Siemens 6AV2123-2GA03-0AX0 KTP700 Basic DP Panel

Siemens 6AV2123-2GA03-0AX0 is the SIMATIC HMI KTP700 Basic DP PROFIBUS DP operator panel, with a 7-inch color touchscreen and 8 function keys. It gives machine operators a local interface for process values, alarms and configured control actions.

Version check: Check the complete order number, PROFIBUS DP connection and installed WinCC project before selecting a replacement.

Download
  • Siemens 6AV2123-2GA03-0AX0 KTP700 Basic DP

    Siemens 6AV2123-2GA03-0AX0 is the SIMATIC HMI KTP700 Basic DP, a second-generation Basic Panel for operator control and monitoring over a PROFIBUS DP connection. Its 7-inch touchscreen and eight function keys provide access to machine values, operator commands and alarm acknowledgement. Configured trend views and recipe records support observation of changing process values and management of production settings. The DP interface is a defining selection feature of this complete order number, particularly when maintaining an existing machine project built around PROFIBUS communication.

    Hardware specifications. The 6AV2123-2GA03-0AX0 combines a TFT widescreen display with 800 × 480-pixel resolution, 65,536 colors and LED backlighting. An ARM processor works with 10 MB of user data memory. One RS422/RS485 interface provides the serial connection, and one USB interface is available; this DP version has no Industrial Ethernet interface. The nominal supply is 24 V DC, with an allowed range of 19.2–28.8 V DC, rated current of 230 mA and typical power consumption of 5.5 W. The front and rear protection ratings are IP65 and IP20 respectively, subject to the specified installation conditions.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Siemens AG
    Complete order number 6AV2123-2GA03-0AX0
    Product family SIMATIC HMI Basic Panels, second generation
    Product designation KTP700 Basic DP PROFIBUS DP
    Housing front (W × H) 214 × 158 mm
    Mounting cutout (W × H) 198 × 142 mm, as listed in the current Siemens datasheet
    Mounting depth 39 mm

    Functional Configuration

    Display 7-inch TFT widescreen; LED backlighting
    Resolution / colors 800 × 480 pixels / 65,536 colors
    Active display area 154.1 × 85.9 mm
    Operation Analog resistive touchscreen and 8 function keys
    Interfaces 1 RS422/RS485 interface; 1 USB interface; no Industrial Ethernet
    Communication PROFIBUS/MPI; Modicon Modbus RTU supported; no PROFINET or Modbus TCP/IP
    Engineering software Configurable from WinCC Basic V13 / STEP 7 Basic V13

    Performance & Power

    Processor / user-data memory ARM / 10 MB
    Rated supply / permitted range 24 V DC / 19.2–28.8 V DC
    Rated current / typical power 230 mA / 5.5 W
    Project capacity 800 variables; 250 configurable screens; 50 recipes

    Environment

    Protection IP65 front / IP20 rear, subject to correct installation
    Operating temperature, landscape 0–50 °C upright; 0–40 °C at maximum tilt
    Operating temperature, portrait 0–40 °C upright; 0–35 °C at maximum tilt
    Maximum inclination 35° from vertical
    Storage / transport temperature −20 to +60 °C

    Compatibility & Selection Guide

    Software and system compatibility. The 6AV2123-2GA03-0AX0 is configurable from WinCC Basic V13 / STEP 7 Basic V13 in TIA Portal. Siemens lists PROFIBUS/MPI communication and supported serial drivers including Modicon Modbus RTU. Select the controller interface and WinCC driver for the actual system; a listed controller family does not make an Ethernet-only connection compatible. Published project limits include 800 variables, 250 configurable screens and 50 recipes.

    Wiring & Installation Reference

    Check 6AV2123-2GA03-0AX0 on the nameplate before connection. Use the PROFIBUS DP interfaces and the dimensions specified for this exact order number.

    Power and interfaces

    Interface Marking Connection
    Power DC24V X80 Pin 1: +24 V DC (L+); pin 2: GND 24 V (M).
    PROFIBUS / serial RS422/RS485 X2 X2: 9-pin RS422/RS485 interface. For PROFIBUS RS485, pin 3 is Data B (+) and pin 8 is Data A (−); use the appropriate connector and network settings.
    USB USB X60 USB interface for supported storage and service peripherals.

    Supply: 24 V DC nominal; permitted range 19.2–28.8 V DC.

    Connection: This DP model has no Ethernet interface. Configure the correct MPI/DP address, profile and baud rate; use the intended RS422/RS485 driver.

    View installation reference (PDF)

    Panel mounting and connection

    1. Prepare the enclosure

      Disconnect cabinet power and use qualified personnel. Provide access to the operating front and a protected rear enclosure.

    2. Check the opening

      Use the current Siemens datasheet cutout of 198 × 142 mm. The supporting material must be 2–6 mm thick, with a flat, stable sealing surface for the stated front protection.

    3. Secure the panel

      Insert the KTP700 Basic DP from the front and secure all 7 mounting clips. Do not exceed 0.2 N·m clip torque. Maintain the required ventilation space and orientation-dependent temperature limits.

    4. Connect and check

      Connect equipotential bonding, then the safely isolated DC supply, configuration PC and controller in the documented sequence. Verify polarity and secure cables against strain.

    View dimensions reference (PDF)

    Power and handling precautions

    • Use an SELV/PELV supply. Power conductors may be up to 1.5 mm²; strip 6 mm and fit cable end sleeves. Isolate the supply while terminating.

    • Connect the panel functional-earth point to the bonding rail with 4 mm² conductor. Cable shields do not replace the plant equipotential-bonding network; follow the manual for its sizing and routing.

    Frequently Asked Questions

    Is 6AV2123-2GA03-0AX0 the PROFIBUS model or an Ethernet panel?

    6AV2123-2GA03-0AX0 is the KTP700 Basic DP model with a PROFIBUS-capable RS422/RS485 interface. It has no Industrial Ethernet interface. Verify the complete order number and the controller connection before replacing a PROFINET panel; the physical connection and driver are different.

    Can 6AV2123-2GA03-0AX0 connect to a Modbus TCP controller?

    The datasheet lists Modicon Modbus RTU for this DP panel and explicitly lists Modicon Modbus TCP/IP as unsupported. Use the supported serial driver and correct RS422/RS485 wiring for the application. Do not treat the USB port as an Ethernet or serial-protocol converter.

    How is a project transferred to 6AV2123-2GA03-0AX0?

    Siemens lists MPI/PROFIBUS DP and an external storage medium as transfer methods for this model. Direct Ethernet and direct USB project transfer are not supported. Check the engineering PC connection, configured transfer channel and MPI/DP network settings before commissioning.

    Can 6AV2123-2GA03-0AX0 reuse a KTP600 Basic or TP700 Comfort cutout?

    The operating instructions list the KTP700 Basic cutout as compatible with KTP600 Basic color PN and TP700 Comfort openings. The current exact-model datasheet specifies 198 × 142 mm. Check the actual opening, rear clearance and sealing surface; mechanical fit alone does not establish project or function compatibility.

    Does 6AV2123-2GA03-0AX0 support Sm@rtServer remote access?

    The current Siemens datasheet lists Sm@rtServer and a web browser as unsupported for this DP model. Do not select it on the assumption that an existing remote-view or browser-based service function will be retained.

    Can 6AV2123-2GA03-0AX0 archive alarms and process values on USB?

    Siemens supports one message archive and one process-value archive, with up to 10,000 entries per archive, using USB memory and TXT storage format. The datasheet does not support CSV storage. Use suitable industrial USB media and confirm the required archive settings in the project.

    What must be saved before updating or replacing 6AV2123-2GA03-0AX0?

    Retain the engineering project and make a suitable WinCC or ProSave backup, including recipe and user data that must be kept. Select the correct HMI device and check the panel-image version. An operating-system update deletes panel data, including the project and licenses; maintain stable power throughout backup and restore.

    Can 6AV2123-2GA03-0AX0 load an individual project from USB storage?

    Yes, with a panel image compatible with WinCC (TIA Portal) V14 or later. Use Project Download in Service & Commissioning. The load options let you choose whether to overwrite user administration and recipe data.

    Manufacturer Documentation

    6AV2123-2GA03-0AX0 Product Reference

    Product photograph, model-specific overview and connection notes, together with selected Siemens datasheet pages for the KTP700 Basic DP.

    PDF · 6 pages · 115.7 KB · Compiled by EWOLO CONTROL. Siemens exact-model datasheet 6AV2123-2GA03-0AX0, generated 2026-10-10; Basic Panels 2nd Generation Operating Instructions A5E33293231-AB, October 2016.

    Preview Product Reference (PDF)

    Original manufacturer resources

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Siemens 6AV2123-2GA03-0AX0

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.