GE IC695CPL410-AAAA Rackless RX3i Edge Controller

GE IC695CPL410-AAAA is the original -AAAA revision of the PACSystems RX3i CPL410 rackless controller. It combines PACSystems control with a separate edge-processing environment for applications that require controller operation and higher-level data handling on the same unit.

Version check: Confirm the -AAAA label, installed controller/edge software and PME project; later PACEdge/WebHMI packages and expanded PROFINET capacity are not implied by this revision.

Download
  • GE IC695CPL410-AAAA Rackless RX3i Edge Controller

    GE IC695CPL410-AAAA is the initial -AAAA revision of the PACSystems RX3i CPL410 rackless edge controller. It combines an RX3i control runtime with a separate Linux-based edge environment, allowing control applications and higher-level data-processing applications to operate within one controller platform. Dedicated network interfaces separate the control-system and edge connections, while the local display provides access to controller status and network information. This complete ordering identity is important for an existing installation because the actual firmware, edge-software version and project requirements must be matched to this early hardware revision.

    Hardware specifications. The CPL410 family provides 64 MB of configurable control program/data memory and an OLED status display. Front connections include one LAN1 RJ45 port, two switched LAN2 ports and two switched LAN3 ports, with 10/100/1000 Ethernet capability. The underside Ethernet connection serves the separate edge environment.

    Technical Specifications

    Parameter Specification

    Product Identity

    Platform PACSystems RX3i
    Complete code IC695CPL410-AAAA

    Functional Configuration

    Product function Rackless controller with separate edge environment
    Front network interfaces LAN1: 1 port; LAN2: 2 switched ports; LAN3: 2 switched ports
    Ethernet rates 10/100/1000 Mbps
    Status display OLED
    Configuration software PME; native CPL410 configuration from 9.50 SIM 10
    Edge software / licenses Confirm the actual offered configuration

    Performance & Power

    Control program / data memory 64 MB
    Supply External SELV supply, 18-30 V DC

    Environment

    Operating / storage temperature −40 to +70 °C operating, −40 to +85 °C in storage

    Compatibility & Selection Guide

    System and software compatibility. The official release history lists IC695CPL410-AAAA in August 2018 at firmware 9.55. Native CPL410 configuration requires PME 9.50 SIM 10 or later, subject to the actual firmware and project features. Later PACEdge/WebHMI packages, licenses and expanded PROFINET capacities must be checked individually; they are not established by the historical -AAAA code.

    Wiring & Installation Reference

    Use the applicable rackless CPU installation instructions and verify the installed firmware and accessories before replacement.

    Power and network connections

    Connection Purpose Check
    + / - External SELV DC supply 18-30 V DC; observe polarity
    FGND Ground connection Follow the documented grounding arrangement
    LAN3 Redundant CPU synchronization No unrelated network devices

    The specified power mating connector is Phoenix 1827716. Use 24-16 AWG conductors, strip 7 mm and tighten terminal screws to 0.248 N·m.

    View power connection diagram (PDF)

    DIN-rail or panel mounting

    1. Select the adaptor

      Use the DIN-rail adaptor or compatible panel-mount adaptor.

    2. Secure the unit

      Observe the manufacturer mounting clearances. Replacement adaptor plates use four Torx M3 screws tightened to 0.6 N·m.

    3. Confirm the application

      Verify actual firmware, saved project, network settings and any Energy Pack before returning the CPU to service.

    View mounting instructions (PDF)

    Power and handling precautions

    • Keep power and the required Energy Pack connected throughout a firmware update; follow the manufacturer update procedure.

    • Incorrect connection of the positive supply to FGND can cause a short circuit. Confirm polarity before energizing.

    • If an IC695ACC403 Energy Pack is used, follow its separate wiring and grounding instructions.

    Frequently Asked Questions

    Does IC695CPL410-AAAA automatically include the latest PACEdge and WebHMI package?

    No. The -AAAA code is a historical hardware/release identifier. Confirm the actual software image and licenses; current-family package descriptions do not prove what is installed on an older unit.

    Which PME version is listed for IC695CPL410-AAAA?

    GFK-3003AC specifies PME 9.50 SIM 10 or later for native CPL410 configuration. Match the installed firmware and required features as well.

    Does IC695CPL410-AAAA always support sixty-four PROFINET devices?

    No. The expanded CPL410 limit is firmware/software-dependent: GFK-3003AC identifies firmware 10.15 and PME 9.80 SIM 7 or later for that capability. Do not infer it from the -AAAA suffix.

    What is LAN3 used for on IC695CPL410-AAAA?

    It is the dedicated high-speed synchronization network for the supported redundant CPU arrangement, not a general-purpose connection for other equipment.

    Can I replace another RX3i CPU with IC695CPL410-AAAA without changing the project?

    A replacement requires a compatibility review of the CPU target, firmware, PME version, I/O configuration and application code. A common RX3i family name does not establish a drop-in replacement.

    What should be supplied when ordering IC695CPL410-AAAA?

    Provide the full label, actual controller firmware, required edge-software image/license, PME project version and the existing network/I/O configuration.

    Where can I read the installed PLC firmware revision of IC695CPL410-AAAA on the controller?

    Open the firmware revision item on the front OLED display. DISP moves between menu items and SEL opens the selected item.

    Can IC695CPL410-AAAA preserve its controller state through a power loss?

    A charged IC695ACC403 Energy Pack supplies the energy needed to save the controller state when external power fails.

    Manufacturer Documentation

    IC695CPL410-AAAA Product Reference

    Product photograph, identification and compatibility notes, with selected manufacturer specifications and connection information.

    PDF · 6 pages · 118.8 KB · Compiled by EWOLO CONTROL. GFK-3003AC AC; January 2024; GFK-3053J J; October 2023

    Preview Product Reference (PDF)

    Order & Service Support

    EWOLO CONTROL is an independent supplier of industrial automation spare parts. See About Us for our company background and Company Qualifications for the published ISO 9001:2015 certificate and supplier assessment records.

    01

    Discontinued & Hard-to-Find Parts

    We source DCS, PLC and TSI spares for maintenance and replacement.

    02

    Order & Payment Confirmation

    Pay by bank transfer before dispatch, unless agreed otherwise in writing.

    03

    Pre-Dispatch Verification

    Model, quantity and visible condition are checked against your order.

    04

    Protective Packaging

    Packaging is selected for the product and agreed shipping method.

    05

    Global Shipping & Tracking

    DHL, FedEx, UPS or an agreed carrier. Tracking follows collection.

    06

    Order Documentation

    Commercial invoice and packing list supplied. Agree extra documents before ordering.

    07

    12-Month Warranty

    Eligible items: 12-month return-to-base warranty from dispatch, per quotation.

    08

    After-Sales Support

    Send fault details and photos. Returns need prior written approval.

    REQUEST A QUOTE

    GE IC695CPL410-AAAA

    Include the part number, required quantity and destination in your enquiry. Add the required hardware series or firmware revision, if applicable.

    Request a Quote   →

    Confirm the offered unit's condition, quantity, included accessories and dispatch time in the quotation.

Send your requirement

Fields marked * are required.

No online payment is requested. Final price and terms are supplied in a written quotation.

leave a message

No online payment is requested. Final price and terms are supplied in a written quotation.