ISO 9001:2015 certified industrial automation spare parts supplier

Siemens 6ES7313-6CG04-0AB0 SIMATIC S7-300 CPU 313C-2 DP

Siemens 6ES7313-6CG04-0AB0 is the SIMATIC S7-300 CPU 313C-2 DP for a compact station that combines local digital I/O with a PROFIBUS DP interface.

Match the project hardware entry to CPU 313C-2 DP before exchanging this CPU. Engineering baseline: STEP 7 V5.5 SP1 or V5.3 SP2 with HSP 203.

Download
  • Siemens 6ES7313-6CG04-0AB0 SIMATIC S7-300 CPU 313C-2 DP

    Siemens 6ES7313-6CG04-0AB0 is the SIMATIC S7-300 CPU 313C-2 DP. The 313C-2 DP integrates 16 digital inputs and 16 digital outputs for local machine signals. Its separate PROFIBUS DP interface connects distributed devices while the MPI interface remains available for programming and S7 communication. Embedded I/O comprises 16 DI and 16 DO. The 3 high-speed counters support signals up to 30 kHz.

    Hardware specifications. Integrated work memory is 128 KB, with a typical bit-operation time of 0.07 µs. The 24 V DC supply operates over 19.2–28.8 V DC. The CPU draws 800 mA at its rating and 110 mA typically without load. Its typical power loss is 9 W.

    Software and system compatibility. MPI supports up to 187.5 kbit/s. PROFIBUS DP supports up to 12 Mbit/s and a maximum of 124 DP devices in master mode. This order number uses the CPU 313C-2 DP hardware entry in STEP 7 with STEP 7 V5.5 SP1 or V5.3 SP2 with HSP 203. A SIMATIC Micro Memory Card provides the load memory.

    Technical Specifications

    Parameter Specification

    Product Identity

    Manufacturer Siemens AG
    Complete order number 6ES7313-6CG04-0AB0
    Product family SIMATIC S7-300
    CPU designation CPU 313C-2 DP
    Data-sheet revision baseline Hardware 01 / firmware V3.3
    Housing (W × H × D) 80 × 125 × 130 mm
    Approximate weight 500 g

    Functional Configuration

    Communications MPI and PROFIBUS DP
    Signal arrangement 16 DI and 16 DO
    High-speed counters 3 counters, up to 30 kHz
    Engineering software STEP 7 V5.5 SP1 or V5.3 SP2 with HSP 203

    Performance & Power

    Integrated work memory 128 KB
    Rated supply 24 V DC
    Permissible supply range 19.2–28.8 V DC
    Rated current 800 mA
    Typical no-load current 110 mA
    Typical inrush current 5 A
    Typical power loss 9 W
    Typical bit operation 0.07 µs
    Typical floating-point operation 0.72 µs

    Environment

    Horizontal mounting 0 to 60 °C
    Vertical mounting 0 to 40 °C

    Compatibility & Selection Guide

    Engineering baseline. Configure the exact CPU 313C-2 DP hardware entry with STEP 7 V5.5 SP1 or V5.3 SP2 with HSP 203.

    Compact I/O selection. The 16 onboard inputs and 16 onboard outputs are digital. An application with local analog channels needs appropriate external signal modules.

    Wiring & Installation Reference

    6ES7313-6CG04-0AB0 wiring references cover the supply, network ports and local I/O for this CPU variant.

    Power and interfaces

    Interface Connection Application
    CPU supply 24 V DC Operating range 19.2–28.8 V DC.
    MPI RS-485 Integrated MPI connection for engineering and S7 communication.
    PROFIBUS DP Isolated RS-485 Dedicated DP interface with master and slave modes.
    Local field I/O Front connector One 40-pin front connector.

    View Siemens model data sheet (PDF, p. 3)

    Installation checks

    1. Power and connection

      Use the 19.2–28.8 V DC operating supply range for the CPU. One 40-pin front connector.

    2. Rail and ventilation

      Mount the power supply and CPU at the left of a horizontal assembly or at the bottom of a vertical assembly. Maintain at least 40 mm clearance above and below the modules.

    3. I/O address assignment

      Use the exact compact CPU configuration for the built-in channels and connect each field signal to its assigned front connector position.

    View installation layout (PDF, p. 31)

    Power and handling precautions

    • CPU supply and protection. The CPU expects 19.2–28.8 V DC. Siemens recommends a type C breaker rated at least 2 A or type B rated at least 4 A. Its typical inrush current is 5 A.

    • Field connections. One 40-pin front connector. Verify polarity on the 24 V DC L+ load supply before power is applied. The onboard digital output supply has no reverse-polarity protection.

    • Network settings. Connect the MPI and PROFIBUS networks to their respective ports. Set the DP address, speed and master or slave role to the values used in STEP 7.

    Frequently Asked Questions

    How large a Micro Memory Card can 6ES7313-6CG04-0AB0 use?

    It accepts a SIMATIC Micro Memory Card up to 8 MB as load memory.

    How much retentive data can 6ES7313-6CG04-0AB0 preserve on a power interruption?

    The maximum retentive data area is 64 KB. Allocate the values that must survive a power interruption within that limit.

    How many diagnostic events can 6ES7313-6CG04-0AB0 retain for fault finding?

    The diagnostic buffer has up to 500 entries, with the last 100 entries retained after power loss.

    How long does the real-time clock of 6ES7313-6CG04-0AB0 keep time without power?

    Clock backup time is six weeks at an ambient temperature of 40 °C.

    How many S7-300 racks can 6ES7313-6CG04-0AB0 address in one local assembly?

    The configuration supports up to four racks in total, including the central rack.

    What block-count limit should a project migration to 6ES7313-6CG04-0AB0 allow for?

    The CPU supports up to 1,024 DBs, FCs and FBs combined. The selected memory card can reduce the number that can actually be loaded.

    How many connections can be allocated to programming devices on 6ES7313-6CG04-0AB0?

    The configurable allocation for PG communication is 1 to 7 connections.

    Which startup organization block can 6ES7313-6CG04-0AB0 execute?

    Startup logic runs in OB 100. The CPU supports one startup organization block.

    Manufacturer Documentation

    6ES7313-6CG04-0AB0 Product Reference

    Model-specific specifications, compatibility, installation and the selected Siemens data sheet page.

    PDF · 3 pages · 125.4 KB · Compiled by EWOLO CONTROL.

    Preview Product Reference (PDF)

    Original manufacturer resources

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    Siemens 6ES7313-6CG04-0AB0

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message