assembly uses 3500 Rack Configuration Software for alarm-drive logic based on monitor statuses and voting conditions. Check the host module and TDI/software requirements in the ordering section; the rear output part number alone does not identify the installed logic or firmware.

    What is the minimum switched load for 125720-01 in a standard 3500/32M system?

    The minimum specified switched current is 100 mA at 12 V DC under the standard-system contact ratings.

    Can channels on 125720-01 use different normal coil states?

    Yes. Each of the four relay channels has its own switch selection for normally energized or normally de-energized operation.

    What does the 3500/32M channel alarm LED report when the assembly uses 125720-01?

    CH ALARM indicates that the associated relay channel is in an alarm state. TX/RX shows rack communications.

    Manufacturer Documentation

    125720-01 Product Reference

    Product photograph, identification and technical reference, with selected manufacturer pages covering the documented component and its system requirements.

    PDF · 7 pages · 114.1 KB · Compiled by EWOLO CONTROL. Manufacturer references: 141533 Rev. W.

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Bently Nevada 125720-01

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.